With restructuring of power sector in Pakistan and increase in economic, commercial & industrial
activities, more power utilities and other customers demanded high value packaged solutions for their
Distribution net work, transmission systems, Power generation and enterprise electrification
requirements.
To meet this demand FNP established an Engineering Procurement and Construction division. FNP’s EPC
Division consists of human resource with high academic qualifications and experience of local as well as
global market. The EPC division delivers custom designed and built solutions in following areas:
132kV and 220kV grid stations for power utility companies
132kV and 11kV substations for industrial and commercial customers
Integration of private captive power generation plants into utility network for sale of their
surplus power to utility companies
Power delivery systems for Independent Power Producers (IPPs)
Electrical Plant for, Thermal & Hydro Power Units
Electrification of commercial, housing projects and industrial parks
Security & surveillance system
Our services include:
Design & Engineering
Project Management
Project Execution
Turnkey or customized projects
Automations, Hi-tech Systems & Solution
Field Services for Erection, Testing & Commissioning
Maintenance of Plant/Equipment
In this regards we have ISO certified manufactures / supplier around the world some are mention below;-
Eurogulf Transformer FZC from U.A.E (Manufacturer of Distribution & Power Transformers with collaboration of MACE S.a.s Italy).
HOBUT from England
SEZ - Krompachy from Slovakia
IME from Italy.
Conta-Clip from Germany
RTR Energia from Spain
Conputronics Control from UK
Algodue Elettronica S.R.L from Italy.
Arteche from Spain
Korps from Korea
Nikdim from Bulgaria
Schrack from Austria
1
1
Helukabel GmbH from Germany
Eland from UK
Agro from Switzerland
Cember from Italy
TLA Electrical Distributors Ltd from UK
CAN OZAN PANO from Turkic
Cenit Solar from Spain.
DEIF from UK
Quantum Controls Ltd.
Detail of components & equipments are as under: -
Eurogulf Transformer FZC o Distribution Transformers up to 4000 KVA, up to operational Voltage is 36 KV. o Power Transformer up to 100 MVA, up to operational Voltages is 132 KV. o Multi Tap Transformers to suit from 35Hz to 80Hz frequency System for VSD
application. o Special application motor starting auto transformers with full or intermittent
ratings. o Dry type varnish impregnated transformers for special applications. o Cast resin Transformers up to 5000 KVA.
HOBUT from England
o Analogue/ Digital Ammeters & Volt Meters o Analogue/ Digital PF Meters o Analogue/ Digital Frequency Meters o Analogue/ Digital Mega Var Meters o Analogue/ Digital Mega Watt Meters o Power Transducers o Digital Multi Function Meter M850 o Digital Multi Function Meter M812 o Single Phase Current Transformers (CT’s) o Three Phase Current Transformers (CT’s) o Earth Leakage Relay + CBCT o Earth Fault Relay o Over Current Relay
SEZ - Krompachy from Slovakia
o AC MCB’s o DC MCB’s o Cam/Selector Switches
2
o Rotary Switches o AC Contactor o DC Contactor o Auxiliary Contactor o Auxiliary contact
IME from Italy. o Multifunction Meter o Transducers single & multifunction o Digital Static energy Meters with & without GSM modem. o Differential Relays o Insulation Relays o Measuring Relays. o Current Transformers with built-in transducer.
Conta-Clip from Germany
o Terminal Blocks / Connectors o Earth Terminal Blocks o CT Short Link Terminals o Fuse Terminals o Stoppers & End Plates o Numbering
RTR Energia from Spain
o L.V Capacitors o M.V Capacitors o Power Factor Controllers
Conputronics Control from UK
o Battery Chargers Algodue Elettronica S.R.L from Italy.
o Energy control solutions o Intelligence systems developed for professional security operations and authorized
investigations. o GPS systems solutions for monitoring moving objects, property, people
Arteche from Spain
Korops from Korea
Nikdim from Bulgaria
Schrack from Austria
Helukabel GmbH from Germany
o Control cables copper shielded and unshielded.
o LV Power Cables.
Eland from UK
o Control Cables, Instrumentation Cables.
3
o Power Cables.
Agro from Switzerland
o Cable glands.
Cember from Italy
o Cables lugs – bimetallic
o Cables Terminal Insulated & un-insulated
o Polyamide high temperature Cable ties.
o Steel Cable ties.
TLA Electrical Distributors Ltd from UK
o Eriflex – Low voltage Power Distribution such as Busbar support Flexibar –
insulated busbar up to 2300A.
o Eritech – Facility Electrical Protection
o CADWELD – Electrical Grounding and Bonding.
o CRITEC – Surge Protection devices.
o ERITECH – Grounding Products.
o ERITECH – Lightning Protection Products.
o CADDY – Electrical Fixings, Fasteners and supports.
o CADDY – Mechanical Fixing, Fasteners and supports.
o PULS – DIN Power Supply.
o Fulleon – Sounder & Beacon
o VACON – Inverter Drive.
CAN OZAN PANO from Turkic
o Power distribution panels as IP65, IP55 class.
o Control and automation enclosures as per IP65, IP55 class.
o Synchronization / Parallel gen. set control Panel as IP65, IP55.
o Test Benches as per IP65, IP55.
Cenit Solar from Spain.
o Off grid / On grid Solar system up to 2MWatt.
o Solar water pumping systems – deep well & dewatering.
o Solar Heating system.
DEIF from UK
o Gas engine control unit.
o Generator protection unit.
o Multiple parallel control units.
Quantum Controls Ltd From UK.
o ABB Variable Speed Drives.
o ABB Motors.
o Refurbished Variable Speed derives.
o ABB Motor Gear.
o ABB LV Control Panels (Distribution & Process Control Panels).
4
CONTACTS
Head Office: 155-A, Sarfraz Rafiqui Road, Lahore Cantt, Lahore.
Tel: +92 42 36662054~5
Fax: +92 42 36662053
Name Designation Mobile E-mail
Liaqat Ali Chairman 0333-5898999 rigzoneme@gmail.com
M. Amir Amen CEO - amir@firstnational.com.pk
Akhtar Ali Malik
Executive / Technical
Director 0044-7821043649 malik@firstnational.com.pk
Meshud ul Hassan Technical Director 0321-8491035 mashud@firstnational.com.pk
Engr.Ali Raza Syed Executive / Director 0333-5174770 aliraza@firstnational.com.pk
Qaisar Raza Rana Sales Manager 0344-4451323 rana@firstnational.com.pk
Sanaullah Khan Sales Executive 0344-4451320 sanaullah@firstnational.com.pk
M.Shahid Haroon Estimate Exactive Officer 0344-4451324 shahid@firstnational.com.pk
Miss Aneela Iftikhar Account Officer 042-36662054-55 accounts@firstnational.com.pk
Miss Farina Waheed Customer Care Officer 042-36662054-55 customercare@firstnational.com.pk
Miss Amber Khan Office Attendant Officer 042-36662054-55 missamber@firstnational.com.pk
5
6
Multifunction meters
The art of measuring.
It is the ability of organising and estimating thedata of our everyday experience that makes us toprogress. This estimation is carried out by means of an artwhich enables us to choose among things differentfrom one another by comparing some of theircharacteristics. It is the art of weighing, counting and measuring.
ISTRUMENTI MISURE ELETTRICHE SpA
ISTRUMENTI MISURE ELETTRICHE SpA
7
ISTRUMENTI MISURE ELETTRICHE SpA
ISTRUMENTI MISURE ELETTRICHE SpA
I
Nemo 96 HD Nemo 96 HD
Twins, but differentAs with people, you need only one look to knowthat we are dealing with twins: same physicalstructure, same features, same colour of eyes andhair. But if we want to catch what makes them similarand what distinguishes them, then, as with people, asingle look is no longer enough: we need to knowthem more closely.
Why are different
What distinguishes the two products is definitely the use they are intended for: 96 HD is intended for low voltage applications, while 96 HD+ for both lowand medium voltage applications. This implies some important differences, that is to say, a proper insulation class for voltage and current inputs,
Complete compatibility for optional modules: one module can be installed on any of the two modelswithout limitation; both models can accept up to4 modules at the same time.Same possibility of network connection (single-phase,three-phase 3 or 4 wires).Same reading of measurements and parameterprogramming for the two models; same direct and derived electrical quantities, same energy and time count, same data storing.The software can be updated on field.
Nemo 96 HD+Nemo 96 HD Nemo 96 HD
Nemo 96 HD+
What do have in common
The structure and the mechanical dimensions, the flush mounting fixing system, the expandability of the functions by means of optional modules.The backlit display, characterised by high visibility and information content, and a 4-button keypad for the dialogue man-machine.
bt
and a more complete programming menu that allowsto define specific functioning conditions as, for example, in case of connection by means of current and voltage transformers, linked in medium voltage networks.
MT
8
P•Q•SActive powerReactive powerApparent powerPhase and three-phase instantaneous valueAverage value and average value peak
ICurrentInstantaneous phase and neutral valueHarmonic distortion for phaseAverage value and average value peak
UVoltageInstantaneous valueMin and max valueHarmonic distortion
E•TEnergy counting Total and partial activePositive and negative activeTotal and partial reactivePositive and negative reactivePower factorPhase and three-phase instantaneous valueFrequencyInstantaneous valueHourmeterWorking hour counting
9
Communication interfaceAccording to standard RS 232-C. Communication speed programmable up to 38,400 bit/s.
Communication interfaceAccording to standardPROFIBUS.Communication speedup to 3Mb.
Same modules for: Nemo 96 HD Nemo 96 HD
Communication interfaceAccording to standard RS 485. The protocol used is MODBUS RTU; on demand, implementation of proprietary protocols can be provided.Communication speed programmable up to 38,400 bit/s.
Analogue outputTwo independent andisolated channelswith output current0…20mA and/or 4…20 mA. The association betweenquantities measured and analogue outputs is definedat module’s installation.
Expansion modulesThe seven following expansion modules are available in the kit of Nemo 96 HD and 96 HD+. The modules can be used without limitation on bothmodels, which can accept up to 4 modules each.
Pulse emitter for energy countTwo isolated optorelaysprogrammable independently (time ON and weight of associated energy) foractive and reactive energy. Contacts: SPST-NO.
AlarmsTwo independent and isolated alarm relays with programmable functions.Contacts: SPST.
USCITA CON IMPULSI CONTEGGIO ENERGIA
BUS SPECIALI
USCITA CON ALLARME
COMUNICAZIONEUSCITA ANALOGICA
USCITA CON IMPULSI CONTEGGIO ENERGIA
BUS SPECIALI
USCITA CON ALLARME
COMUNICAZIONEUSCITA ANALOGICA
USCITA CON IMPULSI CONTEGGIO ENERGIA
BUS SPECIALI
USCITA CON ALLARME
COMUNICAZIONEUSCITA ANALOGICA
USCITA CON IMPULSI CONTEGGIO ENERGIA
BUS SPECIALI
USCITA CON ALLARME
COMUNICAZIONEUSCITA ANALOGICA
USCITA CON IMPULSI CONTEGGIO ENERGIA
BUS SPECIALI
USCITA CON ALLARME
COMUNICAZIONEUSCITA ANALOGICA
Neutral currentNeutral currentdirect measure. Programming ofneutral CT ratioindipendent frommeasuring CT’s.
COMUNICAZIONEMULTIMISURA CONTEGGIO ENERGIA CONTROLLO E GESTIOINE
PROTEZIONESENSORI DI CAMPO MISURE CONTROLLOMISURE GRANDEZZE SINGOLE
10
Easy module connectionFixing of optional modules by means of a sliding shutter.The operation requires no screwing.
Mechanics:
Fast mountingPanel fixing system by means of clips.
8162
Reduced depthJust 61mm depth without modules and81mm with mounted modules.
IME is proud and pleased to put on the market
the two latest creations in the already large
family of network devices series Nemo.
Pleased because of the delight always felt
when something new is created, and proud
because of the awareness of creating
products that sum up, from the technical,
functional and esthetical point of view,
the whole experience gained through years
of dedication to the field of electric measurement.
These two products complete our range
proposing flush mounting models
characterised by: high precision, flexibility,
high visibility, clearness of reading
and attention for details.
11
ISTRUMENTI MISURE ELETTRICHE SpA
ISTRUMENTI MISURE ELETTRICHE SpA
Codes
Auxiliary supply
Network
line
Input
voltage
current
frequency
Accuracy class
voltage
current
powers
frequency
active energy
reactive energy
Programmable parameters
connection
average value delay time
display
rated current
CT ratio
VT ratio
Housing
front frame dimensions
depth (without modules)
depth (with modules)
front frame protection degree
Technical Note
Optional modules
energy counting repetition
analogue output
alarm signalling
neutral current
RS485 communication interface
RS232 communication interface
Profibus communication interface
Model Nemo 96 HD+Nemo 96 HD
www.imeitaly.com Via Travaglia 7 20094 Corsico (Mi) Tel.02 44 878.1fax 02 45 03 448 +39 02 45 86 76 63 info@imeitaly.com
low voltage connection on dedicated CT ‘s low and medium voltage
80...265Vac / 110...300Vdc 11...60Vdc
MF96001 MF96002 MF96021 MF96022
single-phase, three-phase 3 or 4 wires
80...500V phase-phase 80...690V phase-phase
1 and 5A
47...63Hz
0,2
0,2
0,5
±0,15Hz
cl.0,5s according to EN62053-22
cl.2 according to EN62053-23
single-phase, three-phase 3 or 4 wires
5 - 8 - 10 - 15 - 20 - 30 - 60 min
contrast and brightness
1 or 5A
1...9999
1...10 1...3000
96 x 96 DIN 43700
62 mm
81 mm
IP54 according to EN60529
2 SPST-NO optorelay pulse outputs
2 indipendent channels 0...20mA and/or 4...20mA
2 indipendent alarms with SPST output
neutral current measure
speed up to 38,400 bit/s
speed up to 38,400 bit/s
speed up to 3 Mb
IME
S.p
.A.
rese
rves
the
rig
ht
tom
od
ify
the
tech
nic
alch
arac
teri
stic
sw
ith
ou
tn
oti
ce.
104/
07Ed
.A08
-W
80...265Vac / 110...300Vdc 11...60Vdc
Technical Note
NT677
NT678
NT679
NT683
NT675
NT676
NT682
Codes
IF96003
IF96004
IF96005
IF96006
IF96001
IF96002
IF96007
NT680 NT681
12
~ NATIONAL TRANSMISSION ANn nESPATCH COMPANY LIMITED
No.CFlSPINTDCU J 666 -I 0
Chief Engineer (System Protection) NTDCLDATED /1,-1 ()c-anl<~
MIS First National Pakistan.28-A, Meera Khan Road, St. John Park1.0hore Cantt
SUDJECT:- APPROVAL OF TRANSDUCERS ]<OR CURRENT (TEMA 14),VOLTAGE ('1'1<:]\1A lJ4) AJI\D ACTIVE PO\VEI~, RRACTIVEPO'VER, APPARENT PO\VJ(J~! l'O\VER FACTOR, PHASEANGLI!: (TEMA fP) - (!\1AKE Jl\IE ITALY)
Rcfr- Your letter No.FNP071l3 dated 27·09·2013
The Transducers of current (TEMA 14), Voltage (TEMA U4) and Active Power,
Reactive Power, Apparent Power, Power Factor, Phase Angle (TEMA fP) - (MA.K.E
lME ITALy) for use in control panels arc hereby Approved for installation III Control
Panels in PEPCO I NTDCL Network. You will provide the necessary literature required
for installation of these transducers.
~~___'~/!.I"'\C.E. (System-Protection) NTDCi
CC re..
I. Chief Engineer (Design) NTDCL, Wapda HO\1~e, Lahore2. All ACE's of this office.
MlflileRlFile
J30·Wnpda House,Lahore,PakistanTF,:+92 42 99202655,Fux:+92 42 99202t84 r..MuiJ:cCSJl@tlldc.gov.pkF.:\Tariq\arshad.doc
13
1mA
1.5 I 2
200 400
0
kW
482
600
300
100 500
kW
Rapporto TA -TVCT -VT ratio
Potenza attivaActive power
Potenza reattivaReactive power
Potenza apparenteApparent power
Fattore di potenzaPower factor
Angolo di fasePhase angle
Potenza mediaMax. demand
FrequenzaFrequency
0...5mA
0...10mA
0...20mA
4...20mA
5...0...5mA
10...0...10mA
20...0...20mA
0...10V
10...0...10V
1...5V
Inserzione diretta fino a 500V Direct connection up to 500V
NT51
4 04
- 20
10 5
aEd
.pag
.1/6
Tema fPTrasduttoreprogrammabile
8 Moduli
Un solo apparecchio per tutte le inserzioni,linea monofase e trifase
Completamente configurabile in campoIngresso tensione trifase diretta fino a 500V
e su TV/100 e 115VIngresso corrente da TA/5A opp. /1A
Misura in vero valore efficace
Misure associabili all’uscita:Potenza attiva
Potenza reattivaPotenza apparenteFattore di potenza
Angolo di fasePotenza media
Frequenza
Uscita realizzabile con tutti i segnali standard
0...5/10/20mA - 4...20mA0...10V - 1...5V
Programmable transducer8 Module
Just one meter for single-phase and 3-phase connectionsWholly field programmableDirect three-phase voltage input up to 500V andthrough V.T. 100 and 115V Current input C.T/5A or /1ATrue R.M.S. measurements
Measured quantity: Active powerReactive powerApparent powerPower factorPhase anglePower demandFrequency
Output possible with all standard signals0...5/10/20mA - 4...20mA0...10V - 1...5V
TRASDUTTORITRANSDUCERS
Grandezza Quantity
Uscita Output
14
MISUREMEASURE
LINEA MONOFASESINGLE PHASE LINE
S250/97
LINEA TRIFASE THREE PHASE
3 FILI EQUILIBRATABALANCED LOAD 3-WIRE
S250/93 S250/100
4 FILI EQUILIBRATABALANCED LOAD 4-WIRE
S250/95
3 FILI SQUILIBRATAUNBALANCED LOAD 3-WIRE
S250/94/96/98
4 FILI SQUILIBRATAUNBALANCED LOAD 4-WIRE
S250/99
Potenza attiva monofaseSingle phase active power •
Potenza attiva L1-NActive power L1-N N •
Potenza attiva L2-NActive power L2-N •
Potenza attiva L3-NActive power L3-N •
Potenza attiva trifaseThree phase active power • • • •Potenza reattiva monofase
Single phase reactive power •Potenza reattiva L1-NReactive power L1-N N •Potenza reattiva L2-NReactive power L2-N •Potenza reattiva L3-NReactive power L3-N •
Potenza reattiva trifaseThree phase reactive power • • • • •
Potenza apparente monofaseSingle phase apparent power •
Potenza apparente L1-NApparent power L1-N N •
Potenza apparente L2-NApparent power L2-N •
Potenza apparente L3-NApparent power L3-N •
Potenza apparente trifaseThree phase apparent power • • • •Fattore di potenza monofase
Single phase power factor •Fattore di potenza L1-N
power factor L1-N N •Fattore di potenza L2-N
power factor L2-N •Fattore di potenza L3-N
power factor L3-N •Fattore di potenza trifaseThree phase power factor • • • •Angolo di fase monofasephase angle, single phase •
Angolo di fase trifasephase angle, three phase • •
Potenza mediapower demand • • • • • •
Valore massimo potenza mediapower max. demand N N N N N N
FrequenzaFrequency • • • • • •
CODICI DI ORDINAZIONEORDERING CODE
INGRESSOINPUT
AL. AUSILIARIA AUX. SUPPLY
TM8P02110 1A 80...500V 115V ca / ac
TM8P02120 5A 80...500V 115V ca / ac
TM8P03110 1A 80...500V 230 - 240V ca / ac
TM8P03120 5A 80...500V 230 - 240V ca / ac
TM8P0H110 1A 80...500V 20...150V cc / dc
TM8P0H120 5A 80...500V 20...150V cc / dc
TM8P0L110 1A 80...500V 150...250V cc / dc
TM8P0L120 5A 80...500V 150...250V cc / dc
NT51
4 04
- 20
10 5
aEd
.pag
.2/6
• Grandezze visualizzate che possono essere trasdotte (associabili all’uscita analogica) Display quantities which can be transduced (which can be associated to the analog output)
N Grandezze solamente visualizzate (non possono essere associabili all’uscita analogica) Quantities displayed only (which cannot be associated to the analog output)
15
INGRESSO
Rete monofase, rete trifase 3 e 4 fili, carico equilibrato squilibratoInserzione: diretta o da TV e TA esterni (con rapporti programmabili)Rapporti TA e TV: programmabili, KTA x KTV ≤ 220.000 (In 5A) - ≤ 2.000.000 (In 1A)Tensione trifase nominale Un: 400V (fase - fase)Tensione monofase: 50...300VCorrente In: 5A oppure 1AFrequenza fn: 50HzEccedenza di breve durata (EN 60688): 2Un/1s - 20In/1sAutoconsumo (per ogni fase): tensione ≤ 0,5VA - corrente 0,5VA
CAMPI NOMINALI DI UTILIZZO (EN 60688)
Tensione trifase: 80...500V (fase - fase)Corrente: 0...120% InFrequenza: 45...65HzFattore di potenza: cosϕ 0,5...1...0,5 − senϕ 0,5...1...0,5Contenuto armonico: fino alla 16a armonica
IMPOSTAZIONE CAMPO DI USCITA
Programmabile: tramite tastieraPotenza corrispondente al fondo scala: 50...150% PnMinimo ∆ inizio - fondo scala: 25% Pndove:Pn (potenza nominale) = Un x In x √3Un (tensione nominale) = 400V (inserz. diretta) - 100V (inserz.su TV esterno)In (corrente nominale) = 5A oppure 1A
POTENZA MEDIA
Visualizzazione e misura: potenza media e valore massimo potenza mediaGrandezza: potenza attiva, reattiva o apparenteTempo di media: selezionabile 5/8/10/15/20/30/60 minutiCalcolo: media fissa sul periodo selezionatoAzzeramento valore massimo potenza media: manuale, da tastiera
VISUALIZZAZIONE
Tipo display: LCDVisualizzazione misure: suddivisa in differenti pagine, con scansione manualeUnità ingegneristica: visualizzazione automatica misure lato primario (TA-TV esterni)
PROGRAMMAZIONE
Programmazione parametri: tastiera frontale, 3 tastiConservazione parametri di configurazione: memoria permanente
PARAMETRI PROGRAMMABILI
Connessione: rete monofase - trifase (3 - 4fili), carico equilibrato - squilibratoTA -TV esterni: rapporto KTA x KTV ≤ 220.000 (In 5A) - ≤ 900.000 (In 1A)Uscita analogica: grandezza associata, inizio e fondo scala, valore nominale dicorrente (o tensione)Potenza media: grandezza, tempo di media, azzeramento
USCITA
Grandezze associabili: vedi tabellaTipo: uni e bidirezionale a zero reale e traslato, per carico d'uscita variabilePrecisione (EN 60688): cl.0,5 (potenza) - cl.1 (fattore di potenza) - ± 0,2Hz (frequenza)Ondulazione (EN 60688): ≤ 1%Tempo di risposta (EN 60688): ≤ 300msValori nominali di corrente: 0...5 - 5...0...5 - 0...10 - 10...0...10 -
0...20 - 20...0...20- 4...20mATensione disponibile: 16,5VCarico di uscita: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)
INPUT
Single phase, three phase network, 3 and 4 wire, balanced and unbalanced loadConnection: direct or by external VT and CT (with programmables ratios)VT and CT ratios: programmables, KVT x KCT ≤ 220.000 (In 5A) - ≤ 2.000.000 (In 1A)Three-phase voltage rating Un: 400V (phase – phase)Single-phase voltage: 50...300VCurrent rating In: 5A or 1AFrequency fn: 50HzExcessive input of short duration (EN 60688): 2Un/1s - 20In/1sRated burden (each phase): voltage ≤ 0,5VA - current ≤ 0,5VA
NOMINAL RANGE OF USE (EN 60688)
Voltage three-phase: 80...500V (phase – phase)Current: 0...120% InFrequency: 45...65HzPower factor: cosϕ 0,5...1...0,5- senϕ 0,5...1...0,5 Harmonic content: up to 16th harmonic
OUTPUT RANGE SETTING
Programmable: by keyPower corresponding to full scale: 50...150% pn∆ min. beginning - full scale: 25% pnwhere:Pn (nominal power) = Un x In x √3Un (nominal voltage) = 400V (direct connection) - 100V (external VT)In (nominal current) = 5A or 1A
POWER DEMAND
Measuring and display: power demand and power max. demandQuantity: active, reactive or apparent powerAveraging time period: selectable 5/8/10/15/20/30/60 minutesCalculation: Average on a selected time intervalMax. demand reset: manual, by keyboard
DISPLAY
Display type: LCDMeasurement display: subdivided on pages, with manual scrollEngineering units: automatic display according to the set VT and CT ratios
PROGRAMMING
Parameters programming: front keyboard, 3 keysHold of configuration parameters: non volatile memory
PROGRAMMABLE PARAMETERS
Connection: single phase - three phase network (3 - 4wire), balanced andunbalanced load External VT - CT: ratio KTA x KTV ≤ 220.000 (In 5A) - ≤ 900.000 (In 1A)Analog output: transduced quantity, beginning and full scale, standard outputPower demand: quantity, averaging time period, reset
OUTPUT
Associable quantities: see tableType: unidirectional and reversible, real or live zero for variable output loadAccuracy (EN 60688): cl.0,5 (power) - cl.1 (power factor) - ± 0,2Hz (frequency)Ripple content (EN 60688): ≤ 1%Response time (EN 60688): ≤ 300msCurrent rated values: 0...5 - 5...0...5 - 0...10 - 10...0...10 -
0...20 - 20...0...20- 4...20mACompliance voltage: 16,5VOutput load: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)
NT51
4 04
- 20
10 5
aEd
.pag
.3/6
16
Valori nominali di tensione: 0...10V - 10...0...10 - 1...5VCarico di uscita: ≥ 5kΩ
ALIMENTAZIONE AUSILIARIA
Valore nominale Uaux ca: 115 – 230 e 240VVariazione ammessa: 0,85…1,1UauxFrequenza nominale faux: 50HzVariazione ammessa: 47…63HzAutoconsumo: ≤ 3VAValore nominale Uaux cc: 20…150Vcc -150...250VccAutoconsumo: ≤ 3WProtezione contro l’inversione di polarità
PROVE DI ISOLAMENTO (EN 60439-1)
Categoria di installazione: IIIGrado di inquinamento: 2Tensione di riferimento per l’isolamento: 500VProva di tensione a impulso 5kV 1,2/50μs 0,5JCircuiti considerati: ingresso, uscita, alimentazione ausiliariaProva di tensione alternata 2,5kV valore efficace 50Hz/1 minCircuiti considerati: ingr.tensione, ingr.corrente, uscita, alimentazione ausiliaria Prova di tensione alternata 4kV valore efficace 50Hz/1 minCircuiti considerati: alimentazione ausiliaria verso tutti gli altri circuitiProva di tensione alternata 4kV valore efficace 50Hz/1 minCircuiti considerati: tutti i circuiti e massa
COMPATIBILITA' ELETTROMAGNETICA
Prove di emissione in accordo con EN61000-6-3Prove di immunità in accordo con EN61000-6-2
CONDIZIONI AMBIENTALI (EN 60688)
Gruppo di utilizzo: IITemperatura di riferimento: 15...30°CTemperatura di impiego: 0...50°CCondizione limite di temperatura: -10...55°C Temperatura di immagazzinaggio: -25...70°CAdatto all’utilizzo in clima tropicaleMassima potenza dissipata 1: ≤ 4,8W1 Per il dimensionamento termico dei quadri
CUSTODIA
Dimensioni: 8 moduli DIN 43880Connessioni: morsetti a vite per conduttore fino a 4mm2 (amperometriche 8mm 2)Montaggio: a incastro su profilato 35mmTipo profilato: a cappello TH35-15 (EN60715)Materiale custodia: policarbonato autoestinguenteGrado di protezione (EN 60529): IP52 (frontale), IP20 (morsetti)Peso: 480 grammi
Voltage rated values: 0...10V - 10...0...10 - 1...5VOutput load: > 5kΩ
AUXILIARY SUPPLY
Rated value Uaux ac: 115 – 230 and 240VTolerance: 0,85…1,1UauxRated frequency faux: 50HzTolerance: 47…63HzRated burden: ≤ 3VARated value Uaux dc: 20…150Vdc -150...250VdcRated burden: ≤ 3WProtected against incorrect polarity
TESTS OF INSULATION PROPERTIES (EN 60439-1)
Installation category: IIIPollution degree: 2Insulation voltage rating: 500VImpulse voltage test 5kV 1,2/50μs 0,5JConsidered circuits: input, output, auxiliary supply A.C. voltage test 2,5kV r.m.s. 50Hz/1 minConsidered circuits: voltage input , current input, output, auxiliary supplyA.C. voltage test 4kV r.m.s. 50Hz/1minConsidered circuits: auxiliary supply toward all circuitsA.C. voltage test 4kV r.m.s. 50Hz/1minConsidered circuits: all circuits and earth
ELECTROMAGNETIC COMPATIBILITY
Emission test according to EN61000-6-3Immunity test according to EN61000-6-2
ENVIRONMENTAL CONDITIONS (EN 60688)
Usage group: IIReference temperature: 15...30°CNominal temperature range: 0...50°CLimit temperature range: -10...55°CLimit temperature range for storage: -25...70°CSuitable for tropical climatesMax. power dissipation 1: ≤ 4,8W1 For switchboard thermal calculation
HOUSING
Dimensions: 8 module DIN 43880Connections: screw terminals for cable up to 4mm 2 (ammetric 8mm 2)Mounting: snap-on 35mm rail Rail type: top hat TH35-15 (EN60715)Housing material: self-extinguishing policarbonateProtection degree (EN 60529): Ip52 (front frame); Ip20 (terminals)Weight: 480 grams
NT51
4 04
- 20
10 5
aEd
.pag
.4/6
17
SCHEMI D’INSERZIONE WIRING DIAGRAMS
2 5 7 9
OUTPUTINPUT
8 4 61 3
X
S1
P1L
N
11
2 11
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
NT51
4 04
- 20
10 5
aEd
.pag
.5/6
2 5 7 98 4 61 3
X
XX
2 5 8
S1
P1
a
AL1
L2
L3
11
2 5 8
OUTPUTINPUT
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
OUTPUT
1214 15
OUTPUT
17 131214 1517
+ -mA- V
13
+ -mA- V
V mA
2 5 7 98 4 61 3
XXX
X
XX
2 5 8
S1
P1
a
AL1
L2
L3
N
11
11
OUTPUTINPUT
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
USCITA ANALOGICA ANALOG OUTPUT
LINEA MONOFASE • SINGLE PHASE
LINEA TRIFASE 3 FILI, CARICO EQUILIBRATO
THREE PHASE 3 WIRE, BALANCED LOAD
LINEA TRIFASE 4 FILI, CARICO EQUILIBRATO
THREE PHASE 4 WIRE, BALANCED LOAD
2 5 7 98 4 61 3
X
XX
S1
P1L1
L3
11
5 8
L2
OUTPUTINPUT
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
S 250/97
S 250/93
S 250/100
S 250/95
18
La I.M
.E. S
.p.A.
si ris
erva
in qu
alsias
i mom
ento,
di m
odific
are l
e car
atter
istich
e tec
niche
senz
a dar
ne pr
eavv
iso. /
I.M.E
. S.p.
A. re
serve
s the
right,
to m
odify
the t
echn
ical c
hara
cteris
tics w
ithou
t noti
ce.
NT51
4 04
- 20
10 5
aEd
.pag
.6/6
2 5 7 98 4 61 3
X
XX
2 5 8
a
AL1
L2
L3
11
2 5 8
S1
P1
S1
P1
OUTPUTINPUT
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
2 5 7 98 4 61 3
X
XX
2 5 8
S1
P1
a
AL1
L2
L3
11
2 5 8
S1
P1
OUTPUTINPUT
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
2 5 7 98 4 61 3
X
XX
2 5 8
S1
P1
a
AL1
L2
L3
11
2 5 8
S1
P1
OUTPUTINPUT
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
LINEA TRIFASE 3 FILI, CARICO SQUILIBRATO
THREE PHASE 3 WIRE, UNBALANCED LOAD
140
89,5
69
45
DIMENSIONI DIMENSIONS
2 5 7 98 4 61 3
XXX
X
XX
2 5 8
S1
P1 S1
P1 S1
P1
a
AL1
L2
L3
N
11
11
OUTPUTINPUT
1214 1517
+ -mA- V
13 20
AUX.SUPPLY
2121+ –CURRENTVOLTAGE
LINEA TRIFASE 4 FILI, CARICO SQUILIBRATO
THREE PHASE 4 WIRE, UNBALANCED LOAD
S 250/99
S 250/94
S 250/96
S 250/98
19
1.5 I 2
200 400
0
V
482
600
300
100 500
V
0...5mA
0...10mA
0...20mA
4...20mA
0...5V
0...10V
2...10V
NT555 03 - 2011 8aEd.pag.1/3
Tema U4Trasduttore di tensione alternata
2 Moduli
Misura del valor medio, taratura rapportata al valore efficace
Ingresso diretto fino a 500VUscita selezionabile in campo (7 portate)
Valori selezionabili: 0…5/10/20mA - 4…20mA
0…5/10V - 2…10V
Alternating voltage transducer2 Module
To measure average value, calibration according RMS valueDirect input up to 500VOutput selectable on field (7 ranges)
Selectable values: 0…5/10/20mA - 4…20mA 0…5/10V - 2…10V
TRASDUTTORITRANSDUCERS
Inserzione diretta o su TV/100V o TV/110V
Direct connection or on VT/100V or VT/110V
Uscita Output
20
INGRESSO
Tensione nominale Un: 100 - 110 - 120 - 250 - 400 - 500V
Altri valori a richiesta
Frequenza nominale fn: 50Hz
Eccedenza di breve durata (EN 60688): 2Un/1s (max 600V)
Autoconsumo: ≤ 0,5VA
CAMPI NOMINALI DI UTILIZZO (EN 60688)
Frequenza: 47…63Hz (fn 50Hz)
Forma d'onda: sinusoidale, fattore di forma 1,11
INTERVALLO DI MISURA
Tensione: 0...120% Un
USCITA
Tipo: unidirezionale a zero reale, per carico d'uscita variabile
Precisione (EN 60688): classe 0,5
Ondulazione (EN 60688): ≤ 1%Tempo di risposta (EN 60688): ≤ 300 msValore nominale: selezionabile tramite dip switch (7 portate)
Valori nominali di corrente: 0…5 - 0…10 - 0…20mA - 4...20mA
Tensione disponibile: 15V
Carico di uscita: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)Valori nominali di tensione: 0…5 - 0…10 - 2…10V
Carico di uscita: ≥ 5kΩ
INPUT
Voltage rating Un: 100 - 110 -120 - 250 - 400 - 500V
Other values on request
Frequency rating fn: 50Hz
Excessive input of short duration (EN 60688): 2Un/1s (max 600V)
Rated burden: ≤ 0,5VA
NOMINAL RANGE OF USE (EN 60688)
Frequency: 47…63Hz (fn 50Hz)
Waveform: sinusoidal, form factor 1,11
MEASURING RANGE
Voltage: 0...120% Un
OUTPUT
Type: unidirectional, real or live zero for variable output load
Accuracy (EN 60688): class 0,5
Ripple content (EN 60688): ≤ 1%
Response time (EN 60688): ≤ 300 ms
Rated value: selectable by dip switch (7 ranges)
Current rated values: 0…5 - 0…10 - 0…20mA - 4...20mA
Compliance voltage: 15V
Output load: ≤ 750Ω (20mA) - ≤ 1,5kΩ(10mA) - ≤ 3kΩ (5mA)
Voltage rated values: 0…5 - 0…10 - 2…10V
Output load: ≥ 5kΩ NT555 03 - 2011 8aEd.pag.2/3
CODICI DI ORDINAZIONEORDERING CODE
INGRESSOINPUT
AL. AUSILIARIA AUX. SUPPLY
TM3U210 100V 115V ca / ac
TM3U220 110V 115V ca / ac
TM3U230 120V 115V ca / ac
TM3U270 250V 115V ca / ac
TM3U290 400V 115V ca / ac
TM3U2A0 440V 115V ca / ac
TM3U2C0 500V 115V ca / ac
TM3U310 100V 230 - 240V ca / ac
TM3U320 110V 230 - 240V ca / ac
TM3U330 120V 230 - 240V ca / ac
TM3U370 250V 230 - 240V ca / ac
TM3U390 400V 230 - 240V ca / ac
TM3U3A0 440V 230 - 240V ca / ac
TM3U3C0 500V 230 - 240V ca / ac
TM3UH10 100V 20...150V cc / dc
TM3UH20 110V 20...150V cc / dc
TM3UH30 120V 20...150V cc / dc
TM3UH70 250V 20...150V cc / dc
TM3UH90 400V 20...150V cc / dc
TM3UHA0 440V 20...150V cc / dc
TM3UHC0 500V 20...150V cc / dc
TM3UL10 100V 150...250V cc / dc
TM3UL20 110V 150...250V cc / dc
TM3UL30 120V 150...250V cc / dc
TM3UL70 250V 150...250V cc / dc
TM3UL90 400V 150...250V cc / dc
TM3ULA0 440V 150...250V cc / dc
TM3ULC0 500V 150...250V cc / dc
TM3U2P0 da precisare / on request 115V ca / ac
TM3U3P0 da precisare / on request 230 - 240V ca / ac
TM3UHP0 da precisare / on request 20...150V cc / dc
TM3ULP0 da precisare / on request 150...250V cc / dc
21
ALIMENTAZIONE AUSILIARIA
Valore nominale Uaux ca: 48 - 115 – 230 e 240V
Altri valori a richiesta
Variazione ammessa: 0,9…1,1Uaux – 40...60V (Uaux 48V)
Frequenza nominale faux: 50Hz
Variazione ammessa: 47…63Hz
Autoconsumo: ≤ 3VAValore nominale Uaux cc: 20…150Vcc – 150…250Vcc
Autoconsumo: ≤ 1,5WProtezione contro l’inversione di polarità
ISOLAMENTO (EN 60439-1, EN61010-1)
Categoria di installazione: III
Grado di inquinamento: 2
Tensione di riferimento per l’isolamento: 600V
Prova di tensione a impulso 5kV 1,2/50µs 0,5J
Circuiti considerati: ingresso, uscita, al. ausiliaria
Prova a tensione alternata 2,5kV valore efficace 50Hz/1min
Circuiti considerati: ingresso, uscita, al. ausiliaria
Prova a tensione alternata 4kV valore efficace 50Hz/1min
Circuiti considerati: tutti i circuiti e massa
COMPATIBILITA' ELETTROMAGNETICA
Prove di emissione in accordo con EN 50081-1, EN 55011
Prove di immunità in accordo con EN 50082-2
Prova di disturbo ad alta frequenza, onda oscillatoria smorzata 1MHz (IEC255-4)
Tensione di prova: 2,5kV modo comune, 1kV modo serie
CONDIZIONI AMBIENTALI
Gruppo di utilizzo: II
Temperatura di riferimento: 15…30°C
Temperatura di impiego: 0…45°C
Condizione limite di temperatura: -10…55°C
Temperatura di magazzinaggio: -25…70°C
Umidità relativa: fino a 75%
Adatto all’utilizzo in clima tropicale
Massima potenza dissipata 1: ≤ 2,6W1Per il dimensionamento termico dei quadri
CUSTODIA
Dimensioni: 2 moduli DIN 43880
Connessioni: morsetti fissaggio a vite per conduttore fino a 4 mm2
Montaggio: a incastro su profilato 35mm
Tipo profilato: a cappello TH35-15 (EN60715)
Materiale custodia: makrolon autoestinguente
Grado di protezione (EN 60529): IP40 (frontale), IP20 (morsetti)
Peso: 200 grammi
AUXILIARY SUPPLY
Rated value Uaux ac: 48 - 115 – 230 and 240V
Other value on request
Tolerance: 0,9…1,1Uaux – 40...60V (Uaux 48V)
Rated frequency faux: 50Hz
Tolerance: 47…63Hz
Rated burden: ≤ 3VA
Rated value Uaux dc: 20…150Vdc – 150…250Vdc
Rated burden: ≤ 1,5W
Protected against incorrect polarity
INSULATION (EN 60439-1, EN61010-1)
Installation category: III
Pollution degree: 2
Insulation reference voltage: 600V
Impulse voltage test 5kV 1,2/50µs 0,5J
Considered circuits: input, output, aux. supply
A.C. voltage test 2,5kV r.m.s. 50Hz/1min
Considered circuits: input, output, aux. supply
A.C. voltage test 4kV r.m.s. 50Hz/1min
Considered circuits: all circuits and earth
ELECTROMAGNETIC COMPATIBILITY
Emission tests according to EN 50081-1, EN 55011
Immunity tests according to EN 50082-2
High frequency disturbance test, 1MHz damped oscillatory wave (IEC255-4)
Test voltage: 2,5kV common mode, 1kV series mode
ENVIRONMENTAL CONDITIONS
Usage group: II
Reference temperature: 15…30°C
Nominal temperature range: 0…45°C
Limit temperature range: -10…55°C
Limit temperature range for storage: -25…70°C
Relative humidity: up to 75%
Suitable for tropical climates
Max. power dissipation 1 : ≤ 2,6W1For switchboard thermal calculation
HOUSING
Dimensions: 2 module DIN 43880
Connections: screw terminals for cable up to 4 mm 2
Mounting: snap-on 35mm rail
Rail type: top hat TH35-15 (EN60715)
Housing material: self-extinguishing makrolon
Protection degree (EN 60529): IP40 (front frame), IP20 (terminals)
Weight: 200 gramsLa I.M.E. S.p.A. si riserva in qualsiasi mom
ento, di modificare le caratteristiche tecniche senza darne preavviso. / I.
M.E
. S.p
.A. r
eser
ves
the
right
, to
mod
ify th
e te
chni
cal
char
acte
ristic
s w
ithou
t not
ice.
SCHEMA D’INSERZIONE WIRING DIAGRAM DIMENSIONI DIMENSIONS
1 3
aA
bB
INPUT
mA V
1719
OUTPUT
– + –
1 3 20
AUX.SUPPLY
21(+) (–)
18
∼
NT555 03 - 2011 8aEd.pag.3/3
S 306/24
22
1mA
1.5 I2
200 400
0
A
482
600
300
100 500
A
0...5mA
0...10mA
0...20mA
4...20mA
0...5V
0...10V
2...10V
NT5
5402
-200
87a
Ed.
pag.
1/3
Tema I4Trasduttore di corrente alternata
2 Moduli
Misura del valor medio, taratura rapportata al valore efficace
Ingresso su TA/1A - TA/5AUscita selezionabile in campo (7 portate)
VVaalloorrii sseelleezziioonnaabbiillii:: 0…5/10/20mA - 4…20mA
0…5/10V - 2…10V
Alternating current transducer2 Module
To measure average value, calibration according RMS valueInput on CT/1A - CT/5AOutput selectable on field (7 ranges)
SSeelleeccttaabbllee vvaalluueess:: 0…5/10/20mA - 4…20mA 0…5/10V - 2…10V
TRASDUTTORITRANSDUCERS
Inserzione su TA/1A o TA/5A Connection up to CT/1A or CT/5A
Uscita Output
23
INGRESSO
Corrente nominale In: 1 - 1,2 - 5 - 6A
Frequenza nominale fn: 50 - 400Hz
Eccedenza di breve durata (EN 60688): 20In/1s
Eccedenza continua: 3In
Autoconsumo: ≤ 0,2VA
CAMPI NOMINALI DI UTILIZZO (EN 60688)
Frequenza: 47…63Hz (fn 50Hz)
Forma d'onda: sinusoidale, fattore di forma 1,11
INTERVALLO DI MISURA
Corrente: 0…120%In
USCITA
Tipo: unidirezionale a zero reale o traslato, per carico d'uscita variabile
Precisione (EN 60688): classe 0,5
Ondulazione (EN 60688): ≤ 1%
Tempo di risposta (EN 60688): ≤ 300 ms
Valore nominale: selezionabile tramite dip switch (7 portate)
Valori nominali di corrente: 0…5 - 0…10 - 0…20mA - 4...20mA
Tensione disponibile: 15V
Carico di uscita: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)
Valori nominali di tensione: 0…5 - 0…10 - 2…10V
Carico di uscita: ≥ 5kΩ
ALIMENTAZIONE AUSILIARIA
Valore nominale Uaux ca: 48 - 115 – 230 e 240V
Altri valori a richiesta
Variazione ammessa: 0,9…1,1Uaux – 40...60V (Uaux 48V)
Frequenza nominale faux: 50Hz
Variazione ammessa: 47…63Hz
Autoconsumo: ≤ 3VA
Valore nominale Uaux cc: 20…150Vcc – 150…250Vcc
Autoconsumo: ≤ 1,5W
Protezione contro l’inversione di polarità
ISOLAMENTO (EN 60439-1)
Categoria di installazione: III
Grado di inquinamento: 2
Tensione di riferimento per l’isolamento: 450V
Prova di tensione a impulso 5kV 1,2/50µs 0,5J
Circuiti considerati: ingresso, uscita, al. ausiliaria
Prova a tensione alternata 2,5kV valore efficace 50Hz/1min
Circuiti considerati: ingresso, uscita, al. ausiliaria
Prova a tensione alternata 4kV valore efficace 50Hz/1min
Circuiti considerati: tutti i circuiti e massa
INPUT
Current rating In: 1 - 1,2 - 5 - 6A
Frequency rating fn: 50 - 400Hz
Excessive input of short duration (EN 60688): 20In/1s
Continuous excessive input: 3In
Rated burden: ≤ 0,2VA
NOMINAL RANGE OF USE (EN 60688)
Frequency: 47…63Hz (fn 50Hz)
Waveform: sinusoidal, form factor 1,11
MEASURING RANGE
Current: 0…120%In
OUTPUT
Type: unidirectional, real or live zero for variable output load
Accuracy (EN 60688): class 0,5
Ripple content (EN 60688): ≤ 1%
Response time (EN 60688): ≤ 300 ms
Rated value: selectable by dip switch (7 ranges)
Current rated values: 0…5 - 0…10 - 0…20mA - 4...20mA
Compliance voltage: 15V
Output load: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)
Voltage rated values: 0…5 - 0…10 - 2…10V
Output load: ≥ 5kΩ
AUXILIARY SUPPLY
Rated value Uaux ac: 48 - 115 – 230 and 240V
Other value on request
Tolerance: 0,9…1,1Uaux – 40...60V (Uaux 48V)
Rated frequency faux: 50Hz
Tolerance: 47…63Hz
Rated burden: ≤ 3VA
Rated value Uaux dc: 20…150Vdc – 150…250Vdc
Rated burden: ≤ 1,5W
Protected against incorrect polarity
INSULATION (EN 60439-1)
Installation category: III
Pollution degree: 2
Insulation reference voltage: 450V
Impulse voltage test 5kV 1,2/50µs 0,5J
Considered circuits: input, output, aux. supply
A.C. voltage test 2,5kV r.m.s. 50Hz/1min
Considered circuits: input, output, aux. supply
A.C. voltage test 4kV r.m.s. 50Hz/1min
Considered circuits: all circuits and earth NT5
54
02 -
2008
7a
Ed.
pag.
2/3
CODICI DI ORDINAZIONEORDERING CODE
INGRESSOINPUT
AL. AUSILIARIA AUX. SUPPLY
TM3I210 1A 115V ca / ac
TM3I230 5A 115V ca / ac
TM3I310 1A 230 - 240V ca / ac
TM3I330 5A 230 - 240V ca / ac
TM3IH10 1A 20...150V cc / dc
TM3IH30 5A 20...150V cc / dc
TM3IL10 1A 150...250V cc / dc
TM3IL30 5A 150...250V cc / dc
24
ELECTROMAGNETIC COMPATIBILITY
Emission tests according to EN 50081-1, EN 55011
Immunity tests according to EN 50082-2
High frequency disturbance test, 1MHz damped oscillatory wave (IEC255-4)
Test voltage: 2,5kV common mode, 1kV series mode
ENVIRONMENTAL CONDITIONS
Usage group: II
Reference temperature: 15…30°C
Nominal temperature range: 0…45°C
Limit temperature range: -10…55°C
Limit temperature range for storage: -25…70°C
Relative humidity: up to 75%
Suitable for tropical climates
Max. power dissipation 1: ≤ 2,6W1For switchboard thermal calculation
HOUSING
Dimensions: 2 module DIN 43880
Connections: screw terminals for cable up to 4mm 2
Mounting: snap-on 35mm rail
Rail type: top hat TH35-15 (EN60715)
Housing material: self-extinguishing makrolon
Protection degree (EN 60529): IP40 (front frame), IP20 (terminals)
Weight: 200 grams
NT5
54
02 -
2008
7a
Ed.
pag.
3/3
La I.
M.E
. S.p
.A. s
i ris
erva
in q
uals
iasi
mom
ento
, di m
odifi
care
le c
arat
teris
tiche
tecn
iche
sen
za d
arne
pre
avvi
so. /
I.M
.E. S
.p.A
. res
erve
s th
e rig
ht, t
o m
odify
the
tech
nica
l ch
arac
teris
tics
with
out n
otic
e.
SCHEMA D’INSERZIONE WIRING DIAGRAM DIMENSIONI DIMENSIONS
mA V
L
N
S1
P1
1 3
INPUT
1719
OUTPUT
– + –
1 3 20
AUX.SUPPLY
2121(+) (–)
18
S 306/23
COMPATIBILITA' ELETTROMAGNETICA
Prove di emissione in accordo con EN 50081-1, EN 55011
Prove di immunità in accordo con EN 50082-2
Prova di disturbo ad alta frequenza, onda oscillatoria smorzata 1MHz (IEC255-4)
Tensione di prova: 2,5kV modo comune, 1kV modo serie
CONDIZIONI AMBIENTALI
Gruppo di utilizzo: II
Temperatura di riferimento: 15…30°C
Temperatura di impiego: 0…45°C
Condizione limite di temperatura: -10…55°C
Temperatura di magazzinaggio: -25…70°C
Umidità relativa: fino a 75%
Adatto all’utilizzo in clima tropicale
Massima potenza dissipata1: ≤ 2,6W1Per il dimensionamento termico dei quadri
CUSTODIA
Dimensioni: 2 moduli DIN 43880
Connessioni: morsetti fissaggio a vite per conduttore fino a 4mm2
Montaggio: a incastro su profilato 35mm
Tipo profilato: a cappello TH35-15 (EN60715)
Materiale custodia: makrolon autoestinguente
Grado di protezione (EN 60529): IP40 (frontale), IP20 (morsetti)
Peso: 200 grammi
25
NT791 01 - 2013 0 Ed.
pag.1/4
ANIndicatori AnalogiciAQMrad
per tensione alternata48x48mm72x72mm96x96mm
Indicazione diretta della tensione di ingresso odella tensione primaria del TV esterno
Equipaggio a bobina mobile,con accessorio raddrizzatoreIngresso diretto da 10 a 600V
Ingresso da TV esterno /100V - /110VAmpiezza scala 240°
Precisione cl.1,5
AQMradAnalog Meters for alternating voltage48x48mm72x72mm96x96mm
Direct indication of input voltage or primaryvoltage of external VTMoving coil equipmentwith rectifier accessoryDirect connection 10...600VInput by external VT /100V - /110VScale lenght 240°Accuracy class 1,5
INDICATORI ANALOGICIANALOG METERS
Scala intercambiabileInterchange scales
AQ72Mrad - AQ96Mrad Coprimorsetto di serieStandard terminal cover
26
Opzione / Option Suffisso / Suffix Esempio / Example
TropicalizzatoTropicalized
Aggiungere “1” al codice standardAdd “1” at the end of standard code AN65DDC300 ⇒ AN65DDC3001
Protezione frontale IP54IP54 Front protection
Aggiungere “3” al codice standardAdd “3” at the end of standard code AN65DDC300 ⇒ AN65DDC3003
Altre esecuzioni disponibili su tutti i modelli: Other executions available on all models:
NT791 01 - 2013 0 Ed.
pag.2/4
INSERZIONE SU TV
Dati da indicare oltre al codice di ordinazione
Scala e rapporto TV
Il valore della scala dovrà corrispondere al prodotto tra il valore di portata
scelto e il rapporto del TV
Es. portata 120V – rapporto TV 500/100V = valore scala = (120 x 500) : 100 = 600V
Solo per cod. AN54P11111 - AN64P11111 - AN74P11111: scala e rapporto TV
Es. scala 0...300V – rapporto TV 230/100V
VISUALIZZAZIONE
Scala: intercambiabile, con inserimento guidato a protezione dell’indice e cassettino
di chiusura
Colore scala: fondo bianco, divisioni e numerazione nere
A richiesta scale personalizzate
Opzioni: segno rosso di riferimento
Ampiezza scala: 240°
Tracciatura standard: 0...Un
Colore indice: nero
Opzione: indice rosso di riferimento (regolabile)
CONNECTION ON VT
Data to be shown in addition to ordering code
Scale and VT ratio
The scale value must correspond to the result between the chosen range
value and the VT ratio
Ex. range 120V – VT ratio 500/100V = scale value = (120 x 500) : 100 = 600V
Only for code AN54P11111 - AN64P11111 - AN74P11111: scale and VT ratio
Ex. scale 0...300V – VT ratio 230/100V
DISPLAY
Scale: interchangeable, easy-insertion to protect the pointer as wellas relevant
closing slip
Scale colour: white background, black divisions and numbering
Customized scales upon request
Option: reference red mark
Scale length: 240°
Standard scale marking: 0...Un
Pointer colour: black
Option: (adjustable) reference red pointer
InserzioneConnection 0...In - DIRETTA / DIRECT
ModelloModel AQ48Mrad AQ72Mrad AQ96Mrad
DimensioniDimensions 48 x 48 72 x 72 96 x 96
PortataRange CODICE DI ORDINAZIONE / ORDERING CODE
10V AN54DDB100 AN64DDB100 AN74DDB100
15V AN54DDB150 AN64DDB150 AN74DDB150
25V AN54DDB250 AN64DDB250 AN74DDB250
30V AN54DDB300 AN64DDB300 AN74DDB300
40V AN54DDB400 AN64DDB400 AN74DDB400
60V AN54DDB600 AN64DDB600 AN74DDB600
100V AN54DDC100 AN64DDC100 AN74DDC100
150V AN54DDC150 AN64DDC150 AN74DDC150
200V AN54DDC200 AN64DDC200 AN74DDC200
250V AN54DDC250 AN64DDC250 AN74DDC250
300V AN54DDC300 AN64DDC300 AN74DDC300
400V AN54DDC400 AN64DDC400 AN74DDC400
500V AN54DDC500 AN64DDC500 AN74DDC500
600V AN54DDC600 AN64DDC600 AN74DDC600
InserzioneConnection da TV / on VT
ModelloModel AQ48Mrad AQ72Mrad AQ96Mrad
DimensioniDimensions 48 x 48 72 x 72 96 x 96
PortataRange CODICE DI ORDINAZIONE / ORDERING CODE
100V AN54111111 AN64111111 AN74111111
120V AN54211111 AN64211111 AN74211111
125V AN54311111 AN64311111 AN74311111
131,58V AN54411111 AN64411111 AN74411111
133,33V AN54511111 AN64511111 AN74511111
136,36V AN54611111 AN64611111 AN74611111
150V AN54711111 AN64711111 AN74711111
altri valoriother values
AN54P11111 AN64P11111 AN74P11111
27
NT791 01 - 2013 0 Ed.
pag.3/4
INGRESSO
Grandezza: tensione alternata monofase
Inserzione: diretta (S 250/124 - /141) o da TV esterno (S 250/125 - /142)
Misura: valor medio, rapportato al valore efficace, fattore di forma 1,11
Tensione nominale Un
Inserzione diretta: 10...600V
Inserzione da TV esterno: TV/100V - TV/110V
Sovraccarico permanente: 1,2Un
Sovraccarico istantaneo: 10Un/5s
Frequenza nominale fn: 50Hz
Frequenza di funzionamento: 45...65Hz
Precisione (EN/IEC 60051): cl.1,5
Autoconsumo: ≃1mA
ISOLAMENTO (EN/IEC 61010-1)
Categoria di installazione: III
Grado di inquinamento: 2
Tensione di riferimento per l’isolamento: 600V (Fase - Neutro)
Prova a tensione alternata 4kV valore efficace 50Hz/5s
Circuiti considerati: tutti i circuiti verso terra
CONDIZIONI AMBIENTALI
Temperatura di riferimento: 23°C
Campo nominale di utilizzo: 5...40°C
Campo di funzionamento: -25...50°C
Campo limite per l’immagazzinamento e trasporto: -40...80°C
Prova di vibrazioni: in accordo con EN/IEC 60051-1 paragrafo 7.6
Prova d’urto: in accordo con EN/IEC 60051-1 paragrafo 7.6
CUSTODIA
Fissaggio: incasso
Foratura pannello: vedi tabella
Frontale: vedi tabella
Profondità: vedi tabella
Connessioni: morsetti a vite / faston 6,3 x 0,8mm (AQ48Mrad solo faston)
Materiale custodia: policarbonato autoestinguente
Grado di protezione(EN/IEC 60529): IP52 frontale, IP20 morsetti (con coprimorsetto)
Opzione: protezione frontale IP54
Peso: vedi tabella
INPUT
Quantity: single-phase, alternating voltage
Connection: direct (S 250/124 - /141) or by external VT (S 250/125 - /142)
Measure: average value measurement, related to r.m.s value, form factor 1,11
Rating voltage Un
Direct connection: 10...600V
Connection by VT external: VT/100V - VT/110V
Continuous overload: 1,2Un
Istantaneous overload: 10Un/5s
Rating frequency fn: 50Hz
Working frequency: 45..65Hz
Accuracy (EN/IEC 60051): class 1,5
Rated burden: ≃1mA
INSULATION (EN/IEC 61010-1)
Installation category: III
Pollution degree: 2
Insulation rating voltage: 600V (Phase - Neutral)
A.C. voltage test 4kV r.m.s. 50Hz/5s
Considered circuits : all circuits and earth
ENVIRONMENTAL CONDITIONS
Reference temperature: 23°C
Nominal range of use: 5...40°C
Operating range: -25...50°C
Limit range for storage and transport: -40...80°C
Vibration test: according to EN/IEC 60051-1 paragraph 7.6
Shock test: according to EN/IEC 60051-1 paragraph 7.6
HOUSING
Mounting: flush mounting
Panel cutout: see table
Front frame: see table
Depth: see table
Connections: screw terminal / fast-on 6,3 x 0,8mm (AQ48Mrad only fast-on)
Housing material: self-extinguishing policarbonate
Protection degree (EN/IEC 60529): IP52 front frame, IP20 terminals (with protection)
Option: protection IP54 front frame
Weight: see table
28
LOAD∼
V
Rad
S 250/141
a
A
b
B
LOAD∼
V
Rad
S 250/142
NT791 01 - 2013 0 Ed.
pag.4/4
La I.M.E. S.p.A. si riserva in qualsiasi mom
ento, di modificare le caratteristiche tecniche senza darne preavviso. / I.
M.E
. S.p
.A. r
eser
ves
the
right
, to
mod
ify th
e te
chni
cal
char
acte
ristic
s w
ithou
t not
ice.
SCHEMI D’INSERZIONE WIRING DIAGRAMS
DIMENSIONI DIMENSIONS
B
AB
A
C
88 98 78
43 52
3,5
LOAD∼
V
S 250/124
a
A
b
B
LOAD∼
V
S 250/125
Accessorio raddrizzatoreper AQ48M/rad
Rectifier accessoryfor AQ48M/rad
Modello / Model Schemi / Diagrams A B C Peso / Weight
AQ48Mrad S 250 / 130 - 131 48x48 45x45 85,5 250 gr.
AQ72MradS 250 / 132 -133
72x72 68x68 84 300 gr.
AQ96Mrad 96x96 92x92 84 350 gr.
AQ48Mrad AQ48Mrad
AQ72/96Mrad AQ72/96Mrad
29
NT790 12 - 2012 1aEd.pag.1/5
ANIndicatori AnalogiciAQMrad
per corrente alternata48x48mm72x72mm96x96mm
Indicazione diretta della corrente di ingresso odella corrente primaria del TA esterno
Equipaggio a bobina mobile, con accessorio raddrizzatore
Ingresso diretto 1...5AIngresso da TA esterno /5A oppure /1A
Versione per avviamento motore 2In opp. 5InAmpiezza scala 240°
Precisione cl.1,5
AQMradAnalog Meters for alternating current48x48mm72x72mm96x96mm
Direct indication of input current orprimary current of external CTMoving coil equipment,with rectifier accessoryDirect connection 1...5AInput by external CT /5A or /1AVersion for starting motor 2In or 5InScale length 240°Accuracy class 1,5
INDICATORI ANALOGICIANALOG METERS
2In
5In
In
Scala intercambiabileInterchange scales
AQ72M - AQ96M Coprimorsetto di serieStandard terminal cover
30
NT790 12 - 2012 1aEd.pag.2/5
InserzioneConnection 0...In - DIRETTA / DIRECT
ModelloModel AQ48Mrad AQ72Mrad AQ96Mrad
DimensioniDimensions 48 x 48 72 x 72 96 x 96
PortataRange CODICE DI ORDINAZIONE / ORDERING CODE
1A AN51D1A100 AN61D1A100 AN71D1A100
2,5A AN51D1A250 AN61D1A250 AN71D1A250
5A AN51D1A500 AN61D1A500 AN71D1A500
Opzione / Option Suffisso / Suffix Esempio / Example
TropicalizzatoTropicalized
Aggiungere “1” al codice standardAdd “1” at the end of standard code AN6151C500 ⇒ AN6151C5001
Protezione frontale IP54IP54 Front protection
Aggiungere “3” al codice standardAdd “3” at the end of standard code AN6151C500 ⇒ AN6151C5003
Altre esecuzioni disponibili su tutti i modelli: Other executions available on all models:
InserzioneConnection da TA/ 5A on CT/5A da TA/ 1A on CT/1A
Scala / Scale 0...In 0...InModello / Model AQ48Mrad AQ72Mrad AQ96Mrad AQ48Mrad AQ72Mrad AQ96Mrad
DimensioniDimensions 48 x 48 72 x 72 96 x 96 48 x 48 72 x 72 96 x 96
Portata / Range CODICE DI ORDINAZIONE / ORDERING CODE
Senza scalaWithout scale AN51510000 AN61510000 AN71510000 AN51110000 AN61110000 AN7111000
5A AN51D1A500 AN61D1A500 AN71D1A500 AN5111A500 AN6111A500 AN7111A500
10A AN5151B100 AN6151B100 AN7151B100 AN5111B100 AN6111B100 AN7111B100
15A AN5151B150 AN6151B150 AN7151B150 AN5111B150 AN6111B150 AN7111B150
20A AN5151B200 AN6151B200 AN7151B200 AN5111B200 AN6111B200 AN7111B200
25A AN5151B250 AN6151B250 AN7151B250 AN5111B250 AN6111B250 AN7111B250
30A AN5151B300 AN6151B300 AN7151B300 AN5111B300 AN6111B300 AN7111B300
40A AN5151B400 AN6151B400 AN7151B400 AN5111B400 AN6111B400 AN7111B400
50A AN5151B500 AN6151B500 AN7151B500 AN5111B500 AN6111B500 AN7111B500
60A AN5151B600 AN6151B600 AN7151B600 AN5111B600 AN6111B600 AN7111B600
70A AN5151B700 AN6151B700 AN7151B700 AN5111B700 AN6111B700 AN7111B700
75A AN5151B750 AN6151B750 AN7151B750 AN5111B750 AN6111B750 AN7111B750
80A AN5151B800 AN6151B800 AN7151B800 AN5111B800 AN6111B800 AN7111B800
100A AN5151C100 AN6151C100 AN7151C100 AN5111C100 AN6111C100 AN7111C100
120A AN5151C120 AN6151C120 AN7151C120 AN5111C120 AN6111C120 AN7111C120
125A AN5151C125 AN6151C125 AN7151C125 AN5111C125 AN6111C125 AN7111C125
150A AN5151C150 AN6151C150 AN7151C150 AN5111C150 AN6111C150 AN7111C150
160A AN5151C160 AN6151C160 AN7151C160 AN5111C160 AN6111C160 AN7111C160
200A AN5151C200 AN6151C200 AN7151C200 AN5111C200 AN6111C200 AN7111C200
250A AN5151C250 AN6151C250 AN7151C250 AN5111C250 AN6111C250 AN7111C250
300A AN5151C300 AN6151C300 AN7151C300 AN5111C300 AN6111C300 AN7111C300
400A AN5151C400 AN6151C400 AN7151C400 AN5111C400 AN6111C400 AN7111C400
500A AN5151C500 AN6151C500 AN7151C500 AN5111C500 AN6111C500 AN7111C500
600A AN5151C600 AN6151C600 AN7151C600 AN5111C600 AN6111C600 AN7111C600
700A AN5151C700 AN6151C700 AN7151C700 AN5111C700 AN6111C700 AN7111C700
750A AN5151C750 AN6151C750 AN7151C750 AN5111C750 AN6111C750 AN7111C750
800A AN5151C800 AN6151C800 AN7151C800 AN5111C800 AN6111C800 AN7111C800
1.000A AN5151D100 AN6151D100 AN7151D100 AN5111D100 AN6111D100 AN7111D100
1.200A AN5151D120 AN6151D120 AN7151D120 AN5111D120 AN6111D120 AN7111D120
1.250A AN5151D125 AN6151D125 AN7151D125 AN5111D125 AN6111D125 AN7111D125
1.500A AN5151D150 AN6151D150 AN7151D150 AN5111D150 AN6111D150 AN7111D150
1.600A AN5151D160 AN6151D160 AN7151D160 AN5111D160 AN6111D160 AN7111D160
2.000A AN5151D200 AN6151D200 AN7151D200 AN5111D200 AN6111D200 AN7111D200
2.500A AN5151D250 AN6151D250 AN7151D250 AN5111D250 AN6111D250 AN7111D250
3.000A AN5151D300 AN6151D300 AN7151D300 AN5111D300 AN6111D300 AN7111D300
4.000A AN5151D400 AN6151D400 AN7151D400 AN5111D400 AN6111D400 AN7111D400
5.000A AN5151D500 AN6151D500 AN7151D500 AN5111D500 AN6111D500 AN7111D500
6.000A AN5151D600 AN6151D600 AN7151D600 AN5111D600 AN6111D600 AN7111D600
8.000A AN5151D800 AN6151D800 AN7151D800 AN5111D800 AN6111D800 AN7111D800
10.000A AN5151E100 AN6151E100 AN7151E100 AN5111E100 AN6111E100 AN7111E100
31
NT790 12 - 2012 1aEd.pag.3/5
Modello Model
Scala per / Scale forAQ48Mrad
Scala per / Scale forAQ72Mrad
Scala per / Scale forAQ96Mrad
ScalaScale
0...In per amperometri su TA/5A / for CT/5A ammeters
Portata / Range CODICE DI ORDINAZIONE / ORDERING CODE
5/5A SC51D1A500 SC61D1A500 SC71D1A500
10/5A SC5151B100 SC6151B100 SC7151B100
15/5A SC5151B150 SC6151B150 SC7151B150
20/5A SC5151B200 SC6151B200 SC7151B200
25/5A SC5151B250 SC6151B250 SC7151B250
30/5A SC5151B300 SC6151B300 SC7151B300
40/5A SC5151B400 SC6151B400 SC7151B400
50/5A SC5151B500 SC6151B500 SC7151B500
60/5A SC5151B600 SC6151B600 SC7151B600
70/5A SC5151B700 SC6151B700 SC7151B700
75/5A SC5151B750 SC6151B750 SC7151B750
80/5A SC5151B800 SC6151B800 SC7151B800
100/5A SC5151C100 SC6151C100 SC7151C100
120/5A SC5151C120 SC6151C120 SC7151C120
125/5A SC5151C125 SC6151C125 SC7151C125
150/5A SC5151C150 SC6151C150 SC7151C150
160/5A SC5151C160 SC6151C160 SC7151C160
200/5A SC5151C200 SC6151C200 SC7151C200
250/5A SC5151C250 SC6151C250 SC7151C250
300/5A SC5151C300 SC6151C300 SC7151C300
400/5A SC5151C400 SC6151C400 SC7151C400
500/5A SC5151C500 SC6151C500 SC7151C500
600/5A SC5151C600 SC6151C600 SC7151C600
700/5A SC5151C700 SC6151C700 SC7151C700
750/5A SC5151C750 SC6151C750 SC7151C700
800/5A SC5151C800 SC6151C800 SC7151C800
1000/5A SC5151D100 SC6151D100 SC7151D100
1200/5A SC5151D120 SC6151D120 SC7151D120
1250/5A SC5151D125 SC6151D125 SC7151D125
1500/5A SC5151D150 SC6151D150 SC7151D150
1600/5A SC5151D160 SC6151D160 SC7151D160
2000/5A SC5151D200 SC6151D200 SC7151D160
2500/5A SC5151D250 SC6151D250 SC7151D250
3000/5A SC5151D300 SC6151D300 SC7151D300
4000/5A SC5151D400 SC6151D400 SC7151D400
5000/5A SC5151D500 SC6151D500 SC7151D500
6000/5A SC5151D600 SC6151D600 SC7151D600
8000/5A SC5151D800 SC6151D800 SC7151D800
10000/5A SC5151E100 SC6151E100 SC7151E100
Versione / Version Suffisso / Suffix Esempio / Example
Scala ristretta al fondo 2In2In overscale
Sostituire la 6a cifra del codice (1) con 2Replace the 6a digit of the code (1) with 2 SC5151C500 ⇒ SC5152C500
Scala ristretta al fondo 5In5In overscale
Sostituire la 6a cifra del codice (1) con 5Replace the 6a digit of the code (1) with 5 SC5151C500 ⇒ SC5155C500
Inserzione su TA/1ACT/1A connection
Sostituire la 5a cifra del codice (5) con 1Replace the 5a digit of the code (5) with 1 SC5151C500 ⇒ SC5111C500
Altre esecuzioni disponibili su tutti i modelli: Other executions available on all models:
32
NT790 12 - 2012 1aEd.pag.4/5
VISUALIZZAZIONE
Scala: intercambiabile, con inserimento guidato a protezione dell’indice e cassettino
di chiusura
Colore scala: fondo bianco, divisioni e numerazione nere
A richiesta scale personalizzate
Opzioni: segno rosso di riferimento
Ampiezza scala: 240°
Tracciatura standard: 0...In
Tracciatura avviamento motore: 0...In...2In opp. 0...In...5In
Colore indice: nero
Opzione: indice rosso di riferimento (regolabile)
INGRESSO
Grandezza: corrente alternata monofase
Inserzione: diretta (S 250/130 - /132) o da TA esterno /5A opp. /1A (S 250/131 - /133)
Misura: valor medio, rapportato al valore efficace, fattore di forma 1,11
Corrente nominale In
Inserzione diretta: 1...5A (vedi tabella)
Inserzione da TA esterno: 5A oppure 1A
Sovraccarico permanente: 1,2In
Sovraccarico istantaneo: 10In/5s
Frequenza nominale fn: 50Hz
Frequenza di funzionamento: 45...65Hz
Precisione (EN/IEC 60051): cl.1,5
Autoconsumo: ≤ 1,1VA
ISOLAMENTO (EN/IEC 61010-1)
Categoria di installazione: III
Grado di inquinamento: 2
Tensione di riferimento per l’isolamento: 600V (Fase - Neutro)
Prova a tensione alternata 4kV valore efficace 50Hz/5s
Circuiti considerati: tutti i circuiti verso terra
CONDIZIONI AMBIENTALI
Temperatura di riferimento: 23°C
Campo nominale di utilizzo: 5...40°C
Campo di funzionamento: -25...50°C
Campo limite per l’immagazzinamento e trasporto: -40...80°C
Prova di vibrazioni: in accordo con EN/IEC 60051-1 paragrafo 7.6
Prova d’urto: in accordo con EN/IEC 60051-1 paragrafo 7.6
CUSTODIA
Fissaggio: incasso
Foratura pannello: vedi tabella
Frontale: vedi tabella
Profondità: vedi tabella
Connessioni: morsetti a vite / faston 6,3 x 0,8mm (AQ48Mrad solo faston)
Materiale custodia: policarbonato autoestinguente
Grado di protezione(EN/IEC 60529): IP52 frontale, IP20 morsetti (con coprimorsetto)
Opzione: protezione frontale IP54
Peso: vedi tabella
DISPLAY
Scale: interchangeable, easy-insertion to protect the pointer as well as relevant
closing slip
Scale colour: white background, black divisions and numbering
Customized scales upon request
Option: reference red mark
Scale length: 240°
Standard scale marking: 0...In
Motor startup marking scale: 0...In...2In or 0...In...5In
Pointer colour: black
Option: (adjustable) reference red pointer
INPUT
Quantity: single-phase, alternating current
Connection: direct (S 250/130 - /132) or by external CT /5A or /1A (S 250/131 - /133)
Measure: average value measurement, related to r.m.s value, form factor 1,11
Rating current In
Direct connection: 1...5A (see table)
Connection by CT external: 5A or 1A
Continuous overload: 1,2In
Instantaneous overload: 10In/5s
Rating frequency fn: 50Hz
Working frequency: 45..65Hz
Accuracy (EN/IEC 60051): class 1,5
Rated burden: ≤ 1,1VA
INSULATION (EN/IEC 61010-1)
Installation category: III
Pollution degree: 2
Insulation voltage rating: 600V (Phase - Neutral)
A.C. voltage test 4kV r.m.s. 50Hz/5s
Considered circuits : all circuits and earth
ENVIRONMENTAL CONDITIONS
Reference temperature: 23°C
Nominal range of use: 5...40°C
Operating range: -25...50°C
Limit range for storage and transport: -40...80°C
Vibration test: according to EN/IEC 60051-1 paragraph 7.6
Shock test: according to EN/IEC 60051-1 paragraph 7.6
HOUSING
Mounting: flush mounting
Panel cutout: see table
Front frame: see table
Depth: see table
Connections: screw terminal / fast-on 6,3 x 0,8mm (AQ48Mrad only fast-on)
Housing material: self-extinguishing policarbonate
Protection degree (EN/IEC 60529): IP52 front frame, IP20 terminals (with protection)
Option: protection IP54 front frame
Weight: see table
33
NT790 12 - 2012 1aEd.pag.5/5
SCHEMI D’INSERZIONE WIRING DIAGRAMS
LOAD∼
A
Rad
S 250/130
S1
P1
S2
P2 LOAD∼
A
Rad
S 250/131
DIMENSIONI DIMENSIONS
B
AB
A
C
88 98 78
43 52
3,5
LOAD∼
A
S 250/132
S1
P1
S2
P2 LOAD∼
A
S 250/133
Accessorio raddrizzatoreper AQ48M/rad
Rectifier accessoryfor AQ48M/rad
La I.M.E. S.p.A. si riserva in qualsiasi mom
ento, di modificare le caratteristiche tecniche senza darne preavviso. / I.
M.E
. S.p
.A. r
eser
ves
the
right
, to
mod
ify th
e te
chni
cal
char
acte
ristic
s w
ithou
t not
ice.
Modello / Model Schemi / Diagrams A B C Peso / Weight
AQ48Mrad S 250 / 130 - 131 48x48 45x45 85,5 250 gr.
AQ72MradS 250 / 132 -133
72x72 68x68 84 300 gr.
AQ96Mrad 96x96 92x92 84 350 gr.
AQ48Mrad AQ48Mrad
AQ72/96Mrad AQ72/96Mrad
34
35
ENERGY MEASUREMENT AND CONTROL www.algodue.com
Technical Information
1SAUUPM3H157 May 2005
General Description
The UPM315 is a multifunction metering device with
advanced functionality features, suitable for electrical
parameters measurement and power quality analysis .
It provides accurate True RMS values on graphic LCD display,
or via communication port. Six or more parameters displayed
simultaneously give the complete situation of the electrical
line at first sight.
The UPM315 performs clear graphical functions such as:
waveforms of voltage and current, harmonic spectrum, phasor
diagrams and trends of measured values.
A simple menu structure makes the instrument easy-to-use
and allows a quick check of the instrument set-up and memory
status. Three languages can be selected easily: English,
German, Italian.
The backlighted LCD display is highly efficient therefore it
guarantees perfect visibility in all light conditions.
The UPM315 offers small size and a variety of mounting
combinations making it suitable for new installations as well
as retrofit applications. The power meter fits both in 4” round
and DIN96 square cutouts. The tranducer unit can be
mounted on opposite side of the display, on any flat surface
or onto a 35mm DIN rail.
n DIN 96 & ANSI 4” Cutout for New or Retrofit
Panels
n Highly Sofisticated Power Meter Providing
Advanced Functionality Features
n Large Graphic LCD Display with Excellent
Visibility
n UL Recognized Under UL61010B-1 and CAN/
CSA-C22.2 No.1010.1-92
n THD Even, Odd and Individual FFT Harmonic
Analysis up to 50th Order
n Power and Current Demand Calculation
n On-Board Memory up to 2MB
n Programmable Min/Max & Energy Data Logging
n Event and Alarm Recording, Waveform Capture,
Waveform Display, Phasor Diagrams, Historical
Trending, Time-of-Use and more....
UPM315DIN 96x96 and ANSI 4” Power Meter
Applications
••••• Switchboards, gensets, motor control centers, etc.
• Power monitoring & control systems
• Individual machine load monitoring
• Power demand analysis and management
• Harmonics monitoring
• Remote metering and cost allocation
Benefits
••••• The UPM315 provides hundreds of accurate True RMS
metering values at low cost.
• It provides peak average current and power demand
information. This data is essential to work out proper
strategies aimed at avoiding uncontrolled power peaks
and consequent penalties.
• Being ultra-compact with flexible mounting, the UPM315
is suitable for replacing conventional meters. It fits in ANSI
4” and DIN 96 cutout allowing retrofit to existing
equipment.
• The UPM315 offers time and cost saving on mounting,
compared to many individual single-function
instruments.
• The recorded data allows to generate on a PC
consumption profiles, logged values trends, event and
alarm reporting, cost allocation and reports as well as
to identify critical values.
• Via communication port it is possible to read and log on
a PC all the readings and download the stored data.
CONFIGURATIONS
1) DIN 96x96 compact instrument
2) ANSI 4” instrument
3) ANSI 4” display + remote tranducer
4) Transducer without display
36
ENERGY MEASUREMENT AND CONTROL www.algodue.com
UPM315 - DIN 96x96 and ANSI 4” Power Meter
Main Features
Measurements
••••• Three-phase 3-wire or 4-wire unbalanced load operation
• Direct measurement up to 600 (750)VAC
• Programmable 1A / 5A current full scale
••••• True RMS metering provides accurate measurement even
for distorted waveform
• Fully bi-directional, four-quadrant readings. 10 energy
counters are available, the apparent power/energy is
splitted in four counters: import lagging, import leading,
export lagging, export leading
• Volts, Amps, Power, PF, Frequency, Energy, Min/Max
values, Demand, Harmonics, etc. The full version
instrument provides more than 600 measured/calculated
parameters and shows on the LCD more than 35 graphical
pages
• Individual & total harmonic distortion for voltage and
current up to the 50th order. The harmonic content is
represented like even, odd and total
• Advanced waveform capture function. The instrument can
store, after a trigger, up to 200 waveforms with a resolution
from 16 to 128 samples (depending on the number of
waveforms).
The trigger can be programmed on a digital input or output
change, on a set point crossing or the capture can be
started from the keypad.
The stored waweform is downloadable through the
communication port.
Modularity
• Two slots for plug-in options boards
• The tranducers version, the ANSI 4” display unit and the
compact DIN 96 instrument allow various mounting
combinations to fit the requirements of new installations
as well as retrofit applications. The “Physical
Configurations” page shows the mounting combinations
Graphics
• The excellent graphical display performs clear graphical
representations allowing an immediate comprehension
of the measured parameters. Are displayed the voltage
and current waveforms, the harmonic spectrum and the
phasor diagrams.
• Moreover 6 measured values can be represented as a
graphical trend on the display. The scale of the trend can
be selected between 15 min, 1 hour, 1 day and 1 month.
On-Board Memory
• 128k or 2MBytes non-volatile memory for data storage
• Programmable start/stop time of recordings
• Wraparound or Fill (FIFO/Stack) selectable recording mode
• Min/Avg/Max logging every 1, 5, 10, 15, 30, 60 minutes,
programmable up to 8 selectable parameters
• Total and daily energy consumption recording. The
individual consumption of more than 300 days is
recorded.
• Time-of-Use (TOU) programmable data recording. The
TOU function stores the energy consumption in different
registers according the programmed time-scheme. A
group of 120 registers gives the situation of the previous
and current day, and of the previous and current month.
This feature is designed to fit different tariff structures.
It’s possible to program up to 10 daily tariff schedules
containing up to 3 tariffs and 8 tariff changes. Each
schedule can be assigned to the days of the week and
months as requested. Up to 20 holidays can be assigned
to the lowest tariff.
A diagnostic algorithm checks and notifies any setup
overlapping.
• Event, alarm and digital outputs ON/OFF recording. The
instrument records the status change of 8 programmable
set points, the digital outputs ON/OFF and the instrument
supply ON/OFF. All the events are integrated by date
and time reference
Communication
• Both RS232 and RS485 included in the basic unit. The
selection is made by dip-switches
• Modbus protocol or standard ASCII protocol
• Communication speed programmable up to 57,600 bps
• Optional 10/100 Ethernet, Profibus or Lonbus interfaces
• On-board HTML Web Page server or direct
communication through Ethernet / Internet network using
Modbus or standard ASCII protocol
Inputs & Outputs
• Up to 6 digital outputs for energy pulsing or for alarm
tripping. Two digital Optomos ML outputs are included in
the basic unit.
• Up to 4 analog outputs 0-20 or 4-20 mA
• Optional four digital inputs for pulse counting. A multiplier
is programmable for each input in order to store the real
quantities, as well different measurement units are
selectable (kWh, kVAh, kvarh, m3, etc.)
• One of the digital inputs can be programmed as demand
period syncronization input
Other
• Real Time Clock with battery backup
• Calculation of capacitor bank value for PF compensation
• No.1 programmable user page with 6 parameters
selected among measured values
• Five alpha-numeric characters password to avoid
unauthorized setup access
• Downloadable firmware via serial port
2
37
ENERGY MEASUREMENT AND CONTROL www.algodue.com
INSTANTANEOUS MEASUREMENTS
PHASE VOLTAGE VL1-N
- VL2-N
- VL3-N
[V]
LINE VOLTAGE VL1-L2
- VL2-L3
- VL3-L1
[V]
SYSTEM VOLTAGE V [V]
LINE CURRENT IL1
- IL2
- IL3
- IN
[A]
SYSTEM CURRENT I [A]
POWER FACTOR PFL1
- PFL2
- PFL3
SYSTEM POWER FACTOR PF
COS Ø DPFL1
- DPFL2
- DPFL3
APPARENT POWER SL1
- SL2
- SL3
[VA]
SYSTEM APPARENT POWER S [VA]
ACTIVE POWER PL1
- PL2
- PL3
[W]
SYSTEM ACTIVE POWER P [W]
REACTIVE POWER QL1
- QL2
- QL3
[var]
SYSTEM REACTIVE POWER Q [var]
FREQUENCY f [Hz]
DEMAND (AVERAGE VALUES) PAV
- SAV
- QAV
- IAV
- ITHAV
( )
THERMAL CURRENT IL1
- IL2
- IL3
[A2s]
VOLTAGE & CURRENT THD (Total ) THDVL1,
L2,
L3
- THDIL1,
L2,
L3
[%]
VOLTAGE & CURRENT THD (Even, Odd) THDVL1,
L2,
L3
- THDIL1,
L2,
L3
[%]
FFT ANALYSIS 31ST VL1-N
- VL2-N
- VL3-N
- IL1
- IL2
- IL3
[%, V, A]
FFT ANALYSIS 50TH VL1-N
- VL2-N
- VL3-N
- IL1
- IL2
- IL3
[%, V, A]
UNBALANCE V,I [%]
PHASE REVERSAL 123 / 132
REAL TIME CLOCK Date, Time
UPM315 - DIN 96x96 and ANSI 4” Power Meter
STORED DATA
SYSTEM ACTIVE ENERGY [Wh]
SYSTEM APPARENT ENERGY (N.4 Counters - ) [VAh]
SYSTEM LAGGING REACTIVE ENERGY [varh ind]
SYSTEM LEADING REACTIVE ENERGY [varh cap]
MIN / MAX VALUES WITH TIME REFERENCE 7xV, 5xI, f, 4xPF, 6xTHD
PEAK VALUES PAV
- SAV
- QAV
- IAV
- ITHAV
( )
PROGRAMMABLE RECORDINGS
DAILY CONSUMPTION (More than 300 days) [Wh, VAh, varh]
ALARM / EVENT LOG 8 Set Points, Outputs ON/OFF, Instrument ON/OFF
MIN / AVG / MAX VALUES(1) [(1)]
ADVANCED FEATURES
GRAPHICAL TRENDS Max 6 parameters [15min/1hrs/1day/1month]
TIME OF USE (TARIFF REGISTERS) [Wh, VAh, varh]
WAVEFORM CAPTURE VL1-N
-VL2-N
-VL3-N
-IL1
-IL2
-IL3
[128 samples max]
CALCULATION OF PF COMPENSATION Capacitor bank [kvar]
DIGITAL INPUTS COUNTERS [Wh, VAh, varh, m3, litres, etc.]
= Standard = Bi-directional value = Optional = Enhanced Package
(1) Programmable every 1, 5, 10, 15, 30, 60 min - Maximum 8 measured parameters.
3
38
ENERGY MEASUREMENT AND CONTROL www.algodue.com
UPM315 - DIN 96x96 and ANSI 4” Power Meter
Specifications
Power supply
Rated voltage: 65 - 250 Vac 50/60Hz or 90 - 250 Vdc
(19 - 60 Vdc - option)
Consumption: 5VA max
Voltage inputs
Maximum measurable voltage: 600 (750)VAC max L-L
Input impedance: >1.3 MOhm
Burden: max 0.15 VA per phase
Frequency: 45 - 65 Hz
Current inputs
Rated current (Ib): 1 / 5 ARMS programmable
Min / max measurable current: 20 mA / 7 ARMS
Maximum overload: 10ARMS continuous - 100 ARMS for 1 sec.
Input impedance: 0.02 Ohm approximately
Burden: max 0,5 VA per phase
Insulation voltage: 150 VAC max between phases
Typical accuracy
Voltage: ± 0.1% reading ± 0.03% full scale
Current: ± 0.1% reading ± 0.05% full scale
Active power: ± 0.5% reading ± 0.1% full scale (PF=1)
Power factor: 1% reading (0,5% optional) (0.5 ind - 0.8 cap)
Active energy: class 1 (class 0,5 optional)
Frequency: ± 0.05% reading ± 1 digits from 45 to 65 Hz
Display and operating controls
Display: Backlighted graphic LCD display
160 x 144 dots
Keypad: 5 push-buttons
Data memory
Type: On-Board non-volatile FLASH, 128kB or 2 MB
Communication port
Type: No.1 selectable RS232 or RS485, optoisolated
No.1 available for plug-in comm. boards
Baud Rate: 300 to 57600 bps
Real Time Clock
Type: with battery backup
Accuracy: ± 30 ppm
Digital outputs
Type: No.2 isolated Optomos (50V - 300mAAC-DC
)
Environmental conditions
Operating temperature: from -15 oC to +60 oC
Storage temperature: from -25 oC to +75 oC
Relative humidity: 80% max. without condensation
Mechanical characteristics
Material: Metal enclosure
Protection degree: IP54 (front panel); IP20 (terminals)
Terminals: Pluggable terminal blocks
(Barrier terminal strips - OPTION)
Size / Weight: 96 x 96 x 130 (mm) DIN version 750 gr
110 x 110 x 40 (mm) ANSI Display 390 gr
90 x 90 x 130 (mm) Transducer 800 gr
Standards compliance
Safety: UL recognized under UL61010B-1and CAN/
CSA-C22.2 No. 1010.1-92, 73/23/EEC,
93/68/EEC directives, EN61010.1
EMC: 89/366/EEC directive and following
modifications 93/31/EEC and 93/68/EEC,
EN50081-2, EN50082-2, EN61326/A1
Single-Phase up to 400V
TYPICAL WIRING DIAGRAMS
3-Phase 4-Wire up to 600V
3-Phase 3-Wire above 600V
L1 N
4
L1 L2 L3 NL1 L2 L3 N
L1 L2 L3
39
ENERGY MEASUREMENT AND CONTROL www.algodue.com
UPM315 - DIN 96x96 and ANSI 4” Power Meter
PHYSICAL CONFIGURATION
Compact DIN 96x96 instrument
Compact version according DIN 96 standard (92 x 92 mm cutout)
Transducer
The transducer can be mounted, using the adapter, on a
flat surface or on a DIN Rail. It can be connected to the
display by a 3m (~10 feet) provided cable.
Rear connections - Barrier terminal strips (OPTION)
The RS232 / RS485 programmable port and the two
digital outputs are included in the basic configuration.
Two slots are available for option boards.
Rear connections - Standard pluggable terminals
The RS232 / RS485 programmable port and the two
digital outputs are included in the basic configuration.
Two slots are available for option boards.
ANSI 4” instrument (display + transducer)
The drawings below show the tranducer mounted on the
backside of the ANSI 4” display.
5
OUT1
OUT2
OUT1
OUT2
40
ALGODUE ELETTRONICA s.r.l.
Via Passerina, 3/A
28010 FONTANETO D'AGOGNA
(NO) ITALY
Tel: +39 0322 89864 - 89307
Fax: +39 0322 89871
E-mail: info@algodue.com
Website: www.algodue.com
ENERGY MEASUREMENT
AND CONTROL
ALRALRALRALRALR AAAAA 55555 XXXXX
Subject to change without notice
UPM315 - DIN 96x96 and ANSI 4” Power Meter
ORDERING INFORMATION
UPM315
Series
User’s Manual Language
D = German
I = Italian
U = English
Communication Protocol
B = ASCII Standard
C = Modbus
E = Ethernet board
L = Lonbus board
P = Profibus board
Aux Power Supply
A = 65 ÷ 250VAC
/ 90 ÷ 250VDC
R = 19 ÷ 60VDC
Serial Port
5 = Selectable RS232/485 (1)
Memory
1 = 128 kBytes (1)
6 = 2MBytes + Enhanced package
Firmware Options
2 = Basic version (1)
3 = Harmonics to 31st+ DPF
4 = Enhanced package + Harmonics + DPF + 2MBytes
Special functions
X = None
5 = accuracy class 0,5 for energy counters
Physical Configuration
STANDARD PLUGGABLE TERMINALS (EU)
A = DIN 96x96 Instrument
B = ANSI Display + Transducer
C = ANSI Display + Transducer + Cable
+ mounting accessories
E = Transducer + mounting accessories
BARRIER TERMINAL STRIPS (USA)
G = DIN 96x96 Instrument
H = ANSI Display + Transducer
I = ANSI Display + Transducer + Cable
+ mounting accessories
K = Transducer + mounting accessories
Inputs (2)
X = None
4 = No.1 DI4-TR board - (No.4 digital inputs)
Analog Outputs (2)
X = None
A = No.1 AO2-0420 board - (No.2
programmable analog outputs)
R = No.2 AO2-0420 boards - (No.4
programmable analog outputs)
Digital Outputs (2)
2 = Basic version with No.2 built-in
optomos outputs (50V - 300mAAC-DC
) (1)
4 = No.1 DO2-ML board - (No.2 ML outputs)
6 = No.1 DO4-ML boards - (No.4 ML outputs)
R = No.1 DO2-R board - (No.2 relay outputs)
S = No.1 DO4-RML board - (No.2 relay
outputs + No.2 ML outputs)
V = No.1 DO2-MH board - (No.2 MH outputs)
W = No.1 DO4-MH boards - (No.4 MH outputs)
NOTES
1) The basic instrument configuration includes:
• Power Supply 65 ÷ 250VAC
/ 90 ÷ 250VDC
• No.2 Optomos Outputs (50V - 300mAAC-DC
)• RS232 / 485 selectable by dip-switches• 128 kBytes data recording memory• Real Time Clock with battery backup
2) The basic instrument can be equipped withmaximum 2 option boards.
DI4-TR No.4 Digital Inputs for Voltage-Free ContactsPROFI Profibus DP InterfaceLON Lonbus InterfaceETH 10/100 Ethernet Interface
PLUG-IN BOARDS
DO2-ML No.2 Optomos Outputs (50V - 300mAAC-DC
)DO2-MH No.2 Optomos Outputs (250V - 80mA
AC-DC)
DO2-R No.2 Relay Outputs (250V - 2AAC
resistive)DO4-ML No.4 Optomos Outputs (50V - 300mA
AC-DC)
DO4-MH No.4 Optomos Outputs (250V - 80mAAC-DC
)DO4-RML No.2 Relay + No.2 Optomos (ML) OutputsAO2-0420 No.2 0÷20 or 4÷20mA Analog Outputs
6
41
42
DIN RANGE PANEL METERSDESCRIPTIONAvailable with moving iron or moving coil movements for a.c. or d.c. use, these DIN panel metershave been supplied worldwide andare recognised for their quality and value. Standard scales or customised dials can be offered.
• Manufactured to:DIN 43700, IEC51 and BS89.
• 48mm, 72mm and 96mm sizes.• a.c. or d.c. use.• Interchangeable dials (72mm & 96mm).• Rugged pivot and jewel movement.• Ammeters, Voltmeters, Frequency
Meters, Power Factor Indicators,Wattmeters, Elapsed Time Indicatorsand Maximum Demand Indicators.
• Optional red secondary pointer andterminal cover.
• Special customised dials.
Howard Butler Limited is one of the largestindependent UK manufacturers of panel metersand associated products.
With over 80 years experience in the industryHOBUT products have built a reputation forhigh quality and modern design at competitive prices.
ANALOGUE PANEL METERS • D IGITAL PANEL METERS • HOURS COUNTERS • SELECTOR SWITCHES • PROTECTION RELAYS • TRANSDUCERSSHUNTS • CURRENT TRANSFORMERS • CHARGER METERS • THERMAL CUTOUTS • MULT I -FUNCTION METERS
11840
43
DIN RANGE PANEL METERSMOVING IRON Types: D48SD, D72SD, D96SD.
Accuracy: Class 1.5 (Class 2.5-60A andabove).
AC ratings: 1A to 100A direct connected(D48SD - 40A max).1A or 5A CT operated.30V to 600V direct connected.
Burden: 0.7VA typical for 1A or 5A CToperated at 50Hz.1.2VA max up to 30A2.4VA max for 40A to 100A.6VA max for voltmeters up to 600V.
Frequency: Calibrated at 50Hz.Specify for frequencies 15Hz upto 400Hz
Scaling: Standard ammeter and voltmeterscales.(2x and 6x overload amme-ter scales available on request).
Damping: Heavily damped movements available.
MOVING COIL Types: D48MC, D72MC, D96MC.Accuracy: Class 1.5. DC ratings: 100µA to 50A direct connected
(D48MC - 40A max).4-20mA, 1mA or 20mAtransducer operated.50mV to 600V direct connected.50mV to 300mV shunt operated.
AC ratings: Rectifier types available for a.c.use (mean sensitivity).
DC burden: 80mV to 150mV volt drop fordirect connect ammeters 1mA(1000Ω/V) for voltmeters andshunt operated ammeters.
Non std.: Suppressed zero voltmeters andtrim potentiometer types available.
WATTMETER Type: D96WA.Accuracy: Class 1.5.AC ratings: 1A or 5A CT operated.
63.5V to 500V direct connected.Burden: Current<0.5VA
Voltage<2.0VA each circuit.
Working range: Current 0-120%
Voltage 75-125%.Frequency: Calibrated for 50Hz or 60Hz.Systems: WA1 Single phase.
WA2 3ph 3 wire balanced loadWA3 3ph 4 wire balanced loadWA4 3ph 3 wire unbalanced loadWA5 3ph 4 wire unbalanced load
Terminals: Screw clamps - connection diagram supplied.
CONNECTIONDIAGRAMS
All DIN range panel meters areavailable as Wattmeters using aseparate transducer.
Moving Iron panel meters can beused for D.C. operation atreduced accuracy.
L N
kK
L l
L1 L2 L3
K
L
k
l
L1 L2 L3 N
kK
L l
L1 L2 L3
K
L
k
l K
L
k
l
L1 L2 L3 N
K
L
k
l
K
L
k
l
K
L
k
l
SINGLE PHASE 3PH 3W BALANCED LOAD 3PH 4W BALANCED LOAD 3PH 3W UNBALANCED LOAD
3PH 4W UNBALANCED LOAD
VOLTMETER
AMMETER
L1
L2
(L)
(N)
Vv
Uu
L1
L2
(L)
(N)L
l
K
k
DIRECTCONNECTED
VOLTAGETRANSFORMER
OPERATED
DIRECTCONNECTED
CURRENTTRANSFORMER
OPERATED
VOLTMETER
AMMETER
-
+
+
-
+
+ +
DIRECTCONNECTED
SHUNTOPERATED
• • •
• • •
•
DIN96
DIN72
DIN48
•
••
•
•
•••
••
44
DIN RANGE PANEL METERSPOWER FACTOR INDICATOR
Type: D96PF.Accuracy: Class 1.5 (±2 electrical degrees).AC ratings: 1A or 5A CT operated.
63.5V to 500V direct connected.Burden: Current<0.5VA
Voltage<2.0VA each circuit.
Working Current 20-150%range: Voltage 75-125%.Scaling: Cos ø 0.5 CAP -|- 0.5 IND.Frequency: Calibrated for 50Hz or 60HzSystems: PF2 3 phase 3 or 4 wire balanced
load.Separate transducer required forsingle phase use.
Terminals: Screw clamps - connection diagram supplied.
MAXIMUM DEMAND INDICATORType: D96MD, conforming to ES50-2.Accuracy: Class 3.AC rating: 5A CT operated with
1.2 x overscaling to 6A.1A version available on request.
Burden: 5VA. Time lag: 15, 20 or 30 mins.Frequency: Calibrated at 50Hz
Specify for frequencies up to 400Hz.Scaling: Range of interchangeable scales
to suit 5A CT’s. For double ratioCT’s two interchangeable dials are fitted.
Mounting: Front of panel fixings are available.
Type: D96CMD.Accuracy: Class 3, moving iron Class 1.5.AC rating: 5A CT operated with
1.2 x overscaling to 6A.1A version available on request.
Burden: 5.6VA. Time lag: 15, 20 or 30 mins.Frequency: Calibrated at 50Hz
Specify for frequencies up to 400Hz.Scaling: Range of interchangeable scales
to suit 5A CT’s. For double ratioCT’s two interchangeable dials are fitted.
Mounting: Front of panel fixings are available.
Types: D48HZ, D72HZ, D96HZ.Accuracy: Class 0.5 (±0.5% of nominal
frequency).Class 1.0 for 45/65 Hz.Class 1.5 for D48HZ types.
Ranges: 45/55, 45/65, 55/65, 360/440Hz.Ranges incorporating RPM scalealso available.
Input volts: 110V±15%, 225V±15%380 to 440V±5%.
Burden: 6mA at nominal voltage.
Types: D48HR, D72HR, D96HR.AC Ratings: 110V or 240V.Frequency: 50Hz or 60Hz.
DC models also available.Range: Seven digits up to 99999.99hrs.Terminals: Connections to terminal block.
Note: D48HR has a special panel cut-out=45.5 mmsq
L1 L2 L3 N
k K
Ll
L1
L2
(L)
(N)L
l
K
k
CURRENTTRANSFORMER
OPERATED
L1
L2
(L)
(N)L
l
K
k
CURRENTTRANSFORMER
OPERATED
CONNECTIONDIAGRAMS
COMBINED MAXIMUM DEMAND INDICATOR
FREQUENCY METER
ELAPSED TIME METER
L1
L2
(L)
(N)
Vv
Uu
DIRECTCONNECTED
VOLTAGETRANSFORMER
OPERATED
L1
L2
(L)
(N)
+0.5–0.0
•
•
• • •
• • •
•
DIN96
DIN72
DIN48
All DIN panel meters are availableas Power Factor Indicators using aseparate transducer.
Bi-metallic movement with additional Moving Iron movement,for instantaneous reading
Bi-metallic movement indirectlyheated.
•
•
•
••
•
45
DIN RANGE PANEL METERS
Our policy is one of continuous development and therefore specifications may change without notice.
HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD
WALSALL WS1 2EB ENGLAND
Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: sales@hobut.co.uk
Web: www.hobut.co.uk
TECHNICAL SPECIFICATION PANEL CUT-OUTS (All dimensions mm)
DIMENSIONS (All dimensions mm)
Standards IEC 51, BS 89.
Enclosure: DIN 43700.Flame retardant: base material UL94V1,case & terminal cover material UL94V0.Scale marking DIN 43802Protection IP52: IP54 can be supplied.
Overload: CURRENT - 1.2 x rating for 2hrs.- 10 x rating for 5 secs.
VOLTAGE - 1.2 x rating for 2hrs.- 2 x rating for 5 secs.
Insulation test: 2kV 50Hz for 1min.
Temperature: Calibrated at 23°c.Suitable for use at -25°c to +40°c.
Available extras: Adjustable red secondary pointer.Terminal cover.Special scale.Polycarbonate window.6.4mm “Faston” terminal tag(voltmeters & ammeters to 5A).
Other DIN products: Our illustrations and technical specifications apply to
meters with 90° scale arcs.Instruments with 240° scale arcs are also available.
dims+0.6–0.0
dims+0.7–0.0
dims+0.8–0.0
4568
6892
92
45
DIN 48 can be slot mounted using the standard fixing clip.DIN 72 & DIN 96 can be supplied with special fixing clips for slot mounting.Slot dimensions available on request.
• Digital panel meters.• Current Transformers.• Shunts.• Power transducers.• Protection relays.• Battery charger indicators.• Thermal cut-outs.
New HOBUT products include:• Pro-Din panel meters.• 240° panel meters.• kWh meters.• Multi-function meters.• Protective current transformers.
Data sheets on the following HOBUT product ranges are available onrequest:
E
F
D
CBA
A
A B C D E FDIN48 (M4 screw clamps) 48 5 43 44.8 10 –Ammeters up to 5A & Voltmeters
DIN48 (M6 stud terminals) 48 5 43 44.8 21 –Ammeters 6A to 40A
DIN72 (M4 screw clamps) 72 5.5 38.5 66 10 –Ammeters up to 5A & Voltmeters
DIN72 (M6 stud terminals) 72 5.5 38.5 66 19 –Ammeters 6A to 50A
DIN72 (M8 stud terminals) 72 5.5 38.5 66 22 –Ammeters 60A to 100A
DIN96 (M4 screw clamps) 96 5.5 38.5 90 10 20Ammeters up to 5A & Voltmeters
DIN96 (M6 stud terminals) 96 5.5 38.5 90 19 20Ammeters 6A to 50A
DIN96 (M8 stud terminals) 96 5.5 38.5 90 22 20Ammeters 60A to 100A
DIN96 Watt-meter 96 5.5 123 90 13 –DIN96 Power Factor Indicator 96 5.5 123 90 13 –DIN96 Max. Demand Indicator 96 5.5 58 90 10 20(M4 screw clamps)DIN96 Combined M.D.I. 96 5.5 58 90 10 20(M4 screw clamps)Note: If terminal covers are fitted as an optional extra, add 23mm to dimension ‘C’ for DIN72 & DIN96 meters, and 25mm to dimension ‘C’ for DIN48 meters.
DIN 96 DIN 72 DIN 48
46
47
PRODIN RANGE PANEL METERS
PD72SD MOVING IRON - AC
PD72HZ FREQUENCY RANGES
PD72MC MOVING COIL - DC
Dimensions (mm)Specifications
Options
DESCRIPTION 72 x 72mm DIN sized panelmeter with a horizontal scaleand a round barrel.Manufactured to IEC51.
APPLICATION Used widely in the panel building industry, where a DINproduct with a horizontal scaleis required. Round barrel allowsstraightforward installation withoutspecial tools.
Our policy is one of continuous development and therefore specifications may change without notice.
HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD
WALSALL WS1 2EB ENGLAND
Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: sales@hobut.co.uk
http://www.hobut.co.uk
Rating Burden Accuracy ClassScaled up to 40A direct connected 1.2VA max up to 30A, 2.4VA up to 40A 1.51A or 5A CT operated, scaled as necessary 0.7VA typically at 50Hz 1.5Scaled 30V to 600V, direct connected 6VA max 1.5
Rating Burden Accuracy Class45/65, 45/55 or 55/65 Hz for 110/230/380V direct connected 6mA at nominal voltage 1.5
Rating Burden Accuracy Class100µA to 40A direct connected up to 150mV 1.54/20mA, scaled as necessary up to 150mV 1.5Scaled up to 600V, direct connected 1mA (1000Ω/V) 1.550mV to 300mV shunt operated, scaled as necessary 1mA (1000Ω/V) 1.5
Flame retardant: Base - UL94V1, Case - UL94V0Protection: IP52 (front of panel)Scale marking: DIN 43802Overload (A): 1.2 x rating 2hrs / 10 x rating 5 secondsOverload (V): 1.2 x rating 2hrs / 2 x rating 5 secondsInsulation test: 2kV 50Hz for 1 minuteTemperature: Calibrated at 23°C, suitable for -25 to +40°CTerminals: M4 screw clamps supplied as standard
(above 5A, M6 studs are supplied)Panel mounting: U-clamp fixing or 2 pin fixing (57mm or 53mm)
• Special scales• M6 terminals, M3 studs • 6.4mm faston tags (up to 5A)• Terminal cover
Panel cut-out ø56
11840
48
R68 RANGE PANEL METERS
R68SD MOVING IRON - AC
R68MC MOVING COIL - DC
Dimensions (mm)Specifications
Options
DESCRIPTION Rectangular fronted, round barrelled, moving iron and moving coil panel meters for AC or DC use. Manufactured to IEC51 / BS89.
APPLICATION Used widely in the panel building, welding, and batterycharger industry, where a roundbarrelled instrument is requiredto fit into a standard 64mmdiameter panel cut-out.
Our policy is one of continuous development and therefore specifications may change without notice.
HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD
WALSALL WS1 2EB ENGLAND
Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: sales@hobut.co.uk
http://www.hobut.co.uk
Rating Burden AccuracyScaled up to 100A direct connected 1.2VA max upto 30A, 2.4VA max 40-100A 2.5%1A or 5A CT operated, scaled as necessary 0.7VA typically at 50Hz 2.5%Scaled 30V to 600V, direct connected 6VA max 2.5%
Rating Burden AccuracyScaled 50µA to 50A direct connected 80mV to 150mV volt drop 1.5%50mV to 300mV shunt operated, scaled as necessary 1mA (1000Ω/V) 1.5%Scaled 50mV to 600V, direct connected 1mA (1000Ω/V) 1.5%
R68SD R68MCScale length 52mm 62mmMovement 90° 90°Fixing method U-clip U-clipFlame retardant Base UL94V1 Base UL94V1
Case UL94V0 Case UL94V0Protection(front of panel) IP52 IP52
82 29.5
58
10
68 63Dia
64
• Adjustable red secondary pointer• 6 x overload scale (R68SD) • Tropical finish• Special dials• Black or white dial mask• R68 available as power factor indicator, wattmeter,
frequency meter, details on request.
Panel cut-out
11840
49
50
51
52
53
AC VOLTAGE
TECHNICAL SPECIFICATION
INPUT
Rated value Un 57.8 <100 / 110 <600 V
Power consumption <1.5 VA (VA1, VA3)
<1 VA (VL1, VL3, VR1)
Working range 15-125% Un (VA1, VA3)
0-125% Un (VL1, VL3, VR1)
Rated Frequency 50 / 60 / 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 1.5 x Un
Overload for 1 sec. 4 x Un (VL1 VL3 VR1 )
2 x Un (VA1 VA3)
OUTPUT
Rated value mA 0-1/5/10/20mA (VA1, VA3)
Rated value mA 1/5/10/20 & 4-20mA (VR1)
Rated value mA 4-20mA (VL1)
Rated Value volts 0-5 / 10 V (VA1, VA3)
Rated value volts 0-5 / 10 & 1-5 V (VR1)
Rated value volts 1-5 V (VL1 VL3)
ADJUSTMENT
Zero No adjustment (VA1,VA3)
Zero ± 2% (VR1,VL1)
Span ± 10% (VA1,VA3,VR1,VL1,VL3)
AUXILIARY
A.C. Voltage 115 / 230 / 400 V
(± 25% / 45-65Hz / <2 VA)
D.C. Voltage 24 / 48 / 110 V (± 20% /
galvanically isolated / < 3 W)
Note M100-VA1 & VA3 are self
powered.
WEIGHT & CASE SIZE
M100-VA1 Approx. 0.3 kg. 55mm case
M100-VL1,VR1 Approx. 0.4 kg. 55mm case
M100-VA3 Approx. 0.6 kg. 100mm case
M100-VL3 Approx. 0.7 kg. 100mm case
ORDERING INFORMATION
Product Code Input In Output Aux Freq. OptionsM100-AL1 5A 4-20mA 230V 50Hz
OPTIONS
1. Non standard inputs / outputs only as far as technically
acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C
7
The M100 series voltage transducers are designed to measure
A.C. Voltage in single and 3 phase system. They convert the
A.C. Signal to a D.C. Output that is directly proportional to
the input signal.
The M100-VA1 VA3 are self powered (i.e. no auxiliary
required) average sensing RMS calibrated voltage
transducers, mA and voltage outputs are available.
The M100-VL1 VL3 are average sensing RMS calibrated, live
zero voltage transducers. Auxiliary is required to provide
power so that 4mA output signal is present when the input is
zero.
The M100-VR1 is true RMS sensing RMS calibrated allowing
measurement of distorted waveforms of up to 9th harmonic
with a crest factor of 5. The VR1 is typically used in voltage
measurement where distorted waveform is common such as
thyristor drives.
The above units are used to measure voltage in energy
management systems, switchboards, generator and telemetery
controls. Isolation of 4kV is provided between the input and
output signal, allowing the ouput to be fed to conventional
analogue meters, digital meters, PLC, and computer systems.
TYPICAL APPLICATIONS
SELECTION GUIDE
M100-VA1 1 ph. self powered ave. sensing RMS calibrated
M100-VL1 1 ph. aux powered ave. sensing RMS calibrated
M100-VR1 1 ph. aux powered true RMS sensing RMS cal.
M100-VA3 3 ph. self powered ave. sensing RMS calibrated
M100-VL3 3 ph. aux powered ave. sensing RMS calibrated
54
AC VOLTAGE CONNECTION
DIAGRAMS
9
M100-VA1 / VS1 M100-VL1 / VR1 / VX1
M100-VA3 M100-VL3 / VX3
55
56
57
58
59
M850 MULTIFUNCTIONMETERSDESCRIPTION The new range of Hobut multifunction panel metersfeature 96 x 96mm sizes complete with unique blueLED screen, which can be seen in direct sunlight. Therange is easy to use, features user-programmable CT &VT ratios, and can be used on any single or 3 phasesystem with any input voltage without re-programming.
APPLICATION The range is a cost effective replacement for traditionalpanel meters and is suitable for low, medium and highvoltage control panels, gensets, building managementsystems, power management and more.
STANDARD FUNCTIONS:
Phase Voltage (V)
Phase to Neutral Voltage (V)
Phase Current (I)
Frequency (Hz)
Active Power (W)
Active Energy (kWh)
Reactive Power (VAr)
Apparent Power (VA)
Reactive Energy (VArh)
Power Factor (PF)
Instantaneous Amp Demand
Instantaneous Watt Demand
Instantaneous VA Demand
Maximum Amp Demand
Maximum Watt Demand
Maximum VA Demand
Neutral Current Measurement
RANGE ORDERING INFORMATION
PLUG-IN OPTIONS
All models feature thefollowing user-programmablefunctions:
• Current Transformer Ratio• Voltage Transformer Ratio• Baud Rate, Parity, Stops
• AC or DC AUX• 1A or 5A CT• Single or 3 phase system• Input voltage range 28-570V• RS485 address, 1-247• Security code access for
programming
PROGRAMMABLE FUNCTIONS
Suitable for any 1 or 3 phasesystem, AC aux 100-440V or DC aux 100-420V
Input 28/330V L-N48/570V L-L5A
STANDARD PRODUCT OPTIONAL EXTRAS
Pulsed Output
RS 485 Output
1A input (instead of 5A)
330mV Input(instead of 1A or 5A CT)
Order example: a standard product with RS 485 output is partnumber M850-MP1-RS
M850-MP1 P RS 1 MV
Both pulsed output(for Wh or VArh) andRS 485 output(Modbus protocol)are plug in optionswhich can besupplied with themultifunction meter.If purchasedseparately please useordering codes onright.
RS 485 Outputwhen ordered separately
use part RS485-M850
Pulsed Outputwhen ordered separately
use part PULSE-M850
60
L1
L2
L3
NL K
L3l k
L K
L2l k
L K
L1l k
L1L2L3NAUX UH
L+ N-
M850 MULTIFUNCTIONMETERS
ACCURACY Volts/Amps: 0.5% of readingFrequency: 0.1 HzActive Power: 1% of readingApparent Power:1% of readingPower Factor: 2% of rangeEnergy: IEC 1036 Class 1INPUT Rated Un: 28-330V LN, 48-570V L-LOverload: 800V continuousBurden: 0.5VA per phaseRated In: 0.5-6AOverload: 10 In for 1 secBurden: 0.5VA per phaseAuxiliary: 100-440V AC / 100-420V DC Frequency: 45/65HzDISPLAY Digits: 3 lines 9999Size: 14.2mm 7 segmentBrightness: user adjustableOUTPUT RELAY (Wh or VArh) Pulse output: SPST-NO (10 watt, 300VDC, 500mA)Pulse duration: programmable from 40msec-200msec
INSULATION Test Voltage: 3kV RMS 50Hz for 1 minute between case,
input and aux.1kV between case, input, aux, relay output & RS485 output.
Impulse test: EMC 5kV transient complies with IEC801/ EN55020 HF
Surge withstand: IEC801/EN55020 Ansi C37.90AInterference: EHF 2.5kV 1Mhz complying to IEC255-4Protection class II: Complying to IEC348 / BS4753 /
DIN57411 / VDESTANDARDS General: IEC688, BSEN60688, BS4889, IEC359EMC: BSEN61000-6-3:2007, BSEN61000-6-4:2007,Safety: IEC1010, BSEN601010ENVIRONMENT Working temp: 0-60ºCStorage temp: -40 to +85ºCRelative humidity: 0-95% non condensingShock: 30G in 2 planesMATERIAL Black polycarbonate case to UL94V0Weight: 0.35kg
SPECIFICATIONS
CONNECTION DIAGRAM
96
96
with plug inoption fitted
8219
61
92 (+0.8)
92 (+0.8)
Panel cut out
DIMENSIONS (mm)
Our policy is one of continuous development and therefore specifications may change without notice.
HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD
WALSALL WS1 2EB ENGLAND
Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: sales@hobut.co.uk
Web: www.hobut.co.uk
VOLTAGE CURRENT L1 L2 L3 N L1 L2 L3
1ph ! - - ! ! - -1ph 3W ! ! - ! ! ! -3ph 3W ! ! ! - ! - !
3ph 4W ! ! ! ! ! ! !
3ph 3W BAL ! ! ! - ! - -3ph 4W BAL ! - - ! ! - -
Unused Voltage terminals are internally connected
61
NEW
101L SERIESTYPE CTH101L
19 SERIESTYPE 196
NEW
H
W
Ø
D
H
W
Ø
D
PRIMARYCURRENT
PRODUCT SELECTION GUIDE
An easy to use product selector for the HOBUT range of standard current transformers.Many more current transformers can also be seen on our web site
www.currenttransformers.co.uk
STANDARD CURRENT TRANSFORMERSSELECTION GUIDE
DIN railmount and foot mount
Sealableterminalcovers
Inside Dia. (mm) Ø 21 15 24 – 20 28 40
Busbars (mm) – – 30 x 10 WOUND 20 x 20 40 x 10 50 x 1020 x 20 PRIMARY 30 x 10 40 x 30
Dimensions (mm) H 65 70 70 85 78 78 95
W 45 49 49 60 60 60 70
D 30 43 30 43 30 30 40
DIN Rail Mount l l l l l l –
Foot Mount l l l l l l l
Terminal Cover l l l l l l l
40A 25A 60A 1A 30A 100A 250A
300A 125A 600A 60A 75A 800A 1200A
17 SERIES16 SERIES14 SERIES13 SERIESSERIESTYPE 175TYPE 164TYPE 162TYPE 160TYPE 143TYPE 141TYPE 132
PRIMARYCURRENT
Inside Dia. (mm) Ø 45 – 60 60 85 –
Busbars (mm) 60 x 15 60 x 30 60 x 30 80 x 10 100 x 30 100 x 5550 x 30 50 x 50 60 x 30 80 x 50
Dimensions (mm) H 108 126 124 124 160 144
W 85 90 100 100 135 129
D 30 45 40 40 40 40
DIN Rail Mount – – – – – –
Foot Mount l l l l l l
Terminal Cover l l l l l l
400A 400A 400A 400A 400A 600A
1600A 1600A 2000A 2000A 4000A 4000A
21 SERIES20 SERIES18 SERIESSERIESTYPE 21TYPE 208TYPE 206TYPE 186
All current transformers are supplied as standard with 5A secondry. 1A secondry available by request.A range of accuracies are available from 0.2S to class 3, protection and class X.
62
127 SERIESTYPE CTH127L
H
W
Ø
D
H
W
Ø
D
Our policy is one of continuous development and therefore specifications may change without notice.
HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD
WALSALL WS1 2EB ENGLAND
Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: sales@hobut.co.uk
http://www.hobut.co.uk
PRIMARYCURRENT
Inside Dia. (mm) Ø – – – – – – –
Busbars (mm) 127 x 38 127 x 54 65 x 32 84 x 34 105 x 38 127 x 38 127 x 54
Dimensions (mm) H 115 140 113 135 156 178 178
W 160 160 90 96 98 98 125
D 40 40 45 40 40 40 40
DIN Rail Mount – – – – – – –
Foot Mount l l l l l l l
Terminal Cover l l l l l l l
400A 400A 150A 150A 200A 400A 400A
4000A 6000A 2000A 2500A 4000A 4000A 6000A
RECTANGULAR MOULDED CASESERIESTYPE CTV127LTYPE CTV127MTYPE CTV105TYPE CTV84TYPE CTV65
PRIMARYCURRENT
Inside Dia. (mm) Ø 16 21 25 or 31
Busbars (mm) 16mm 21mm 25mm or 31mmAPERTURES APERTURES APERTURES
Dimensions (mm) H 80 79 90
W 75 105 140
D 60 38 38
DIN Rail Mount – OPTION OPTION – –
Foot Mount l l l – OPTION
Terminal Cover l l l – –
60A 100A 250A 100A 1A
160A 250A 600A 6000A 6000A
RING TYPECAST RESINSERIES
All current transformers are supplied as standard with 5Asecondry. 1A secondry available by request.
A range of accuracies are available from 0.2S to class 3,protection and class X.
MANUFACTUREDTO ORDER
ANY SIZEANY BUSBAR
MANUFACTUREDTO ORDER
ANY SIZEANY BUSBAR
QualityHOBUT products are manufactured to stringentQuality Control techniques and the company isapproved to ISO 9001 certification.
3 PHASETYPE CT140FTYPE CT105FTYPE CT75
TYPE CTH127M
NEW
CUSTOMPRODUCTSHoward Butler Ltd.manufacture special CTsfor various applicationsthroughout the world. We manufacture highaccuracy CTs such as 0.2S& 0.5S, protection CTssuch as 5P10 & 5P20,Class X CTs and more. We can provide a solutionfor every low voltage CT application.
63
64
65
66
67
Circuit breakers PR 60 J
A 15
Technical data PR 60 J – DCStandards EN 60 898-1, EN 60 947-2Number of poles 1, 2Instantaneous tripping characteristics C - according to EN 60 898-1, M - according to EN 60 947-2Rated current In A 0,2 - 63Rated voltage Un V 220; 440Short-circuit breaking capacity kA 4,5Electrical endurance switching cycles 4 000Mechanical endurance switching cycles 100 000Cross sectional area of inlet conductors mm2 1,5 - 25 for Cu conductors
2,5 - 25 for Al conductorsMounting on rail DIN 35x7,5 EN 60 715
on boardDegree of protection IP 20
IP 40 from the front panelAmbient air temperature °C from -25 to +55Working positions optionalResistance against vibrations 3g(8-50Hz)Approved ESS, ESČAccesories auxiliary and signal contacts - PKJ, 2PKJ,PKJ+SKJ
shunt trip - VCcovers - KSP1, KSP3indications labels - ŠNlockable operating means - UP1sealing blind - PZmounting brackets - PP, PL, PPL
Charakteristic CRated cur-rent In, A
Type desig-nation
Ordering number
0,5 PR 61J-C 0,5 00995101 PR 61 J-C 1 00995112 PR 61 J-C 2 00995123 PR 61 J-C 3 00995134 PR 61 J-C 4 00995146 PR 61 J-C 6 00995158 PR 61 J-C 8 0099516
10 PR 61 J-C 10 009951713 PR 61 J-C 13 009951816 PR 61 J-C 16 009951920 PR 61 J-C 20 009952025 PR 61 J-C 25 009952132 PR 61 J-C 32 009952240 PR 61 J-C 40 009952350 PR 61 J-C 50 009952463 PR 61 J-C 63 00995250,5 PR 62 J-C 0,5 00995501 PR 62 J-C 1 00995512 PR 62 J-C 2 00995523 PR 62 J-C 3 00995534 PR 62 J-C 4 00995546 PR 62 J-C 6 00995558 PR 62 J-C 8 0099556
10 PR 62 J-C 10 009955713 PR 62 J-C 13 009955816 PR 62 J-C 16 009955920 PR 62 J-C 20 009956025 PR 62 J-C 25 009956132 PR 62 J-C 32 009956240 PR 62 J-C 40 009956350 PR 62 J-C 50 009956463 PR 62 J-C 63 0099565
Rated cur-rent In, A
Type desig-nation
Ordering number
0,8 PR 61J-M 0,8 00995301,2 PR 61J-M 1,2 00995312 PR 61 J-M 2 00995323 PR 61 J-M 3 0099533
4,2 PR 61 J-M 4,2 00995346 PR 61 J-M 6 00995358 PR 61 J-M 8 0099536
10 PR 61 J-M 10 009953712 PR 61 J-M 12 009953814 PR 61 J-M 14 009953917 PR 61 J-M 17 009954021 PR 61 J-M 21 009954125 PR 61 J-M 25 009954232 PR 61 J-M 32 009954340 PR 61 J-M 40 009954450 PR 61 J-M 50 009954563 PR 61 J-M 63 00995460,8 PR 62 J-M 0,8 00995701,2 PR 62 J-M 1,2 00995712 PR 62 J-M 2 00995723 PR 62 J-M 3 0099573
4,2 PR 62 J-M 4,2 00995746 PR 62 J-M 6 00995758 PR 62 J-M 8 0099576
10 PR 62 J-M 10 009957712 PR 62 J-M 12 009957814 PR 62 J-M 14 009957917 PR 62 J-M 17 009958021 PR 62 J-M 21 009958125 PR 62 J-M 25 009958232 PR 62 J-M 32 009958340 PR 62 J-M 40 009958450 PR 62 J-M 50 009958563 PR 62 J-M 63 0099586
1 - pole
Scheme Picture
2 - pole
Scheme Picture
Charakteristic M
1 - pole
2 - pole
68
Circuit breakers PR 60 J
A 16
Protection of DC circuits
It is possible to use both PR 60 and PR 60 J miniature circuit breakers for protection of DC circuits depending on voltage.
For voltage Un up to:
• 40Vd.c.useminiaturecircuitbreakersPR60.Sourcepoles(+)and(-)canbeconnectedtothe circuit breaker terminals arbitrarily.• 220Vd.c.or440Vd.c.,useminiaturecircuitbreakersPR61JorPR62J.Astheseminiaturecircuit breakersareequippedwithpermanentmagnets,sourcepoles(+)and(-)mustbeconnectedto identicallymarkedterminalsofthecircuitbreakers(seeconnectionexample).
69
70
71
72
73
74
75
76
77
78
79
80
81
82
CONTA-CLIP
Product overview
Three-wire installation
terminals DLI|DLIS
Page 80
Screw connection system
SRK|SSL
Page 16
Screw connection system
RK|SL
Page 24
Double-level terminal blocks
RKD|RKDG
Page 46
Test-disconnect
terminals PTK
Page 68
Fuse-disconnect terminals
STK|SIK
Fused terminals SK
Page 72
Feed-through terminals for
direct no-rail mounting
Page 92
Tension-spring connection
system
ZRK|ZSL
Page 138
Double-level terminal blocks
ZRKD| Double-level PE
terminal ZSLD
Page 152
Triple-level terminal block
ZIKD
Page 158
Screw connectionsystem
Pressure-springconnection system
Pressure-spring connection
system
FRK|FSL
Page 106
Disconnect-blade terminals |
Disconnect terminals | Fused
terminals FTRK
Page 122
Double-level terminal blocks
FRKD | Double-level PE
terminal FSLD
Page 116
8
CONTA-CONNECT
Tension-springconnection system
83
Triple-level terminal block
IKD|IK
Page 58
Triple-level terminal block
IKD|DLI
Page 56
Disconnect terminal
TRK|STK 2|TK
Page 62
Motor-connection terminal
VMAK
Page 57
Pluggable connection system
PK-TS
Page 100
Disconnect-blade terminals |
Disconnect terminals | Fused
terminals FTRK
Page 162
Three-wire installation
terminals FDLIS
Page 128
Motor-connection terminal
ZVMAK
Page 159
Compact terminal series for
direct mounting ZSRK | ZSLN
Page 178
9
84
CONTA-CLIP
Product overview
End stops
Page 274
End support
Page 274
Cuttable terminal rails EKB
Page 224
Shield-connection clip SAB |
SSAB
Page 230
DIN rails TS
Page 268GENERALACCESSORIESCONTA-CONNECT
10
CONTA-CONNECT
Ceramic terminal blocks KKB
Page 228
Stud connection system HSK
Page 186
Transformer terminals
TKS|TK
Page 198
SPECIAL TERMINALS Feed-through terminals RK | Fused
terminals SIK/SK, in high-temp.
design
Page 206
Test adapters
Page 318
labelling adapters
Page 314
Test plugs
Page 317
Fuse holders
Page 322
85
Shield-connection clip SAB |
SSAB
Page 230
EX terminal blocks ATEX
Page 242
Marker holders for terminal
blocks and end stops
Page 276
Cross-connections
(Potential distribution)
Page 282
11
Covers
Page 310
End plates | Visual separation
Page 278
Terminal blocks for temperature
measuring circuits TSK
Page 210
Screw-distributor blocks SVB
Page 218
Terminal blocks with spade
connection FF/SF
Page 212
Pressure-spring junction
terminals D
Page 222
Fuse cartridges
Page 324
Specific accessories
Page 326
CE electrical cabinet
socket outlet
Page 330
86
87
AUXILIARY RELAYS FOR TRIPPING APPLICATIONS
88
Auxiliary relays | Tripping applications
ARTECHE offers a wide range of relays specially designed to be used in circuit breaker tripping applications.
› Interface between protection and control equipments and HV and/or MV circuit breakers, eliminating risks in case of internal failure of the circuit breaker.
› Trip contacts multiplication, to operate directly on the circuit breaker and transmit the corresponding alarms in a minimum time.
› Trip and lock-out, with electric or hand reset to avoid accidental closing of circuit breakers associated to power transformers, generators or machines.
› The surveillance of the trip circuit, guarantees it is in perfect conditions to allow the trip when it is needed.
ANSWER FOR ANY TRIPPING APPLICATION
In addition to the specific applicable standards, ARTECHE auxiliary relays are designed based on the fulfilment of the following standards:
› IEC 61810: Electromechanical all-or-nothing relays.
› IEC 60255: Electrical relays. Measuring relays and protection
equipment.
› IEC 61812: Specified time relays for industrial use.
› IEC 61812: Relés de tiempo especificado para aplicaciones
industriales.
› IEC 60947: Low-voltage switchgear and controlgear.
› IEC 61000: Electromagnetic compatibility.
TECHNICAL STANDARDS
GENERAL STANDARDS
89
usAuxiliary relays | Tripping applications
Some of the general characteristics of the ARTECHE trip relays are:
In addition, the different number of alternatives that are offered when the equipment is selected, both technically (increase of the breaking capacity by serial contacts or by the magnetic blow out, high speed operation of the output contacts, possibility of adding different options to the relay) and in the assembly method (front, rear or flush mounted sockets, with screws or fastons) must be considered.
› High isolation level between input and output circuit, which guarantees that a problem in the circuit breaker will not cause irreparable damages on the protection system.
› Fast operating times, down to 3 ms, minimizing the impact on the total trip time.
› High breaking capacity, which allows direct operation on highly inductive circuits.
› Sturdy design, which ensures high reliability.
› Wide range of auxiliary voltage (Vdc and Vac).
› Self-cleaning of the contacts.
› Security contacts according to EN 50205.
› Easy installation (plug-in relays with diff erent installation possibilities).
› Designed to work in permanent service, even at high temperature for the whole voltage range.
› Possibility to work in environments with relative humidity of 100%.
› Seismic characteristics, allowing their use in installations which can be subject to vibrations, as for example in power stations or in regions with high risk of seism.
› High protection degree (IP40), with transparent cover, making them appropriate for tropical and saline environments.
› Fulfi lment of the most demanding standards: IEC, EN, IEEE, CE and UL mark.
› No maintenance needed.
GENERALCHARACTERISTICS
90
Auxiliary relays | Tripping applications
RANGE OF PRODUCTS
Instantaneous trip relays, whose contacts change instantaneously from the rest position to the working position when the coil is energized. The contacts return to the rest position when the coil is no longer energized.
This range includes relays with 2, 4 and 8 contacts, with operating times from 3 ms to 8 ms, depending on the model.
All the relays include a diode in parallel with the coil (see auxiliary relays with overvoltage protection characteristic) and comply with the sock and vibration standards, related to the relays with seismic characteristics.
Trip relays with 2 stable positions for the output contacts. Depending on which coil is energized, the contacts will change from one position to the other. The design of the ARTECHE relays has no consumption in permanence, and prevents both coils from being energized simultaneously.
This range includes relays with 3, 4 and 8 contacts, with operating times below 10 ms, depending on the model, and possibility of manual reset. The position change is made with 2 sets of coils with separated entrances, in BF-3 and BJ-8, and with breaking-flame contacts for each set of coils.
For single phase or three phase circuit breakers. Through a small supervision current the whole circuit is supervised, in both positions of the circuit breaker (opened or closed).
The correct state of the circuit is showed with a green LED on the front plate of the relay. The output contacts change its position if the relay detects a failure in the continuity of the circuit.
Auxiliary relay with four changeover contacts, aimed to supervise the failure of trip supply. Connecting the relay across the trip circuit supply, the equipment is normally energized. Faults will occur when the trip voltage is lost, so the relay drops off in those cases, providing the related signs and alarms.In order to avoid faulty alarms due to instantaneous supply voltage dips, the drop off time of the relay is delayed over 100 ms so those non-permanent failures of trip supply would not be considered.
TRIP RELAYS
TRIP AND LOCKOUT RELAYS
TRIP CIRCUIT SUPERVISION RELAYS
AUXILIARY SUPPLY CIRCUIT SUPERVISION RELAYS
91
c'i\lus (Auxiliary relays | Tripping applications
TRIP RELAYS (I)Model RD-2R RD-2XR RF-4R RF-4XR
Applications Intended for tripping applications where high demanding requirements in operating time (with tripping time from 8ms to 3 ms) and breaking capacity are needed,
that is the case of tripping HV and MV circuit breakers.
High burden confi guration not available See page 15 for technical details
Construction characteristics
Contacts no. 2 Changeover 4 Changeover
Connections
OptionsWith 0P options • LED included • Diode in parallel with the coil included
Weight (g) 125 250
Dimensions (mm) 22,5 x 50,4 x 72 42,5 x 50,4 x 72 (F short Type)
Coil characteristics
Standard voltages(1) 24, 48, 110, 125, 220,
250 (4) Vdc /110, 127,
230 Vac (50-60Hz)
24, 48, 110, 125, 220,
250 Vdc
24, 48, 110, 125, 220,
250 (4) Vdc / 110, 127,
230 Vac (50-60 Hz)
24, 48, 110, 125, 220,
250 (4) Vdc
Voltage range +10% -20% UN
Pick-up voltageSee pick-up/release voltage-temperature curves
Release voltage
ConsumptionsIn permanence (U
N)
Peak • ≤96 Vdc
Peak • >96 Vdc
0,95 W 1 W
0,8 A / 20 ms 2,5 A / 20 ms 0,8 A / 20 ms 2,5 A / 20 ms
0,3 A / 20 ms 0,8 A / 20 ms 0,3 A / 20 ms 0,8 A / 20 ms
Operating time
Pick-up time <8 ms (<10 ms Vac) <5,5 ms <8 ms (<10 ms Vac) <5,5 ms
Drop-out time Vdc: <40 msVac: <50 ms
Vdc: <40 ms Vdc: <40 msVac: <50 ms
Vdc: <40 ms
Contacts
Contact material AgNi
Contacts resistance(2) ≤30 mΩ
Distance between contacts 1,2 mm
Permanent current 10 A
Instantaneous current 30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact confi guration type B)
Max. breaking capacity See value for 50.000 operations
Umax
opened contact 250 Vdc / 400 Vac
Perfomance data
Mechanical endurance 107 operations
Operating temperature -25ºC +70ºC
Storage temperature -30ºC +70ºC
Max. operating humidity 93% / +40ºC
Operating altitude(3) <2000 m
(1) Other voltage upon request (2) Guarantee data for relays just manufactured
(3) Ask for higher altitudes (4) Voltage not recognized by UL
1
2
( –)
( +)
711
12
13
14
10
5
3
4 8
9
6
2( +)
1( –) 7
53
4
8
6
92
c'i\lus (,,-
.
Auxiliary relays | Tripping applications
3
1
a
d
( –)
( +)
2
4
5
6
7
8
1110
202130314041505160
70
80
61
71
81
Model RJ-8R RJ-8XR RJ-4XR4
ApplicationsIntended for tripping applications where high quality requirements in operating time (with
models even tripping in less than 3 ms) and breaking capacity are needed, that is the case of
tripping HV and MV circuit breakers.
High burden confi guration See page 15 for technical
details
See page 15 for technical
detailsnot available
Construction characteristics
Contacts no. 8 Changeover4 Changeover +
4 Fast Singles-Inversors without break power
Connections
Options With 0P options • LED included • Diode in parallel with the coil included
Weight (g) 500 335
Dimensions (mm) 82,5 x 50,4 x 72 (J short type) 42,5 x 50,4 x 82,5 (F short Type)
Coil characteristics
Standard voltages(1) 24, 48, 110, 125, 220, 250 (4) Vdc/110, 127, 230 Vac (50-60 Hz)
24, 48, 110, 125, 220, 250(4) Vdc
110, 125, 220, 250 (4) Vdc
Voltage range +10% -20% UN
+15% -20% UN
Pick-up voltage / Release voltage See pick-up/release voltage-temperature curves
Consumptions In permanence (U
N)
Peak • ≤96 Vdc
Peak • >96 Vdc
1,4 W 6,5 W
0,8 A / 20 ms 2,5 A / 20 ms 25 W / 5 ms
0,3 A / 20 ms 0,8 A / 20 ms
Operating time
Pick-up time <8 ms Vdc (<10 ms Vac)(Range 24 Vdc <10 ms)
<6,5 ms Contacts 1-4: <3 msContacts 5-8: <20 ms
Drop-out time Vdc: <40 msVac: <50 ms
Vdc: <40 ms Contacts 1-4: <25 ms Contacts 5-8: <50 ms
Contacts
Contact material AgNi Contacts 1-4: AgNi 10 Contacts 5-8: Ag1000
Contacts resistance(2) ≤30 mΩ
Distance between contacts 1,2 mm Contacts 5-8: 1,2 mm
Distance between contacts 10 A Contacts 5-8: 15 A Contacts 1-4: 8 A
Instantaneous current 30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact confi guration type B)
Max. breaking capacity See value for 50,000 operations
Umax
opened contact 250 Vdc / 400 Vac
Perfomance data
Mechanical endurance 107 operations
Operating temperature -25ºC +70ºC
Storage temperature -30ºC +70ºC
Max. operating humidity 93% / +40ºC
Operating altitude(3) <2000 m
5
7
d
a
( +)
( -)
6
4
3
2
1
88180
707160615051404130
20
10
31
21
11
Hig
h br
eaki
ng
capa
city
Trip
TRIP RELAYS (II)
(1) Other voltage upon request (2) Guarantee data for relays just manufactured
(3) Ask for higher altitudes (4) Voltage not recognized by UL
93
Auxiliary relays | Tripping applications
(1) Other voltage upon request (2) Ask for higher altitudes
Model RXR-4
Applications Tripping applications with very high speed requirements
High burden confi guration not available
Construction characteristics
Contacts no. 4 Changeover
Connections
Options No options available
Weight (g) 126
Dimensions (mm) 53 x 90 x 58
Coil characteristics
Standard voltages(1) 110, 125, 250 Vdc
Voltage range +10% -20% UN
Pick-up voltage 40%
Release voltage 28%
Consumptions <3 W
Operating time
Pick-up time <3 ms
Drop-out time <3 ms
Contacts
Contact material AgNi
Permanent current 8 A
Max. making capacity 15 A during 4s
Breaking capacity See breaking capacity curves
Umax
opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations
Operating temperature -10ºC +55ºC
Storage temperature -30ºC +70ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2,000 m
TRIP RELAYS (III)
1
2
( –)
( +)
NO1
NC2
N02
N03
N04
NC3
NC4
NC1
C1
C2
C3
C4
94
c'i\lus
=--r-=--r-=--r-=--r-=--r-=--r-=--r-=--r-
Auxiliary relays | Tripping applications
(1) Other voltage upon request (2) Ask for higher altitudes
TRIP AND LOCKOUT RELAYS (I)Model BF-3R BF-4R BJ-8R
Applications Intended for trip and lockout applications where high demanding requirements in operating time and breaking capacity are needed.
High burden confi gurationnot available
See page 15 for technical
details
See page 15 for
technical details
Construction characteristics
Contacts no. 3 Changeover 4 Changeover 8 Changeover
Connections
Options Options are not available
Weight (g) 300 600
Dimensions (mm) 45 x 45 x 96,5 (F short Type) 90 x 50 x 100,5(J short Type)
Coil characteristics
Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac (50-60 Hz)
Voltage range +10% -20% UN
Pick-up voltage See pick-up voltage / temperature curves for Latching relays
Consumptions only in the change-over 27 W 23 W 35,5 W
Operating time
Pick-up time <10 ms (Vdc) <20 ms (Vac) <10 ms (Vdc) <20 ms (Vac)
Contacts
Contact material AgNi
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 880 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact confi guration type A)
Max. breaking capacity See value for 50.000 operations
Umax
opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations
Operating temperature -40ºC +70ºC
Storage temperature -40ºC +70ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m
913812711
5
4
3
1410
21
+-
+-
Set
Reset
10149138
712
11
6
5
4
3
B1
12-
+
+
Set
Reset
11
51
21
61
20
60
31
71
41
81
30
70
40
80
1
5
2
6
3
7
4
8
a
c
b
d
+
+
-
-
Set
Reset50
10
95
=-r=-r=-r
~ =-r-L2:r =-r
=-r=-r=---r-
c'i\lus (
Auxiliary relays | Tripping applications
(1) Other voltage upon request (2) Ask for higher altitudes
TRIP AND LOCKOUT RELAYS (II)Model BF-4RP BJ-8RP
Applications Intended for tripping and locking applications where high quality requirements in operating
time and breaking capacity are needed, with manual reset.
High burden confi guration See page 15 for technical details See page 15 for technical details
Construction characteristics
Contacts no. 4 Changeover 8 Changeover
Connections
Options Options are not available
Weight (g) 300 600
Dimensions (mm) 45 x 45 x 96,5 (F short Type) 90 x 50 x 100,5 (J short Type)
Coil characteristics
Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc63,5, 110, 127, 230 Vac (50-60 Hz)
Voltage range +10% -20% UN
Pick-up voltage (20ºC) See pick-up voltage / temperature curves for Latching relays
Consumptions only in the change-over 23 W 35,5 W
Operating time
Pick-up time <10 ms (Vdc) <13 ms (Vac) <10 ms (Vdc) <20 ms (Vac)
Contacts
Contact material AgNi
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact confi guration type A)
Max. breaking capacity See value for 50,000 operations
Umax
opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations
Operating temperature -40ºC +70ºC
Storage temperature -40ºC +70ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m
11
51
21
61
20
60
31
71
41
81
30
70
40
80
1
5
2
6
3
7
4
8
a
c
b
d
+
+
-
-
Set
Reset50
10
10149138
712
11
6
5
4
3
B1
12-
+
+
Set
Reset
96
c'i\lus (EAuxiliary relays | Tripping applications
(1) Other voltage upon request (2) Ask for higher altitudes
Model VDF-10 VDJ-30
Applications Trip circuit supervision for single-phase circuit
breakersTrip circuit supervision for three-phase circuit
breakers
Construction characteristics
Timing Contacts no. 2 Changeover 2 Changeover
Connections
Options Options are not available
Weight (g) 100 163
Dimensions (mm) 42,5 x 50,4 x 96,6 (F short Type) 82,5 x 50,5 x 96,6 (J short Type)
Coil characteristics
Standard voltages(1) 24/30, 60, 110/125, 220 Vdc, 110/127, 230 Vac (50-60 Hz)
Voltage range +10% -25% UN
Pick-up voltage (23º C) 70% UN
Release voltage (23º C) 50% UN
Consumptions 3,1 W 3,63 W
Operating time
Drop-out time >200 ms
Contacts
Contact material AgNi
Permanent current 8 A
Instantaneous current 15 A
Max. making capacity 15 A during 4 s
Max. breaking capacity 0,3 A / 110 Vdc
Umax
opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations
Operating temperature -10ºC +55ºC
Storage temperature -30ºC +70ºC
Max. operating humidity 93% / +40ºC
Operating altitude(2) <2000 m
TRIP CIRCUIT SUPERVISION RELAYS
+
-
TRIP SUPPLY
TRIP SUPPLY
Trip contact
6 51 4
FU
FU
CB
CIRCUIT BREAKER
K1 K2
10 14 9 132 12 8
52a 52b
TRIP SUPPLY
+
-TRIP SUPPLY
1Trip contact
1 2
CB1
FU
FU
CB2 CB3
CIRCUIT BREAKER
a
h
K11
11 21 31 41 7110
52a
52a
52a
52b
52b
52b
20 30 40 70
K21
K12
K22
K13
K23
3 b 4 e 7
2
Trip contact
3
Trip contact
97
Auxiliary relays | Tripping applications
(1) Other voltage upon request (2) Guarantee data for relays just manufactured (3) Ask for higher altitudes
Model RUT-4
Applications Supervise only the auxiliary supply circuit of the protection equipments,
avoiding false alarms due to short-time drop of supply
Construction characteristics
Timing Contacts no. 4 Changeover
Connections
Options Options are not available
Weight (g) 250
Dimensions (mm) 42,5 x 50,4 x 96,6 (F short Type)
Coil characteristics
Standard voltages (1) 24, 48, 72, 110, 125, 220 Vdc
Voltage range +10% -20% UN
Pick-up voltage See pick-up release voltage-temperature curves for standard relays
Release voltage
Consumptions in permanence 3,9 W
Operating time
Pick-up time <20 ms
Drop-out time To minimum voltage
Maximum>100 ms<400 ms
Contacts
Contact material AgNi
Contacts resistance (2) ≤30 mΩ
Distance between contacts 1,8 mm
Permanent current 10 A
Instantaneous current 80 A during 200 ms / 200 A during 10 ms
Max. making capacity 40 A / 0,5 s / 110 Vdc
Breaking capacity See breaking capacity curves (Contact Confi guration Type A)
Max. breaking capacity See value for 50.000 operations
Umax
opened contact 250 Vdc / 400 Vac
Performance data
Mechanical endurance 107 operations
Operating temperature -10ºC +55ºC
Storage temperature -30ºC +70ºC
Max. operating humidity 93% / +40ºC
Operating altitude(3) <2000 m
AUXILIARY SUPPLY SUPERVISION RELAYS
11
3
(-)(-) 1
(+)(+) 2
4
5
6
12
13
14
7
8
9
10
98
Auxiliary relays | Tripping applications
HIGH / LOW BURDEN CONFIGURATION (HIGH SPEED TRIPPING RELAYS ONLY)
The standard high speed tripping relays are manufactured with a low burden configuration, considering that the initiating contact is placed close to the tripping relay.
However, and in order to avoid unwanted trip relay operation due to pickup or transients, particularly if the relay operating coil is connected to extensive wiring, ARTECHE tripping relays could be manufactured with a high burden configuration, complying with ESI 48-4 international standard, as EB2 class relays. These EB2 class relays are suitable for use in high security circuit breaker tripping circuits, increasing their immunity to capacitance discharge currents.
Instantaneous relays (self reset relays): same consumption as low burden configuration
Latching relays (electric and hand&electric reset): See table below
For relays with rated voltage up to and including the 125 V, the relays will withstand, without operating, a discharge into their operate circuits of a 10μF capacitor charged to 120% of the higher rated voltage for the relay.
For relays with rated voltage of 220 V, the relays will withstand, without operating a discharge into their operate circuits of a 10μF capacitor charged to 100% of the higher rated voltage for the relay, i.e 242 V.
Specifications:
ESI 48-4 EB1: 1983 Low BurdenESI 48-4 EB2: 1983 High Burden
HIGH BURDEN RELAYS CONSUMPTIONS
Electrical reset and hand and electrical reset relays
Standard Voltage 220 Vdc 125 Vdc 24 Vdc
Consumption (only in commutation) < 150 W (peak) < 100 W (peak) < 75 W (peak)
99
OGIPRO
Company
First National Pakistan155-A Sarfraz Rafiqui RoadLahore Cantt.Pakistan
Our sign JE Peggau, 01st September 2013
Authorized Distribution Letter
Dear Sirs,
GIPRO GmbH in Peggau Austria hereby confirms that First National Pakistan, 155-ASarfraz Rafiqui Road, Lahore Cantt., Pakistan is authorized to represent and to sellGIPRO products in the area of PAKISTAN.
The products are:In- and Outdoor epoxy insulators for several different applicationsSurge arrestors for several needs
With kind regards,
L
Mana ing Director
AnschriftGIPROGmbHWilhelm-Jentsch-Strasse2A 8120 Peggau
BankverbindungBank Die SteiermiirkischeBLZ 20815Kto.Nr. 0000-958702IBAN AT642081500000958702SWIFT/BIC STSPAT2G
FirmendatenFN 144442sUID-Nr ATU40635906ARA-Lizenz 4622
Kommunikation
20130901 JE GIPRO Authorized distribution letter to First National Pakistan.doc
Tel +433127209400Fax +43 3127 20940 40Email info@gipro.comhttp://www.gipro.com
100
theperFectFit
101
102
Reference Adress for supply:
GIPRO GmbH
Wilhelm-Jentsch-Strasse 2
8120 Peggau
AUSTRIA - EUROPE
info@gipro.com | www.gipro.com
103
104
105
;;
J
TYPE TEST REPORTS relating toVARISlLTMHE polymer housectsurge arresters & associated accessories
I
TYPE TESTS REFERENCE SAMPLES TEST REPORT ADDITIONALPERFORMED STANDARD TESTED Reference Dete ' Langutf!!1_6 INFORMATION
, Housings rated CESI12 kV, 24 kVAT-A1f025452 September 3, 2001 English
Insulation withstand tests. &.36kVon the housings lEG 600994- Housing rated CESI
,
& § 10..8.2 1B kV &. type S3 AT ·A1/025961 September 5, 2001 English ,
the insu'latin9 bracketI insulating bracket .I
,
Housing rated CESI August 10, 2006 English, 42 kV A6/02i821 I
Technical dooumentSteep, lightning TPF ST HE 041 e rev. 02 Iand switching lEG 60099-4 6 kV CBSI , (January 4, 2010, English)currenl impulse § 10.8.3 prorated sections AT-AOJ041526 January 25, 2001 English &. Voltage vs current characteristic curve :
residual voltage tests VI 8997 01 XX (E rev. 03II (January "I, 2010, Engllsh)
HE18S0 C.ESI June 7, 2001 EnglishLong duration current lEG 60099-4 surge arresters AT-A1J014923 I
I impulse withstand test §10.8..4 6 kV 81D2 CESI •'September 28,2005 English ,
, prorated sections A5f0465386 kV CESI
January 25, 2001 English I
_prorated sections AT-AO!041527High Gurrent impulse IEC 60099-4 HE 18 80 CBS'I I i
I June 7, 2001 EngUsh, operating duty test § 10.8.5 surge arresters AT -A 1/014924
6 kV S1D2 CESI December 14, 2005 English,
prorated sections A5/055428
Date: January g, g013 Page: 1 J 2Refer.ence : TPF ST HE 01/ E rev. 19,
106
TYPE TESTS REFERENCE SAMPLES TEST REPORT ADDITIONAL IPERFORMED STANDARD TESTED Reference Date Language INFORMATION
Voltage vs time IEC 60099-4 HE range Curve UT 8997 01 XX I E rev. 02characteristic curve § 6.10 (January 4,2010, English)
lEG 60099-4 CESI September 14,2011 EnglishTest carried out
§ 8.6.2.1 8102744'9 in series with a 6 kV 53D2 section
Tests on lEG 60099-4 Type S3D2 CESI September 14,2011 English Test carried out
disconnector _§_ 8.6.2.2 disconnector 81027448 in series with a 6 kV S302 section
lEe 60099-4 CESICurrent vs time characteristic curve
September 13, 2011 English CT 8997 09 9X I E rev. 02§ 8.6.3 B1027905 J (September 14, 20·11, English)
Tests on lEG 60099-4 Type IF CESICurrent vs time characteristic curve
September 11, 1997 English CT 899509 04 I E rev. 08fault indicator § 8.6.4 fault indicator MP·97/026984 (January 4,2010, English)
Short circuit tests IEC 60099-4 HE 24 CESIJune 25, 2008 English§ 10.B.7 surge arresters A8018577
Partial discharge test lEG 60099-4 HE 36 CESI December 22,2000 Engllish§ 10.8.8 surge arresters AT·AOJ042489
Bending moment test lEG 60099-4 HE 36 TRIDELTA I seas November 15, 2012 English§ 10.8.13 surge arresters TR.e 12018BMIEC 60099-4
HE 36 CESI t§ 10.8.14.2.1 December 18, 2002 English(1000 h test) surge arrester AT ·A2J032924
Weather ageing testlEG 60099-4§ 10.8..14.2.2 HE 24 CESI March 27, 2003 English(5000 h test)_ surge arrester AT ·A3/007530
b :reference Is.m_ to the Iatast version of lEe 60099-4 standard, ~ edition 22 published in May 2009
107
Type HE 12Rated voltage Ur in kV rms 12
Rated frequency Hz 50 / 60Continuous operating voltage Uc in kV rms 10,2
Nominal discharge current In in kA with 8/20 impulse 10Line discharge class Class 1
High current impulse withstand kA with 4/10 impulse (x 2) 100Maximum leakage current under Uc at 20 °C resistive component in mA peak 1,0
capacitive component in mA peak 0,5total current in mA rms 1,0
nergy absorption capability with 8/20 impulse kJ / kV of Ur 4,1kJ / kV of Uc 4,8
Long duration current impulse withstand A with 2000 µs impulse (x 18 + 1) 300ergy absorption capability with 2 ms impulse kJ / kV of Ur 2,0
kJ / kV of Uc 2,4kV peak at 2.5 kA 8/20 29,0
Maximum lightning residual voltage kV peak at 5 kA 8/20 30,8kV peak at 10 kA 8/20 32,8kV peak at 20 kA 8/20 36,2kV peak at 40 kA 8/20 41,2
Maximum switching residual voltage kV peak at 125 A 30/80 24,6kV peak at 500 A 30/80 26,1kV peak at 1 kA 30/80 27,1kV peak at 5 kA 1/2.5 32,3
mum steep current impulse residual voltage kV peak at 10 kA 1/2.5 35,4Temporary overvoltage capability in kV rms 1 s without prior duty 15,5
1 s with prior duty 14,01 s with maximum prior duty 13,5
10 s without prior duty 14,810 s with prior duty 13,3
10 s with maximum prior duty 12,9Minimum reference voltage at 20 °C Iref in mA peak AC 1
Uref in kV peak/V2 11,6Short circuit current withstand kA during 0.2 s 20
A during 1.0 s 600Axial partial discharge level pC under 1.05*Uc < 10
Mechanical strength specified short-term load SSL in N.m 125specified long-term load SLL in N.m 100
dynamic pull loading in N 750static pull loading in N 500
torsion in N.m 30Line terminal maximum conductor diameter in mm 18
permissible materials Cu / Al / SteelEarth terminal maximum conductor diameter in mm s/ option
permissible materials Cu / Al / SteelInsulation withstand power frequency 1 min dry in kV rms 42
power frequency 1 min wet in kV rms 381.2/50 lightning impulse dry in kV peak 95
Physical characteristics of the housing material siliconenb of weathersheds ( small / large ) 4 / 5
weathersheds diameter in mm 74 / 104Nominal creepage distance mm 480
mm / kV of Ur 40,0Nominal arc length mm 195
Option S3D21,7Approximate weight in kg
108
Adress of supply:
GIPRO GmbH
www.gipro.com
109
110
111
112
113