View
7
Download
2
Category
Preview:
Citation preview
MUELLER TEMPLATE
April 2016
Department of Environment & Conservation - Gander Clean Water ShowPresenters: Jeff B. Jensen & John Palmer – Mueller CanadaMarch 27th, 2019
FIRE HYDRANT MAINTENANCE BEST PRACTICE
MUELLER TEMPLATE
April 2016
FOREWORD• AWWA Manual M17 @ ACWWA.CA• AWWA C502 standard • Canada Valve Darling troubleshooting manual 1002-
001
MUELLER TEMPLATE
April 2016
ANNUAL INSPECTION
• 2 x per year
• Check for damaged exterior parts
• Remove caps, clean, grease all – replace
• Flush Hydrant
• Use listening device for leaks while in open
• Close, repeat step
• Remove cap, inspect drainage
3
MUELLER TEMPLATE
April 2016
THIS IS NOT THE TIME FOR HYDRANT MAINTENANCE
4
MUELLER TEMPLATE
April 2016
PREVENTATIVE MAINTENANCE – CONFUSED?
5
MUELLER TEMPLATE
April 2016
KNOW YOUR HYDRANTS – HAVE TOOLS
6
MUELLER TEMPLATE
April 2016
DRY TOP OPERATION ASSEMBLY
• Operating assembly uses grease or oil
• Bearing lubricated each operation exercise
• One piece op nut / thrust collar per C502
• O-ring sealed
7
MUELLER TEMPLATE
April 2016
TRAFFIC FEATURE
• Bury line 3-4” above
• Breakaway FlangeBreakable Cast Traffic Flange
vsStrong Ductile Extension Flange
• Breakaway CouplingBreakable Cast or SS Coupling
vsStrong Ductile or solid SS
8
MUELLER TEMPLATE
April 2016
HYDRANT MAIN VALVE
9
• Main Valve Disc ‘ball’ –EPDM or SBR rubber
• Bronze Main Valve Seat resist corrosion
• Bronze Drain Ring for easy removal of main valve and self drain
MUELLER TEMPLATE
April 2016
DRY BARREL COMPRESSIONTYPE HYDRANT
• Moves vertically on a stem
• Seats against the hydrant base
• 5 ¼” or 4 ½” diameter main valve
10
MUELLER TEMPLATE
April 2016
THANK YOU FOLKS FOR KEEPING YOUR HYDRANTS OPERABLE
QUESTIONS?
11
Recommended