EPICS Support for Group3 Control System . Carl Lionberger Group3 ™ optical-fiber-connected I/O Software and operational experience. Group3 control system. VME-Based fiber-optic loop controller 2 loops/VME bd, 8 bds/VME crate SDLC 1.152 Mbaud on loop 16 DI’s (Device Interface) / loop - PowerPoint PPT Presentation

Citation preview

8 May 2001 EPICS Group3 Carl Lionberger 1

EPICS Support for Group3 Control System

Carl Lionberger

Group3™ optical-fiber-connected I/OSoftware and operational experience

8 May 2001 EPICS Group3 Carl Lionberger

2

Group3 control system• VME-Based fiber-optic loop controller

– 2 loops/VME bd, 8 bds/VME crate– SDLC 1.152 Mbaud on loop

• 16 DI’s (Device Interface) / loop– CNA – 2 AI, 1 AO, 8BI, 8BO

• Has PID (not supported)– CN3 – CPU + 3 I/O boards

• digital I/O, analog I/O, motor control• Serial, gpib (not supported)

– Diagnostic Port on each DI

8 May 2001 EPICS Group3 Carl Lionberger

3

Optical Fiber Items

• HP HFBR Versatile Link– 40 meters max/link plastic, 3 km max/link glass

• Plastic easy to terminate in-house• Glass & SMA connectors by special order

– Have had bad experience with passive cable extenders (barrel connectors, feed-throughs)

8 May 2001 EPICS Group3 Carl Lionberger

4

Group3 controls in a rack

8 May 2001 EPICS Group3 Carl Lionberger

5

Group3 EPICS support• CNA combination module

– Ai, ao, bi, bo, mbbi, mbbiD, mbbo, mbboD• B digital module

– bi, bo, mbbi, mbbiD, mbbo, mbboD• C 8 16-bit analog input – ai• D 8 12-bit analog output – ao• E 4-channel DC motor controller

– Mbbo for mode, ao for speed, accel• G 4-channel stepper – steppermotor record• H 4-channel encoder – ai, steppermotor record• F dual-serial, diagnostic port – vxWorks tty driver• Loop Controller (status) – ai, mbbi, mbbiD

8 May 2001 EPICS Group3 Carl Lionberger

6

CNA Module

8 May 2001 EPICS Group3 Carl Lionberger

7

Power Supply Control with CNA

8 May 2001 EPICS Group3 Carl Lionberger

8

Directly connected CNAs

• 2 CNA’s connected directly to each other by two fiber cables

• Output of each one reflects corresponding inputs of other

• Nice for remote power switches and resets• No Software!

8 May 2001 EPICS Group3 Carl Lionberger

9

Cache Polling Loop

~30Hz

DI1

DI2

DI3

Loop Controller

input PV

Output PV

Device Support

drvG3

Sequence-number concurrency control

Per-DI semaphore protected

Interrupt IO Scan Queue

vxWorks tty driver

Group3 EPICS support

8 May 2001 EPICS Group3 Carl Lionberger

10Group3 layout screen

8 May 2001 EPICS Group3 Carl Lionberger

11Loop Controller Diagnostic

8 May 2001 EPICS Group3 Carl Lionberger

12

Group3 Diagnostic Port

8 May 2001 EPICS Group3 Carl Lionberger

13

Dbior report level 3Scanner has run 13221688 times.

Loop Controller 12 in use at 0xffffc000 with status 0x0

Extended error: 0x1 error count: 3477 DI online bits: 0x7f

IO Buffer memory 34 percent used; 14 of 60 iodefs used.

Receive count 288247461 and Send count 292452437

Error vector 0x1000000 DI vector 0x0 IO vector 0x0 SDLC 0x84

Error vector bits:

Bad SDLC Packet

Active nodes:

IODef 0 DI 0 Board 0 Type 6 IO Address 0xcf80 updates/sec 0 OK

vxWorks tty name: LEBT:Extr receive index 0

IODef 8 DI 3 Board 1 Type 101 IO Address 0xcc48 updates/sec 1 OK

Ints/sec: 1 0 0

IODef 9 DI 6 Board 1 Type 3 IO Address 0xcc24 updates/sec 28 OK

Ints/sec: 0 0 0 0 0 0 0 0

8 May 2001 EPICS Group3 Carl Lionberger

14

Dbior report level 4IODef 3 DI 3 Board 0 Type 6 IO Address 0xce00 updates/sec 0 OK

vxWorks tty name: LEBT:Chop_P receive index 0

r mses r tries data buffer

136003 0 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00

00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00

00 75 66 66 65 72 20 6f 76 65 72 66 6c 6f 77 0d

0a 20 6f 76 65 72 66 6c 6f 77 0d 0a 20 20

IODef at 0xffffc070 DI 0x3 Bd 0x0 Type 0x6 offset 0xe00

IODef 9 DI 6 Board 1 Type 3 IO Address 0xcc24 updates/sec 20 OK

Ints/sec: 0 0 0 0 0 0 0 0

r mses r tries data buffer

265969 0 01 00 03 00 02 00 02 00 02 00 01 00 03 00 03 00

IODef at 0xffffc0d0 DI 0x6 Bd 0x1 Type 0x3 offset 0xc24

IODef 10 DI 0 Board 1 Type 101 IO Address 0xcbdc updates/sec 7 OK

Ints/sec: 5 2 0

8 May 2001 EPICS Group3 Carl Lionberger

15

Sparks Can Still Get In• Power (24V AC/DC)

– Isolation transformer types– Routing of 110 V

• Signals– RC networks in CN3, CNA connector blocks– Grounding and shielding

• VME crates – Overall grounding and power quality

8 May 2001 EPICS Group3 Carl Lionberger

16

General Problems• No readback of outputs through normal channels.

– Could startup with diagnostic ports only to obtain initial readback value for glitchless performance.

• Rewrite driver

• CN3 board addressing flaw– Don’t use multiple boards of same type in same CN3!– Firmware fix in the works?

• Addresses not reconfigurable on the fly• Diagnostic port-level automatic configuration

support inadequate

8 May 2001 EPICS Group3 Carl Lionberger

17

Conclusions

• Easy to set up and use• Runs reliably under reasonable conditions• Optical fiber communication link does not

solve all electrical isolation problems• There are still some possible driver level

issues

Recommended