ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
On – site Dissolved Gas Analysis according to
IEC60567 / ASTM D 3612
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Which tests can you do on transformer oil at – site?
Breakdown voltage tests Tan Delta and resistivity tests Water content measurement acc. to Karl-Fischer Total gas content measurement Dissolved Gas analysis
The total of all parameters allows a diagnostic about the condition
of the transformer
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
What is Dissolved Gas Analysis?
A quantitative analysis of all dissolved gases in the
transformer oil. The analysis is done after the extraction of
the gases and a gas chromatography thereafter.
The aim of the analysis is an early determination of aging
and functional problems of the transformer.
모든정량분석은 변압기 오일을 용해하는것입니다 . 이 분석은
가스의 추출과 가스 chromatography thereafter 를 한후에 이루어 집니다 . 이 분석의 목표는 변압기의 노화와 기능적결함을 초기에 진단하는 것입니다 .
PREDICTIVE MAINTENANCE !
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Which gases need to be detected ?accord. to ASTM 3612 / IEC 567
ASTM 3612 IEC 567
Oxygen O2, Nitrogen N2 Oxygen O2, Nitrogen N2
Hydrogen H2 Hydrogen H2
Carbon Monoxid CO, Carbon Dioxid CO2 Carbon Monoxid CO, Carbon Dioxid
CO2
Methan CH4 Methan CH4
Ethan C2H6 Ethan C2H6
Ethylen C2H4 Ethylen C2H4
Acetylen C2H2 Acetylen C2H2
Propan C3H8 (Propan C3H8, Propylen C3H6
Propylen C3H6
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Which gases are detected ?
Oxygen O2, Nitrogen N2
Hydrogen H2
Carbon Monoxid CO, Carbon Dioxid CO2
Methan CH4
Ethan C2H6
Ethylen C2H4
Acetylen C2H2
Propan C3H8
Propylen C3H6
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
The Use of Atmospheric Gases
N2 and O2 are indispensable for the evaluation of the transfomer condition
N2: Referenzvalue for the gas saturation.
O2: Very important indicator for the ageing process
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
60.000
400 1600
15.000
N 2
H 2
Gas saturation level > 50.000 < 70.000ppm
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
The Use of Secondary Gases (Propan and Propen)
The ‘Memory‘ of Thermic Faults
Due to the slow solubility of C3H6 and C3H8 both gases serve as a memory of Thermic faults.
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Reasons for high gas content and interpretation of the values with ratios
Electrical Discharge Acetylen C2H2 3Ethan C2H6
Partial Discharge Hydrogen H2 10Methan CH4
Overheating of Oil Ethylen C2H4 1 for temperatures below 300 o CPropylen C3H6 1 for temperatures over 300 o C
Overheating of cellulosis Carbondioxid CO2 10Carbonmonoxid CO
Degradation of cellulosis caused by electr. Faults Carbondioxid CO2 3Carbonmonoxid CO
Leakage, contamination of the oil with ambient air Oxygen O2Nitrogen N2
Leacking tap changer vessel Acetylen C2H2 2Hydrogen H2
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
An Example of Premature Ageing
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Advantages of on-site analysis
Minimizing problems of oil sampling
Time reduction ( sample dispatch, waiting for
results )
Direct Buchholzgas analysis
Short reaction times
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Steps of the Dissolved Gas Analysis
Degassing
Gas chromatography
Interpretation of the values with integrated
expert - system
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Degassing of oil sample
1. Preparation 2. Oilsample 3. Degassing 4. Gas transfer
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Partial Vacuum degassing acc. to IEC EN 60567
Advantages:
Easy extraction at-site
Simple to handle
Very high sensibility
High accuracy
Comparable with laboratory degassing
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Principle of a gas chromatographic analysis
Gas supply
Flow-
Controller
Injection
system
Detector
Column with oven
Electronic amplifier
Computer
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Automatic sample Loop
Sample Loop with fixed dosing: 100 µl
Carrier gas Carrier gasPosition „Load“
Position „Inject“
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Schematic of the Gaschromatograph
exte rn algas-supp ly
A r
connec to rs w ith f ilter h igh pressu re gas cy linde rs
H2
m as ter sw itch (open /c lose d)
H 2
m anom e te r A r
p ressu re re duce r
pum p
H2
A r
tcdfiltera ir
in jectorfid
sepa ra tion co lum n
h igh pressu re gas sup p ly
reference channel
sample channel
A r
H 2
p ressu re sw itch
e lectron icp ressu recontro ller
f. e.: C arboxen 1010 Plot0.32 m m i. d., 30 m length
e lectron icm ass flowcontro ller
21
34
6
5
sa m p lelo o p
2 0 0 µ l
6 -p o r t-va lv e
outle t
“Load”
e lectron icm ass flowcontro ller
Restrictor
Test point
Bypass
Valve
non -retu rn va lve s
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Typical Chromatograms
TCD-Channel FID-Channel
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
MobilGC - Software
Clearly structured with
helpful tools for
monitoring and
evaluation
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
MobilGC - Evaluation
Simple operation with clear structures
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
MobilGC – Expert- System
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
DUVAL TRIANGLE
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Advantages of the MobilGC
portable Gaschromatograph
Internal gas supply
Immediate analysis
Direct analysis of Buchholzgases
Online Monitoring of transformers through combination of autm. Vacuum degassing and MobilGC
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Analyse und Probenvorbereitung entsprechen dem KYOTO – Protokoll
Flamme wird mit Wasserstoff betrieben
Es erfolgt keine Emission von CO2 in die Umgebungsluft
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Automatic Vacuum Degassing without Mercury
Entgasungs-gefäß
M V 1
M V 2
M V 3
Pum pe
Septum p
Öl
Gas
Patent Nr. DE 10252652
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Automatic Vacuum Degassing without Mercury
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Comparison Measurements
Component Toepler-Pump Vacuum Degassing
Lab GC Mobil GC Lab GC Mobil GC
H2 234 235 225 239
CO 230 231 220 225
CO2 1320 1297 1243 1341
Methan 25 25 23 25
Ethan 162 165 115 149
Ethylen 10,1 10,0 7,4 10,9
Acetylen 0,8 1,0 0,4 0,76
Features and Benefits:
■ Fully automatic procedure
■ One touch operation
■ Multi-periodic vacuum
degassing
■ Fast and reliable
■ Full TOGA analysis ( 11
gases )
■ Automatic transfer of gas
sample
■ Compl. to ASTM3612 / IEC
567
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
TOP-TOGA- GC
Automatic Vacuumdegassing
without Mercury
Short degassing time ( < 3 min.)
Automatic Transfer of the gases to
the GC
Additional analog ports for further
parameters
Plausibility test and trendanalysis
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Online-Monitoring with Automatic Vacuumdegassing and MobilGC
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Further products for transformer testing
Karl Fischer Pocket Titrator
Tan delta and Resistivity Measurement
Total Gas Content Measurement
Capacitance test on transfomers
Petrochemical and Environmental Applications
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Pocket Titrator
Low background drift measuring cell
Preconfigured methods
“One click” measurement
AEC (automatically electrolysis controlled)
High precision even in low concentrations
Suitable for all commonly used Karl-Fischer-
reagents
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Tan Delta and Resistivity Measurement
Fully automatic testing sequence
Optional manual testing sequence
Automatic calibration and resistance measurement
Windows software
Menu driven software operations
ENERGY SUPPORT
Experts in providing mobile Solutions
Energy Support GmbH . Sperberweg 47 . D - 41468 Neuss T +49 2131 4039607 . F +49 2131 4039608 . info@energy-support.de
Total Gas Content Measurement
Gas separation by means of fully vacuum degassing ( accord. to DIN EN 60567, DIN IEC 599 and IEEE C57.104-1991) and display of results
Subsequently to the determination of the total gas content a gas chromatographic analysis can be made.