FIRE SERVICES AT DATA CENTRE

FM200 TRAINING COURSE

INTRODUCTION OF FM 200

THE PROPERTIES OF FM-200®

WHAT IS FM-200® ?

C C C

F F F

F F

F FH

ASHRAE Designation = HFC227eaASHRAE Designation = HFC227ea

Fire TriangleFuel, oxygen, heat

What is fire?A series of highly exothermic chain-branching free radical reactions

Removal of any element of fire triangle results in suppression

THE PHYSICS OF FIRE

Removes heat, so fire can’t sustain itself

FAST & EFFICIENT PERFORMANCE

FM-200® CHEMICAL/PHYSICALEXTINGUISHING MECHANISM

Physical

Chemical

80%

Physical

Chemical 20%

80%

20%

Halon 1301 FM-200®®

Cup Burner Conc. [Heptane] - 5.8%

Use Concentration [Minimum] - 7.5% for ISO compliance

Maximum Discharge Time limited to 10 Seconds

HOW IS FM-200® APPLIED?

Compact storage space requirements

FAST & EFFICIENT PERFORMANCE

Halon 1301

CO

Inert Gas

FM-200® iscompletely safe for use in occupiedspaces.

HUMAN SAFETY

Reaches extinguishing concentration within 10 seconds

Provides ACTIVE Fire Protection

FM-200® IS FAST & EFFECTIVE

FM-200® ENGINEERED SYSTEMS

14

ENGINEERED CENTRAL STORAGE FM-200® SYSTEM

Raised Floor

Distribution PipeDischarge Nozzles

Smoke Detectors

Manual Station

Containers

Computer Rooms

PRIMARY APPLICATIONS

3M™ Novec™ 1230 Fire Protection Fluid

Novec 1230 fluid has distinct environmental benefits Ozone depletion potential (ODP) of

0

5 day atmospheric lifetime

Global Warming Potential (GWP) of 1

THE NEW CLEAN AGENT

FM200 CONTROL EQUIPMENT

Kentec Panel Kentec lock off

FM200 CONTROL EQUIPMENT

Kidde Panel Kidde Panel

FM200 CONTROL EQUIPMENT

Chubb Panel Viking & Notifier Panel

FM200 CONTROL EQUIPMENT

Thorn Panel

FM200 CONTROL EQUIPMENT

FM200 CYLINDER

Kidde FM200

FM200 CYLINDER

Chemetron FM200

FM200 CYLINDER

ThornFM200

FM200 CYLINDER

Fike FM200

FM200 CYLINDER

Siemens FM200

FM200 CYLINDER

SIGNAGE BOX AND PRESSURE SWITCH

Signage Box Pressure Switch for Fed-back Signal

AUTO-MANUAL Mode Selection Provided Next to the Panel Outside the Room

When Personal Before Enter the Room:

- Switch the Auto-Manual Switch to “MANUAL” - “System Inoperative” Signal Box Flash - Switch Back to “AUTO” when Leave the Room

MODE SELECTION

Two Detection Zones for Each SystemCross Zone OperationActivating Anyone Zone:

- Alarm Sound - “Do Not Enter” Sign Flash, Don’t Enter the Room

FM200 OPERATION IN AUTO MODE

Two Zones Activated:

- Two-Tone Sounder Raised - “Evacuate” Sign Flash, Evacuate Room

Immediately - A/C in the Room Will Shunt Down - System Start Count Down for 30 Sec. - Gas Discharge to Room After Count Down

FM200 OPERATION IN AUTO MODE

When Personal Working inside the Room:One Zone of Alarm Activated and Alarm

Sound: - Check Any Fire Happened in Room - Inform Others to Leave the Room if Fire Happened - Go out of the Room, Push the “Manual Release”

Switch to Discharge Gas Two Zone Activated: - Evacuate Room Immediately - Go out of the Room, Push the “Manual Release”

Switch to Discharge Gas

FM200 SYSTEM OPERATION IN MANUAL MODE

Check Smoke Detectors- Corrosion- Dirty

- Generate False Alarm FrequentlyCheck Modules

- Simulate Tests to Check the Modules

Working Properly

MAINTENANCE OF AFA AND FM200 SYSTEMS

Monthly & Annual

- To Be Carried-Out By FS Contractor

MAINTENANCE

What is VESDA…

INTRODUCTION OF VESDA SYSTEM

Aspirating Smoke Detection吸气式烟雾探测

THEINTRODUCTION OF VESDA SYSTEM VESDA ADVANTAGE…

VESDA Panel VESDA Panel

INTRODUCTION OF VESDA SYSTEM

Kidde HSSD Panel Kidde HSSD Panel

INTRODUCTION OF HSSD SYSTEM

鐳射探測器主機板

風機

Kidde HSSD Sampling Point

INTRODUCTION OF HSSD SYSTEM

Pre-action System

INTRODUCTION OF PRE-ACTION SYSTEM

Pre-action System

INTRODUCTION OF PRE-ACTION SYSTEM

THANK YOU