ENERBATT 3G
The Enerbatt 3G Battery MonitoringSystem is a complete solut ion forcaptur ing important parameters ofbatteries at real time. The BMS is able,communicate wirelessly, measure up to512 nodes per system and record data inexternal memory cards to enable easydata access and backup securi ty.
Battery Cell Short or Open
Battery Cell Reversal
Battery Cell Impedance
- determine impedance value of
the internal battery cell
Communication & protocol
- R.F 2.4G for wireless connection
- wired communication via
Ethernet TCP/IP, RS 485
The new BMS is able to detect various battery problems to ensurethe batteries are in working conditions.
Short point
Battery voltagedecrease
Open point
Battery voltageincrease
4V dropped
1 cell voltage reverse
The Data collector comes with a large 6.4” LCD Screen with GraphicTouch function offering access and viewing of various batteriesparameters.
Functions of the Data Collector:Real-time Monitoring Information and Battery Test
- Battery Voltage, Battery Impedance, String Voltage, StringCurrent and Environment Temperature
Charts & Curves- Curve, Bar graph, AverageEvents Log
- Alarms via email & dry contactSensor Network Manage
- Battery Configuration settings- Networks Parameters settings
ENERBATT 3G
Impedance curve
Temperature curve
Voltage curve
History curve
Battery voltage
Event logs
Batteries readings
ENERBATT 3GTechnical Specification
18 Watts, maximumPower Consumption
RF 2.4G for wirelessRadio Frequency
Ethernet TCP/IP, RS 485,
Input / Output Dry contact signal
Available Communication Port
100 ~ 240Vac, 35 ~ 60VdcSupply Voltage
440 × 262 × 75Enclosure Dimension (W × H × D) mm
95% without condensingRelative Humidity
0°C~40°COperating Temperature
GENERAL
1M
10mV
1mV
1.5~4V
2V
BATTERY BLOCK VOLTAGE MEASUREMENT
Input Impedance
Accuracy
Resolution
9~16V4.5~8VBlock Voltage Measuring Range
12V6VBlock Rated Voltage
1MInput Impedance
0.3VAccuracy
0.1VResolution
620VMaximum Measurement Voltage
BATTERY STRING VOLTAGE MEASUREMENT
Designed and Engineered by
0.3%Accuracy
0.1AResolution
3,000AMaximum Measurement Voltage
BATTERY STRING CURRENT MEASUREMENT
Recommended