REVISIONS (DO NOT USE THIS BLOCK UNTIL AFTER PERMIT IS ISSUED)
HARRIS COUNTY (IFC 2012)FIRE CODE DESIGN AND COMPLIANCE REVIEW SHEET VERSION 6.0 (MAR 2015)
(http://hcpid.org/permits/docs/FC_FireCodeEffectiveMarch012015.pdf)
BUILDING PLANNING & DESCRIPTION1 MEANS OF EGRESS3 FIRE-RESISTANCE RATE CONSTRUCTION5 STORAGE: STANDARD & HIGH PILED9CHAPTER 10 IBC 2012 CHAPTER 6, 7 AND 10 IBC 2012 CHAPTER 32 IFC 2012 (REFER TO REGULATIONS FOR REQUIREMENT FOR CONSULTANT ENGINEER SECTION
3201.5 HC AMENDMENTS)
NEW CONSTRUCTIONLEASE SPACE BUILD-OUT (LSBO)
SUBSTANTIAL IMPROVEMENT
SHELL BUILDING
CHANGE OF OCCUPANCYOTHER: __________________________
SINGLE OCCUPANCY SEPARATED USE NON-SEPARATED USE
(SECTION 508.3 OR 508.4 IBC 2012)TYPE OF CONSTRUCTION: __________________________ (CHAPTER 6 IBC 2012)HEIGHT LIMITATION: __________________ AREA LIMITATION: ________________ (TABLE 503 IBC 2012)
BUILDING VALUATIONBUILDING NUMBER: ________ OF ________
CALL CENTERPOINT ENERGY AHEAD OF TIME, AT 713-207-4460, TO OBTAIN AN ADDRESS
ADDRESS: ____________________________________________________________________________________CITY, ST: ___________________________________ ZIP CODE: _________________ SUITE: _______________
ESTIMATED COST OF CONSTRUCTION: $_________________________________________________T.D.L.R #: ________________________________ (REQUIRED FOR CONSTRUCTION OVER $50,000)TEXAS DEPARTMENT OF LICENSING AND REGULATIONS(http://www.license.state.tx.us/)TELEPHONE: (512) 463-6599 TOLL FREE (IN TEXAS): 800-803-99202FAX: (512) 475-2871 RELAY TEXAS-TDD: 800-735-2989
HCAD #. OR PROPERTY TAX #: _________________________________ (13 DIGITS) FLOODPLAIN: _______
LIST BELOW THE PURPOSE/USE OF THE BUILDING OR AREA BEING REVIEWED. INCLUDEDETAILS ON THE PRODUCTS/MATERIALS BEING STORED/FABRICATED AND NOTE HOW THEYARE BEING PACKAGED.
SHELL BUILDING PERMIT #: ___________________________ CIVIL PROJECT #: _______________________
GROSS SQUARE FOOTAGE: __________________________ #OF FLOORS: ___________ HEIGHT:__________
OCCUPANCY TYPE AND LOAD2CHAPTER 2, 3 & TABLE 1004.1.2 IBC 2012
A-1 A-2 A-3 A-4 A-5 B E
F-1 F-2 H-1 H-2 H-3 H-4 H-5
I-1 I-2 I-3 I-4 M R-1 R-2
R-3 R-4 S-1 S-2 U
OCCUPANCY CLASSIFICATION TYPES
BREAK DOWN AREAS AND OCCUPANT LOADS PER FLOOR
OCCUPANCYCLASSIFICATION SPECIFIC USE
TOTAL
SQUAREFOOTAGE
SF PEROCCUPANT
DESIGNOCCUPANTS
# OF EXITS PROVIDED# OF REQUIRED EXITSMEANS OF EGRESS SHEET #
STAIRWAYS (PER FLOOR)
EGRESS @ 1ST FL OR LSBO
(SECTION 1005.3 IBC 2012)
PANIC HARDWARE ON EXIT DOORS? YES NO (SECTION 1008.1.9 IBC 2012)STAIRWAYS (SECTION 1009 IBC 2012)MINIMUM CLEAR WIDTH SHOWN ON: ________________________________ (EACH STAIRWELL)EGRESS WIDTHS ARE SHOWN ON: __________ACCESSIBLE AREAS OF REFUGE & 2-WAY COMMUNICATIONS SHOWN ON: ________
FRONTAGE INCREASE CALCULATIONS ARE SHOWN ON SHEET: __________________________________(SECTION 1007.3 TO 1007.6 IBC 2012)
EXIT SIGNS/EGRESS ILLUMINATION (SECTION 1006 & 1011 IBC 2012)REQUIRED AND SHOWN ON: ___________________________ (HIGHLIGHT ON PLANS)
EXTERIOR EMERGENCY LIGHTING PROVIDED? YES NOEXIT TRAVEL DISTANCE (TABLE 1016.2 IBC 2012)
PROVIDE TRAVELDISTANCEMAX TRAVEL DISTANCEOCCUPANCY TYPE SHEET #
ELEVATORSELEVATOR KEYBOX LOCATED IN LOBBY?(MUST BE WITHIN 20' OF THE CALL BUTTON)
NEW EXISTING YES NO
FIRE PROTECTION SYSTEMS4CHAPTER 9 IBC & IFC 2012
ALL FIRE PROTECTION PLANS SHALL BE SUBMITTED FOR REVIEW AFTER BUILDING PERMITHAS BEEN ISSUED (I.E. UNDERGROUND FIRE LINE, SPRINKLER SYSTEM, FIRE ALARM SYSTEM,STANDPIPE, AND FIRE PUMP ROOM)
AUTOMATIC FIRE SPRINKLER SYSTEM/ALTERNATIVE AUTOMATIC FIREEXTINGUISHING SYSTEMALL SPRINKLERS SHALL COMPLY WITH MONITORING(SECTION 903 HC FIRE CODE AMENDMENTS & SECTION 903.4 IFC 2012)
PROVIDED AS NOTED ON: __________ NOT REQUIRED PER SECTION 903
SYSTEM PROVIDED:NFPA 13NFPA 13RNFPA 13DOTHER: __________
STANDARDELOESFRQUICK RESPONSE
SPRINKLER HEAD PROVIDED:
FIRE DEPARTMENT ACCESS TO SPRINKLER CONTROLS:SPRINKLER RISER ROOM OR POST INDICATOR VALVE SHOWN ON: __________(SECTION 901.4.6.1 HC AMENDMENTS IFC 2012)
FDC SHOWN ON: __________ (FDC SHALL COMPLY WITH SECTION 912 IFC 2012)
SUPPRESSION SYSTEM PROVIDED (SECTION 904 IFC 2012)COMMERCIAL KITCHEN - EXHAUST HOOD WITH SUPPRESSION SHOWN ON: __________PAINT BOOTH SUPPRESSION SHOWN ON: __________OTHER: __________________________
STANDPIPE SYSTEM & HOSE CONNECTIONS (SECTION 905 IFC 2012)(I.E. IN STAIRWAYS, STAGES, MALLS)
PROVIDED AS NOTED ON: __________, TYPE OF SYSTEM PROVIDED: _________ (CLASS I, II OR III)NOT REQUIRED PER SECTION 905
PORTABLE FIRE EXTINGUISHERS (SECTION 906 IFC 2012)PROVIDED AS NOTED ON: __________, NUMBER PROVIDED: __________ (HIGHLIGHT ON PLANS)
FIRE ALARM & DETECTION SYSTEMS (SECTION 907 & HC AMENDMENTS IFC 2012)AUTOMATIC WITH SMOKE COVERAGECOMPLYING WITH HC AMENDMENTS - 907.2
EMERGENCY VOICE EVACUATIONMANUAL WITH NOTIFICATION
ELEVATOR RECALL - SUPERVISORY
NOT REQUIRED PER SECTION 907OTHER: ________________________
HVAC & AIR DISTRIBUTION SYSTEM CONTROLS (SECTION 907.2.13.1.2 IFC 2012)SMOKE DETECTORS PROVIDED TO SHUT DOWN UNITS OVER 2,000 CFM PROVIDED ON: __________
FIRE/SMOKE DAMPERS IN THE BUILDING SHOWN ON: __________NO FIRE/SMOKE DAMPERS IN THE BUILDING
SMOKE CONTROL SYSTEMS (SECTION 909 IFC 2012)(I.E. FOR HIGH RISE, ATRIUMSOR STAIRWAY PRESSURIZATION)
PROVIDED AS NOTED ON: __________
NOT REQUIRED PER SECTION 909
SMOKE & HEAT VENTILATION (SECTION 910 & TABLE 910.3 IFC 2012)CALCULATIONS PROVIDED AS NOTED ON: __________
NOT REQUIRED PER SECTION 910NOTE: WHERE AREAS OF THE BUILDING ARE EQUIPPED WITH EARLY SUPPRESSION FAST-RESPONSE(ESFR) SPRINKLERS, AUTOMATIC SMOKE AND HEAT VENTS SHALL BE INSTALLED PERMANUFACTURERS SPECIFICATIONS, MEETING LOCAL JURISDICTION REQUIREMENTS.
SHOW DETAILS OF FIRE WALLS OR FIRE BARRIERS MEETING HORIZONTAL WALLS AND ROOF DECKS(SEE SECTION 706.5, 706.6 & 707.5 IBC 2012)
FIRE-RESISTANCE RATING REQUIREMENTS (TABLES 601, 602 & 602.4 IBC 2012)
HOURSPROVIDED
HOURSREQUIREDBUILDING ELEMENTS UL OR IBC STANDARD USED &
DESIGN DETAIL SHOWN ONSTRUCTURAL FRAME
EXTERIOR BEARING WALLS
EXTERIOR NON-BEARING WALLS
INTERIOR BEARING WALLS
INTERIOR NON-BEARING WALLS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
STAIRWELLS (SECTION 1009)
CORRIDORS (SECTION 1018)
ELEVATOR SHAFTS (SECTION 713)
FIRE RATED DOORS (TABLE 716.5)
DEMISING/PARTITION WALL (SECTION 708)
FIRE BARRIER (SECTION 707)
FIRE WALL (SECTION 706)
DRAFTSTOPS: YES, SHOWN ON: __________ NO (SPRINKLED ATTIC) N/A (SECTION 718.4)
HAVE YOU CHECKED WIDTH OF OPENINGS IN FIRE RATED WALLS?(TABLE 705.8, SECTION 706.8 & 707.6 IBC 2012)
YES NO
FIRE SEPARATION DISTANCE (FEET)(SECTION 602 IBC 2012)
NORTH SOUTH EAST WEST
ROOF COVERING CLASSIFICATION PROVIDED:(TABLE 1505.1 IBC 2012)
A B C
WATER SUPPLY (FOR FIREFIGHTING)6CHAPTER 5, APPENDIX B & C IFC 2012
__________ GROSS SIZE OF BUILDING IN SQUARE FEET (INCLUDE ALL OVERHANGS UNDER ROOF)
PUBLIC WATER SUPPLY WITH FIRE HYDRANTS(FOR PROPOSED AND EXISTING FIRE HYDRANTS ONLY)NAME OF THE MUNICIPAL UTILITY DISTRICT: ________________________________________________NUMBER OF HYDRANTS WITHIN 400 FT (NON-SPRINKLED) OR 600 FT (SPRINKLED) OF BUILDING: __________,SHOWN ON: __________REQUIRED GPM: __________ DURATION: __________ (TABLE B105.1 IFC 2012)
75% REDUCTION? YES NO (MUST MAINTAIN MINIMUM OF 1,500 GPM)
WATER SOURCE FOR RURAL AREAS WITHOUT FIRE HYDRANTS(COMPLETE THE FIRE FLOW CALCULATOR)
***DRY HYDRANTABOVEGROUND STORAGE
UNDERGROUND STORAGEOTHER: _________________________
DESIGN SPECIFICATIONS AND LOCATIONS SHOULD MEET MINIMUM REQUIRED WATER SUPPLY FROM THEFIRE FLOW CALCULATOR NFPA 1142 (http://hcpid.org/permits/docs/FC_fire_flow_calculator.pdf).
***SUBMIT DRY HYDRANT DESIGN PLANS & CALCULATIONS TO FIRE PROTECTION FOR REVIEW &APPROVAL (http://hcpid.org/permits/docs/FC_dry_hydrant_worksheet.pdf)
FIRE LANE ACCESS7CHAPTER 5 & APPENDIX D IFC 2012
FIRE LANE LAYOUT PLAN, WHICH SHALL INCLUDE THE SITE PLAN, THE FIRE LANE & FIRE HYDRANTS, ISSHOWN ON: __________. (HIGHLIGHT THE FIRE HYDRANT LOCATIONS ON THE PLANS) AERIAL ACCESSLAYOUT, FOR BUILDINGS OVER 30 FT, IS SHOWN ON: __________.
FIRE LANES WILL BE APPROVED CONCEPTUALLY DURING THE CIVIL REVIEW PROCESS. HOWEVER, THEFIRE CODE PLAN REVIEWER MAY CHANGE THE FIRE LANE LAYOUT BASED ON THE BUILDINGSPECIFICATIONS.
PROVIDING A DRY STANDPIPE/WALL HYDRANT OR REMOTE FIRE HOSE CONNECTION TO COMPLY WITHFIRE LANE HOSE COVERAGE. SUBMIT PLANS TO FIRE PROTECTION FOR REVIEW (SECTION 915.1 HCAMENDMENTS)
FIRE LANE LAYOUT, GENERAL REQUIREMENTS & APPROVED SIGN(http://hcpid.org/permits/docs/FC_firelane_layout_gen_req_and_approved_sign.pdf)
INTERIOR FINISH8CHAPTER 8 & TABLE 803.9 IBC 2012
ROOMS AND ENCLOSEDSPACES
EXIT ENCLOSURES ANDEXIT PASSAGEWAYS
OCCUPANCYGROUP SHEET #CORRIDORS
PRODUCTS BEING STORED: ____________________________________________________YES NOSTORAGE PACKAGING (I.E. PALLETS, RACKS, SOLID PILED, DRUMS, CARDBOARD BOXES, WRAPPEDIN PLASTIC, ETC.): ____________________________________________________________________________
YES NO
MAXIMUM HEIGHT OF COMMODITY: ____________________________________________________YES NO***THIS BUILDING IS DESIGNED FOR THE INTENT OF HIGH PILED STORAGE. IF YES, THENPROVIDE HIGH PILED STORAGE FORM (http://hcpid.org/permits/docs/FC_high_piled_storage_form.pdf).
YES NO
FIRE DEPARTMENT ACCESS DOORSYES NOHIGH PILED STORAGE RACK LAYOUT/ELEVATIONS, CODE ANALYSIS, ETC. SHOWN ON: __________NO
HAZARDOUS MATERIALS10CHAPTER 50 IFC 2012
***THIS BUILDING IS DESIGNED FOR THE INTENT OF HAZARDOUS MATERIAL STORAGE. IF YES,THEN PROVIDE ALL HMIS SUMMARY AND MSDS REPORTS.
YES NO
EMERGENCY ALARM SYSTEM REQUIRED PER SECTION 5004.9 IFC 2012YES NO
YES
VENTILATION WITH EMERGENCY ALARM STAND BY POWER PER SECTION 5004.3 AND 5004.7 IFC 2012.NOYESSPILL CONTROL AND SECONDARY CONTAINMENT PER SECTION 5004.2 IFC 2012YES NO
SPECIAL CONDITIONS11PROPERTIES WITH FENCE AND GATES SHALL PROVIDE A 911 KEY BOX AT ENTRY GATE
ATRIUM(S) PER 404 IBC 2012?YES NO PAINT SPRAY BOOTHS, COATINGS,DIPPING OR INDUSTRIAL OVENS USEDPER 2404, 2405, 2406 AND CHAPTER 30 IFC2012?
YES NOYES NO HIGH RISE BLDG PER 403 IBC 2012?YES NO ANY FUEL STORAGE TANKS PER
5704 IFC 2012?YES NO SEPTIC SYSTEM? SUBMIT PLANS
TO WASTEWATER FOR REVIEW.YES NOYES NO
YES NO HEALTH DEPARTMENT APPROVAL?REQUIRED FOR ALL ESTABLISHMENTSTHAT SERVE/PREPARE FOOD ANDBEVERAGES FOR THE PUBLIC OR HAVEREFRIGERATED FOOD STORAGE.
YES NO MEDICAL GAS PER 5306 IFC 2012?YES NO
PUBLIC UTILITIES?
CERTIFICATION
PERMIT OFFICE
REVIEWER'S SIGNATURE BLOCK
THE PROJECT KNOWN AS(MUST BE THE NAME OF BUSINESS/DBA IF BUILDING IS FOR A SPECIFIC COMPANY)
PROJECT NUMBER: IFC 2012
COMMENTS & NOTES
A COPY OF THESE APPROVED CONSTRUCTION PLANS MUST BE KEPT AT PROJECT SITE FORTHE FINAL INSPECTION OF THE BUILDING
(http://www.hcad.org)
(http://hcpid.org/permits/fc_welcome.html)
SHEET NO.(S)DATE DESCRIPTION REVIEWER COUNTY P.E. FIRE CODEREVIEW
SHEET NUMBER
________ OF ________
WAS ACCEPTED BY HARRIS COUNTY FOR THE PURPOSES LISTED BELOW:
REVIEWER'S STAMP
BUILDINGS WITHOUT OPENINGSPER 903.2.11 IFC 2012?FIRE PUMP EMERGENCY STANDBYPOWER PER 913.8 HC AMENDMENTS?
MIXED OCCUPANCY
NOT REQUIRED
NO HVAC UNITS OVER 2,000 CFM
YES NO OTHER: __________________________
X
X
TYPE I I B
2 STORIES 9,500
11
19655 WEST ROAD
CYPRESS 77433
6,486 135'-11" RIDGE
1,800,000
ASSEMBLY BUILDING FOR WORSHIP SERVICES / FELLOWSHIP
WORSHIP / FELLOWSHIP AREA
N.A.
24
G3.00
X
N.A.
4 REQD SHEET E-2
X
A-3 200 ' 58 MAX G3.00
X
NA
X
5A3.00
X
X
X
X
X
218 '+ 131 '+ 216 +'662 +'
X
7,319.13 SF
A-3CLASS B
A2.00/A3.00CLASS B
CLASS C
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ROY P. HARPER A.I.A.
NO
X
1
C.07
C.05
ROY P. HARPER A.I.A. INC.
G-1C-10
X
X
X
X
045-079-000-0128
MUD 172
EABPRJB5821358
CLASSROOMS AND NURSERY WILL BE USED ONLY DURING OR BEFORE RELIGIOUS
CEREMONIES IN THE BUILDING
M-1
X
HERITAGE PRESBYTERIAN CHURCH
1510070007 CFCL5
X
NURSERY AREA 315 35 9
B OFFICE AREA 439 100 4
FOOD WARMING AREA 196 200 1
SUNDAY SCHOOL AREA 620 20 31
NOTE: SUNDAY SCHOOL, OFFICES, FOOD WARMING
AREA WILL NOT BE USED OR OCCUPIED DURING
WORSHIP SERVICES
B 200 ' 44 ' MAX
A-3 (E) 200 ' 39' MAX
G3.00
G3.00
A-3
NO CLASSFICTN
*
*
* RE: SECTS 305.201, 308.6.2
RE: MTL. BLDG. DWGS.
UL425 15/A6.02
UL407 2/A6.02
UL419 11/A6.02
11
00
12
NA
NA
RE: MTL. BLDG. DWGS.
BCLASS B
A2.00/A3.00CLASS B
CLASS C
S-1CLASS C
A2.00/A3.00CLASS C
CLASS C
S-1 STORAGE AREA 185 300 1
S-1 200 ' 35' MAX G3.00
1
UL 10A 2,4/A5.00
1
HCPHES HAS DETERMINED THAT THE FOOD WARMING AREA IS NOT CLASSIFIED AS A
COMMERCIAL KITCHEN. SEE ATTACHED DOCUMENTS FROM HCPHES
A-3
A-3
2044872
1,5002 HRS
X
1-21-16 RESUBMITTAL TO FIRE
REVIEW
2-25-16 RESUBMITTAL TO FIRE
REVIEW
1,030 7 147
3,003 208
STAGE AREA 218 15 15A-3
0 0
0 0
0 0
0 0
0 0
NA
3-8-16 RESUBMITTAL TO FIRE
REVIEW
UL425 12,13,15/A6.02
22
Recommended