8/18/2019 Electrical Skills Lab Manual
1/112
Shinas ollege of Technology
Engineering Department
E E l l e e c c t t r r i i c c a a l l s s k k i i l l
l l s s
L A B O R A T O R Y M A N U A L
Course Code: EEPW2241 AY 2015-2016 Semester: 2 ID No.: Name of the Student:
Section No. Level: Specialization:
8/18/2019 Electrical Skills Lab Manual
2/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
3/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
CONTENTS
Experiment
No.Name of the Experiment
Page
No.
Table of contents
Course objectives, outcomes
Course assessment scheme
Laboratory rules
General safety precautions and guidelines
in the ELECTRICAL SKILLS lab
Introduction
1 Electrical Supply
2 Measurement of the Earth Resistance
3 Preparation of Galvanized Steel Conduit
4 Wiring Lighting Circuit
5 Testing Wiring Circuits
6 Connection of Fluorescent Tube Light
7 Sodium Vapor Lamps
8Connection and Trouble Shooting of Fan
Circuit
9 Metal Halide Lamps
8/18/2019 Electrical Skills Lab Manual
4/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
COURSE OUTCOMES:
EEPW2241: ELECTRICAL SKILLS
Prerequisites: Engineering Workshop (EEPW 1240)
Goal: To provide the students with the concepts, techniques and applications of
electrical workshop
Objectives Outcomes
This course should enable the
student to:
1. Know the safety practices in
the workshop and production
areas.2. Understand the aspects of
electrical installation
techniques.
3. Understand how to assemble
steel conduit.
4. Understand how to wire
lighting and circuits.
5. Understand the concepts ofconstruction of DC and single-
phase AC motors.
6. Know different methods of
protections.
7. Understand how to control
circuits of single phase AC
motors.
Upon completion of the course, the student will be
able to:
1. Familiarize and apply the electricity safety
rules in Oman and in IEE regulation.
2. Describe the power distribution systems,Earthing arrangement, electrical bonding,
PME supplies and current protective
conductors.
3. Prepare for assembling steel conduit.
4. Wire lighting and power circuits.
5. Assemble and connect fluorescent and sodium
vapour lamps.
6. Test the wiring circuits like visual inspectiontest, continuity test and insulation resistance
test.
7. Define the fault diagnosis techniques in
electrical insulations.
8. Describe the construction of DC and single
phase AC motor.
9. Construct bell indictor circuits.
10. Apply different methods of circuit’sprotection.
11. Control the circuits of single-phase AC motors.
8/18/2019 Electrical Skills Lab Manual
5/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Sources:
I. Text Books
1. “Electrical Installation work, Brain McAdam, Elsevier 4Th Edition.
2. Electrical skills, Ministry Manual.
II. Reference Books
3. “Electrical Engineering, “Allen R Pearson Prentice Hall.
4. “Basic Electrical Installation Work’’, Trevor Linsley, Newness(ACT)
5. “Electrical Installation”, Thompson FG, Longman (NCT), 4Th Edition. 6. “Electrical Technology”, BL Theraja & AK Theraja S Chand Publications.
7. “Residential Construction Academy”, Stephen Herman, Thompson Publisher.
8. “Electrical Instant Answer” Garg Tuck, MC Graw Hill Publications.
III. Web sites
http://www.ehcoman.com
http://www.majanco.co.om
8/18/2019 Electrical Skills Lab Manual
6/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
COURSE ASSESSMENT METHODS
Assessment Scheme (Total Practical Courses)
Course Grading Scheme
Course Passing Grade : 67-69 (C grade)*
* Depends on the course
Marks Grade GPA
90-100 A 4.0
85-89 A- 3.7
80-84 B+ 3.3
76-79 B 3.073-75 B- 2.7
70-72 C+ 2.3
67-69 C 2.0
60-66 C- 1.7
55-59 D 1.0
Below 55 F 0.0
Graduation Grading Scheme
Below grade is displayed in the graduation certificate and it is based on the Overall CGPA ofall levels.
Descriptive GradeGradeOverall CGPA
Excellent A 4
A- 3.7-3.99
Very Good B+ 3.3-3.3.69
B 2.-23
Good B- .-.2
C+ .2-.2
Satisfactory C .2.-.23
Fail
C-
92-92
D 92-923
F 0.0-.99
8/18/2019 Electrical Skills Lab Manual
7/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Assessment Methods
(Total Practical Courses)
Theory (T) Practical (P)
Not Applicable
Lab report 45 marks
Viva-Voce 15 marks
Written Questionnaire 40
marks
100 % Practical part marks= Total marks out of 100
Assessment scheme for the Lab work
Part I: Lab report with data collection and analysis–
45 Marks
Part II: One Viva-voce – 15 marks
Part III- Written questionnaire – 40 Marks
In this part the student is subject to frequent written questionnaire about the performed
experiments. It may include experimental data collection. A minimum of three written
assessments are to be conducted (i.e. n > 3, where n= no. of practical assessments
conducted). Best of (n-1) performances to be considered for final marks. All written
assessments are announced.
8/18/2019 Electrical Skills Lab Manual
8/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Attendance:
Issuing of Warning Letter Percentage Number of Hours
First 10%
Second 20%
Third 30%
If the absence reaches 30%, the student will be debarred from the final exam and will
get ZERO in the final exam.
A student will be considered as LATE when s/he arrives after 10minutes of the class
start time. Being LATE for THREE times in a class will be considered as ONE class
absence.
The full course delivery plan must be covered. If students are absent without a valid
reason, it will be considered as if the topic/s is already covered and will be included
in exams.
If a student is absent for two continuous weeks within the semester in all courses,
s/he will be DISMISSED from the College.
Absence Excuse:
If a student failed to attend any class, s/he has to submit the original excuse
document within one week from the date of absence to registration department
only.
If a student failed to attend midterm or final exam, s/he has to fill in aSupplementary Exam Form attached with the original excuse stamped from
concern authorities and submit it to the registration department within one week
from the exam date. Hospital/Clinic Attendance Certificate is not accepted as a
valid excuse.
The coverage of topics in the midterm supplementary exam will include topics
covered up to the midterm exam + topics covered one week after the midterm
exam.
The final complementary exam will be conducted within four weeks from thestart of next semester.
8/18/2019 Electrical Skills Lab Manual
9/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Course Withdrawal
A student is allowed to withdraw one course during the semester. The withdrawal
period will end a week after the midterm exam resultannouncement.
Submission of Assignment
20% of assignment scored mark will be reduced for each day of late submission.
Cheating
In case of an accusation of cheating during an examination is proven, the following will
be imposed:
Disciplinary Action for Cheating Case/s:
First Offense (Zero Mark)
Second Offense (Study Suspension for one semester)
Third Offense (Dismissal from the College)
8/18/2019 Electrical Skills Lab Manual
10/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Theory (T) Practical (P)
Not Applicable
Lab report 45 Marks
Viva-Voce 15 Marks
Written Questionnaire 40 Marks100 % Practical part marks= Total marks out of 100
Part I- Lab report with data collection and analysis – 45 marks
No. Factors Marks
1 Ability to follow procedure, data collection 10
2Data analysis, interpretation of results & conclusions related to
the objectives and course outcomes10
3
Completeness, accuracy and
correctness of data and results (Figures, graphs, tables, units,
software)
20
4 Submission on time 05
Total 45 marks
Part II: One Viva-voce – 15 marks
Part II- Written questionnaire – 40 marks
In this part the student is subject to frequent written questionnaire about the performed
experiments. It may include experimental data collection. A minimum of three written
assessments are to be conducted (i.e. n > 3, where n= no. of practical assessments
conducted). Best of (n-1) performances to be considered for final marks. All writtenassessments are announced.
Total weightage for all the above procedures (Part I + Part II+ Part III) is 100%
8/18/2019 Electrical Skills Lab Manual
11/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
WRITING LAB REPORT
1. Each Student has to write a Lab report on each Experiment / Exercise performed &
submit the report within one week.
2. But if the student fails to submit the report within one week, he/she will loose 1
mark each day till the report is submitted.
3.
After the completion of each experiment student must take the signature of course
Lecturer on the cover page.
4.
Attach the cover page to each Lab report before submission.
5.
The report must be written on plane A4 sheets & preferably on both sides of the
paper
6.
Neat report with all the required data, graph, units and conclusion will get better
marks.
8/18/2019 Electrical Skills Lab Manual
12/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Dos and Don’ts:
Dos:
1. Before starting Laboratory work follow all written and verbal instructions
carefully. If you do not understand a direction or part of a procedure, ASK YOURCONCERN TEACHER BEFORE PROCEEDING WITH THE ACTIVITY
2. Do your wiring, setup, and a careful circuit checkout before applying power.
3. Conduct yourself in a responsible manner at all times in the laboratory. Don’t talk
aloud or crack jokes in lab.
4. Appropriate Personal Protective Equipment should be worn during laboratory
experiments.
5. Do not eat food, drink beverages or chew gum in the laboratory and do not use
laboratory glassware as containers for food or beverages. Smoking is strictlyprohibited in lab area
Don’ts
1. Avoid contact with energized electrical circuits.
2. Do not make circuit changes or perform any wiring when power is on.
3. Do not wear loose-fitting clothing or jewelry in the lab. Rings and necklaces areusual excellent conductors in contact with your skin.
4. Do not touch anything if your hands are wet. The "one-hand" approach is safest.
5. Do not wander around the room, distract other students, startle other students or
interfere with the laboratory experiments of others
8/18/2019 Electrical Skills Lab Manual
13/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Electrical Accidents/ Hazards are attributed to:
Shock/ Electrocution
Arcing
Fire
Explosion
Which result in:
Loss of Life
Loss of Property
Safety First SAFETY CLOTHING MUST BE WORN SAFETY SHOES MUST BE
WORN
Boys Girls
8/18/2019 Electrical Skills Lab Manual
14/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Introduction
Electricity and related water sector in Sultanate of Oman
The Law for The Regulation and Privatization of the Electricity andRelated Water Sector (the Sector Law) was promulgated by Royal Decree
# 78/2004 and came into effect on 1 August 2004.
Reference : http://www.ehcoman.com
http://www.ehcoman.com/http://www.ehcoman.com/http://www.ehcoman.com/http://www.ehcoman.com/
8/18/2019 Electrical Skills Lab Manual
15/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Electricity Distribution in Oman: Geographical Coverage
Reference : http://www.ehcoman.com
Majan Electricity Company: Profile
Majan through its systems, processes and people offers sustainable
management of electricity with the purpose of serving the people of Omanby delivering safe, reliable and economical electricity. *
Reference : http://www.majanco.co.om
http://www.ehcoman.com/http://www.ehcoman.com/http://www.ehcoman.com/http://www.majanco.co.om/http://www.majanco.co.om/http://www.majanco.co.om/http://www.majanco.co.om/http://www.ehcoman.com/
8/18/2019 Electrical Skills Lab Manual
16/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Regulation Describe about
OES 1 33KV & 11KV Overhead Lines
OES 2 Underground Cables
OES 3 LT Overhead Lines
OES 4 Electrical Installations in Buildings
General Derogation OES 4 clause 6.5 Use of PVC Conduits
OES 5, 5A & 6 Transformers
OES 7, 21, 22, 23, 28 & 31 LT Equipment
OES 8,9,10,16,17,18,20,25, 26, 29 &
33Overhead Line Material & Equipment
OES 11General Specifications Electrical Equipment &
Materials
OES 21A, 12B, 13, 14, 15, 19, 34 & 35 Switchgear & Associated Equipment
OES 24 3311KV Indoor Substations
OES 27 Volume 1 132 33KV Substations
OES 27 Volume 2 132 33KV Substations
OES 30 33 11KV Outdoor Substation
OES 32 132KV OHL
http://www.aer-oman.org/pdf/o2.pdfhttp://www.aer-oman.org/pdf/o3.pdfhttp://www.aer-oman.org/pdf/o4.pdfhttp://www.aer-oman.org/pdf/o4.pdfhttp://www.aer-oman.org/pdf/o5.pdfhttp://www.aer-oman.org/pdf/o5.pdfhttp://www.aer-oman.org/pdf/o4.pdfhttp://www.aer-oman.org/pdf/o3.pdfhttp://www.aer-oman.org/pdf/o2.pdf
8/18/2019 Electrical Skills Lab Manual
17/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
STANDARD OES 4
Ministry of Electricity and Water (now MHEW), Sultanate of Oman has
issued REGULATIONS FOR ELECTRICAL INSTALLATIONS known as
STANDARD OES 4 which is available at
http://www.aer-oman.org
BS 7671:2008
• This British Standard specifies the “Requirements for Electrical
Installations”
• It is also known as IEE Wiring Regulations
• The regulations apply to the design, erection, and verification of
electrical installations.
• These regulations are updated and applicable in the region.
8/18/2019 Electrical Skills Lab Manual
18/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
STANDARD OES 4
Scope and Coverage
(Where to use the standard?)
The regulations apply to electrical installations such as those of,
– Residential Premises
– Commercial Premises
– Public Premises
– Industrial Premises
– Agricultural and Horticultural Premises
– Prefabricated Buildings
– Construction Sites, Exhibitions, Fairs and other temporary installations.
The regulations cover,
– Circuits supplied at normal voltages up to and including 415/240 V AC 50
Hz.
– Any wiring not specifically covered by the specifications of appliances.
– Fixed wiring for telecommunications, signaling, control (excluding external
wiring of apparatus).
Reference: STANDARD OES 4, SECOND EDITION, MAY 1989
8/18/2019 Electrical Skills Lab Manual
19/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
ELECTRICAL STANDARD
Compliance with Regulations
(Why to use/meet the standard?)
Compliance with electrical regulations is essential to ensure safety of life,
plant, equipment and buildings especially from the hazards of fire, electrical
shocks and mishaps in the utilization of electricity in and around buildings.
PROTECTION AGAINST ELECTRIC SHOCK
In electrical installations, one of the major risks is electric shock. Persons and
livestock (animals) shall be protected against dangers that may arise,
a. from contact with live parts of the installation by:
– appropriate measures to prevent contact; ISOLATION
– Limiting the value and duration of current which can pass through a body to
a value lower than shock current. INSULATION
b. From contact with exposed metal parts by one of the following methods.
– Preventing a fault current from passing through the body of any person or
any livestock. EARTHING
– Limiting the value and duration of current which can pass through a body to
a value lower than shock current. INSULATION
– Automatic disconnection of the supply on the occurrence of a fault likely tocause a current to flow through a body in contact with the exposed metal
parts, where the value of the current is equal to or greater than the shock
current . ISOLATION
PROTECTION AGAINST THERMAL EFFECTS
Another major risk with the electrical installations is excessive temperature
likely to cause burns, fires and other injurious effects.
Protection shall be provided against
– The harmful effects of heat or thermal radiation developed by electricalequipment.
– Ignition, combustion or degradation or material.
Reference: BS7671-2008
– flame and smoke where a fire hazard could be propagated from an electrical
installation to other nearby fire compartments and
8/18/2019 Electrical Skills Lab Manual
20/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
– Safety services being cutoff by the failure of electrical equipment.
PROTECTION AGAINST OVERCURRENT
Persons or livestock shall be protected against injury and property shall be
protected against damage due to excessive temperatures or electro-mechanical
stresses caused by over currents likely to arise in live conductors by,
– Automatic disconnection on the occurrence of over-current before the over-
current attains a dangerous value taking into account its duration.
– Limiting the maximum over-current to a safe value and duration.
Conductors other than live conductors and any other parts intended to carry a
fault-current shall be capable of carrying that current without assuming excessive
temperature.
PROTECTION AGAINST VOLTAGE DISTURBANCES AND ELECTROMAGNETIC
DISTURBANCES
Shall cover,
– Protection of low voltage installations against temporary over-voltages due
to earth fault in high voltage systems and due to faults in the low voltage
systems.
– Protection against over-voltages of atmospheric origin or due to switching.
– Measures against electromagnetic influences.
– Protection against under voltages
Reference: BS7671-2008
8/18/2019 Electrical Skills Lab Manual
21/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Compliance with OES4 is achieved through following steps:
(How to meet the Standard?)
1. Submission of Drawings: Schematic and wiring diagrams, layout drawings and
schedule of points with site layout should be submitted to the Ministry beforecommencement of any electrical work whatsoever large or small, new or
additions, and work shall start only after due approval of the Ministry. All work
should be carried out in accordance with the approved drawings.
2. Inspection: All installation work will be subject to inspection and testing by the
ministry and will be connected to the power supply only after the work is
checked and approved by the ministry.
3. Electrical Supervision: All electrical installation works shall be carried out by or
under the direct supervision of a qualified electrical engineer or a supervisor
holding a competency license issued by the Ministry. Such competency licensewill be issued after necessary tests and interview by the Ministry.
4. Standards, Materials and Workmanship: The works shall be carried out in a
neat and workmanlike manner to meet the requirements of these regulations. All
materials used shall be the best of their respective kinds and shall comply with
the latest relevant recommendations of the International Electro-technical
Commission (IEC) if available and if no IEC recommendation is available with the
latest relevant British Standard Specification (BSS)
Reference: STANDARD OES 4, SECOND EDITION, MAY 1989
8/18/2019 Electrical Skills Lab Manual
22/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
23/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Exercise 1: Electrical Supply
Aim: To understand different types of supply systems and trace the electrical supply
system in Shinas College of Technology
(After discussion of the topic in class the students will be taken around the campus
of the institute to trace the electrical supply system)Electrical Power System in Oman:
8/18/2019 Electrical Skills Lab Manual
24/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Electrical supply at the consumers (domestic/ commercial/ industrial) is drawn from
distribution substations. Depending on the applications and KVA the supply voltage is
11kV or 400 V. The distribution substations are equipped with necessary means for
isolation and protection.
Bulk consumers of electricity such as Shinas College of Technology receive electrical
supply at 11kV from distribution substation.
In the consumer premises, the consumer has another substation to step down this
voltage to 400V to meet lighting and low voltage applications.
8/18/2019 Electrical Skills Lab Manual
25/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
26/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
S c h e m a t i c d i a g r a m o
f s u c h a
s y s t e m i
s d i s p l a y e d i n t
h e f o l l o w i n g d i a g r a m :
8/18/2019 Electrical Skills Lab Manual
27/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Exercise 1: Electrical Supply Systems:
Reference:
Chapter 7, Advanced Electrical Installation Work, Fifth Edition,
Publication: Newens
Author: Trevour Linsley
As per the Electricity Regulations applicable in the region to ensure safety, electrical
installations must be equipped with
1. Basic protection and2. Fault protection
This protection is provided using principle of “Protective equi-potential bonding
coupled with automatic disconnection of supply”. In this method all exposed metal
work is electrically connected together to an effective earth connection.
This expose metalwork includes,
Electrical conduits
Trunking
Metal switches
Metalwork of electrical appliances
Water service pipes
Gas and other service pipes and ducting
Central heating and air conditioning systems
Exposed metallic structural parts of the building
Lightening protective systems
8/18/2019 Electrical Skills Lab Manual
28/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
There are three commonly used arrangements of the earthing connection as described
in IEE Electricity Regulations which are discussed here.
TN-S System
TN-C-S System TT System
These have been designated in the IEE Regulations using the letters: T, N, C
and S. These letters stand for:
T - terre (French for earth) and meaning a direct connection to earth.
N - neutral
C - combined
S - separate.
When these letters are grouped, they form the classification of a type of system.The first letter denotes how the supply source is earthed.
The second denotes how the metalwork of an installation is earthed.
The third and fourth indicate the functions of neutral and protective conductors.
8/18/2019 Electrical Skills Lab Manual
29/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
TN-S System (Cable Sheath Earth Supply)
Used where the electricity company’s supply is provided by undergroundcables.
Neutral and protective conductors CP (also called as protective earth PE) are
separate throughout the system.
The protective earth conductor (PE) is the metal sheath and armour of theunderground cable and this is connected to the consumer’s main earthing
terminal.
All exposed metalwork is connected to the protective conductor via the main
earthing terminal of the installation.
8/18/2019 Electrical Skills Lab Manual
30/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
31/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
This system has the neutral of power supply with connection of earth only atone point to the source. The consumer’s earthing terminal is usually connected
to the metallic Armour of the distributor’s cable into the HV / LV transformer.
It is commonly used for underground power supply to the premise or factory
from the distributor substation to customer substation. This earth terminal is
connected by the supply protective conductor (PE) back to the star point
(neutral) of the secondary winding of the supply transformer, which is also
connected at that point to an earth electrode.
http://www.electricneutron.com/tag/cable/http://www.electricneutron.com/tag/cable/http://www.electricneutron.com/tag/cable/
8/18/2019 Electrical Skills Lab Manual
32/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
TN-C-S System (Protective Multiple Earthing Supply)
8/18/2019 Electrical Skills Lab Manual
33/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
34/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
The supply cable uses a combined protective earth & neutral (PEN) conductor.
At the supply intake point a consumer’s main earthing terminal is formed byconnecting the earthing terminal to the neutral conductor.
All exposed conductive parts of the installation are then connected to the mainearthing terminals. Thus phase to earth faults are effectively converted into
phase to neutral faults
8/18/2019 Electrical Skills Lab Manual
35/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
TT System (No Earth Provided Supply)
installations protective conductor must be connected to earth via an earth electrode
provided by the consumer. The TT method is used mostly in country areas with
overhead transmission lines.
In contrast to the TN-S system there is no metallic path from the consumer's terminals
back to the sub-station transformer secondary windings. Because the earth path may beof high resistance, a residual current circuit-breaker (R.C.C.B.) is often fitted so that if a
fault current flows in the earth path then a trip disconnects the phase supply.
For protection against indirect contact in domestic premises, every socket outlet
requires an RCCB with a maximum rated current of 30mA.
8/18/2019 Electrical Skills Lab Manual
36/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
37/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
38/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Residual Current Protection
RCDs are designed to disconnect the circuit if there is a leakage current. By detecting
small leakage currents (typically 5–30 mA) and disconnecting quickly enough (
8/18/2019 Electrical Skills Lab Manual
39/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Advantages
1. They are less sensitive to fault conditions.2. While voltage and current on the earth line is usually fault current from a live wire,
this is not always the case, thus there are situations in which an ELCB can nuisance
trip.
3. When an installation has two connections to earth, a nearby high current lightningstrike will cause a voltage gradient in the soil, presenting the ELCB sense coil with
enough voltage to cause it to trip.
4. If the installation’s earth rod is placed close to the earth rod of a neighboringbuilding, a high earth leakage current in the other building can raise the local
ground potential and cause a voltage difference across the two earths, again
tripping the ELCB.
5. If there is an accumulated or burden of currents caused by items with loweredinsulation resistance due to older equipment, or with heating elements, or rain
conditions can cause the insulation resistance to lower due to moisture tracking. If
there is a some mA who is equal to ELCB rating than ELCB may give nuisance
Tripping.
6. If either of the earth wires become disconnected from the ELCB, it will no longer tripor the installation will often no longer be properly earthed.
7. Some ELCBs do not respond to rectified fault current. This issue is common forELCBs and RCDs, but ELCBs are on average much older than RCB so an old ELCB is
more likely to have some uncommon fault current waveform that it will not
respond to.8. Voltage-operated ELCB are the requirement for a second connection, and thepossibility that any additional connection to earth on the protected system can
disable the detector.
9. Nuisance tripping especially during thunderstorms.
8/18/2019 Electrical Skills Lab Manual
40/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Disadvantages
1. They do not detect faults that don’t pass current through the CPC to the earth rod. 2. They do not allow a single building system to be easily split into multiple sections
with independent fault protection, because earthing systems are usually use
common earth Rod.3. They may be tripped by external voltages from something connected to the
earthing system such as metal pipes, a TN-S earth or a TN-C-S combined neutral
and earth.
4. As electrically leaky appliances such as some water heaters, washing machinesand cookers may cause the ELCB to trip.
5. ELCBs introduce additional resistance and an additional point of failure into theearthing system.
Answer following questions:
1) Why and where protection is required in the Electrical Installations?
2) Where we can use the earthing systems?
a) TN – S System
b) TN – C – S System
c) TT System
3) What is RCD? How does it work?
4) What is the supply voltage obtained from the electricity board to Shinas college of
Technology?
5) What is the kVA rating of the distribution substation in the college premises?
6) What is the type of transformer in the substation?
7) How much voltage is required at the consumer’s premises for Lighting and low
voltage applications?
8/18/2019 Electrical Skills Lab Manual
41/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Exercise 2: Measurement of the Earth Resistance
STANDARD, OES4
Section 4.2.9
CONSUMER EARTING SYSTEM
An independent, separate earthing system shall be installed and maintained by
the consumer. This shall comprise the following,
Earth electrode of 15mm diameter copper earth rod set with driving pin
and head driven to a minimum depth of 3 meters. This shall be installed as
near to the consumer’s main board as possible inside earth pit with
inspection cover as per figure 2.1. The earth electrode shall include a
corrosion resistant terminal clamp. PVC insulated stranded copper earth conductor (35 mm 2 copper for single
consumer installation and 70 mm 2 copper multiple consumer
installation) with cramped terminal lugs, shall be connected between the
earth electrode and the consumer’s main earthing terminal or bar.
PVC insulated earth continuity conductor of every outgoing circuit from
the consumer’s main board shall be connected to the main earthing
terminal.
The resistance of the consumer’s earthing system to the general
mass of earth shall not exceed 50 Ω. To achieve this value in theareas of high soil resistivity, additional earth electrodes with a
minimum spacing of 3 meters shall be installed.
Consumer’s earth electrode resistance shall be measured in accordance
with the method described in Appendix VI of the OES4.
All metal work, exposed conductive parts and enclosures, in the
consumer’s installation (other than live conductors and current carrying
parts) shall be connected with PVC insulated earth continuity conductor
to the main earthing terminal.
The consumer’s earthing system shall be connected to the MEW(electricity Distribution Company) earthing system.
The neutral conductor shall remain insulated throughout the installation
and shall not at any point be connected to the earthing system.
8/18/2019 Electrical Skills Lab Manual
42/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
(Note: all dimensions are in mm)
Figure 2.1: Earth Pit
8/18/2019 Electrical Skills Lab Manual
43/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Aim: To measure the value of earth resistance and earth voltage by using Earth
Resistance Tester (Kyoritsu 4102A).
Apparatus Required:
1) Earth resistance tester - 1 No.
2) Connecting leads - 3 Nos.
3) Earth Electrodes - 2 Nos.
4) Hammer - 1 No.
Theory:
The importance of earthing lies in the fact that it deals with safety. The word
‘earthing’ comes from the fact that the technique itself involves making a low-
resistance connection to the earth or to the ground. The earth is considered to be a
large conductor which is at zero potential.
Reason for Earthing:
The basic reason for earthing is to prevent or minimize the risk of shock to human
beings and livestock by providing a low resistance discharge path for earth leakage
currents which would otherwise provide injuries or even death to a person or animal
touching the metal part.
The following diagram describes the degree of danger of the leakage current; if, it
flows in the human body.
8/18/2019 Electrical Skills Lab Manual
44/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
The following example through the figures describes how the earthing system works:
In the following diagram the metallic part is not earthed and the human being is
touching it.
Let,
The supply voltage is 240V, AC circuit. The apparatus is having 40Ω and the defectiveinsulation is making the metallic body live and it is not earthed. Let the body
resistance is 1000Ω:
As shown above the leakage current may cause death to the person that is in contact
with the metallic part. The fuse in the path will not be able to identify the small rise in
current.
In the following diagram the metallic part is earthed and the human being is touching
it.
With the same supply system let, the sum of the resistance of cable and the metallic
part be 10Ω
Now the current is 4.8 times the fuse rating current. So, the fuse will operate andprotect the human by:
i. Blowing out and separating the supply from the body in touch with the
equipment
ii. By making the potential across the body ‘Zero’ (i.e. a shorted electric part
through the earth wires).
8/18/2019 Electrical Skills Lab Manual
45/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Types of earth electrodes:
Rod and pipe electrodes:
The following drawing describes how such electrodes are used in a distribution
wiring system:
Plate electrodes:
8/18/2019 Electrical Skills Lab Manual
46/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
The following drawing describes how such electrodes are used in a distribution
wiring system:
8/18/2019 Electrical Skills Lab Manual
47/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
48/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Preparation for Measurement:
A)
Mechanical Zero Adjustment
To obtain a measurement value with high accuracy, rotate the meter zero adjuster
with a screwdriver with the range selector switch OFF, and surely match the
indicator to “0” graduation value at the left of the scale board.
B)
Connecting Test ProbeInsert the plug of the probe securely into the terminals of the instrument. Loose
connection may result in inaccurate measurements.
C)
Battery Voltage Check
Set the range selector switch to BATT.CHECK position and press the test button.
Then the indicator swings, make sure that the indicator is at the right of BATT.GOOD
graduation borderline on the scale board. Otherwise, the batteries are exhausted.
Connection Diagram:
8/18/2019 Electrical Skills Lab Manual
49/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Procedure:
1) Strike the auxiliary earth spikes P and C into the ground deeply. They should be
aligned at and interval of 5 -10 meters from the earthed equipment under test.
2) Connect the Green Wire to the earthed equipment under test, Yellow to the
auxiliary earth spike P and the Red to the auxiliary earth spike C from terminals E,
P and C of the instrument respectively.
3) Set the range switch to EARTH VOLTAGE position to check earth voltage. Record
the reading in table below.
4) Set the range switch to × 100 positions, and press the test button. The LED
remains illuminated during testing. Turn the range switch to × 10 and × 1
when the earth resistance is low. This indicated value is the EARTH RESISTANCE of
the earthed equipment under test.
5) Change the spike ‘P’ position to 2m, 4m, 6m, 8m, 10m from the earth pin ‘E’ and
note down the earth resistance and tabulate the readings.
Observations:
Distance From the Earth
Pin ‘E’ to the Spike P
Earth Resistance Observed
Value (Unit)
2 m
4 m
6 m
8 m
10 m
8/18/2019 Electrical Skills Lab Manual
50/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Graph
The variation of earth resistance with distance
Conclusions:
Answer Following Questions,
Why is it necessary to provide earthing?
From the observations above, comment if the earth resistance measured is
acceptable as per the OES 4.
If the value of resistance is unacceptable, what are the measures required to bring itto the acceptable range?
8/18/2019 Electrical Skills Lab Manual
51/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Exercise 3: Preparation of Galvanized Steel Conduit
STANDARD, OES 4
Section 3.13
Steel Conduits and fittings for use in building electrical installations shall
comply with BS 4568, Parts 1 and 2 of heavy gauge hot dip galvanized inside
and outside, screwed type.
Section 6.1
Installation of Conduits
The conduits for each circuit shall be completely installed before any cable is
drawn in.
Conduits shall be securely fixed and where they are liable to mechanical
damage they shall be adequately protected.
Provision for the safe and easy drawing in of cables shall be made by use of
inspection fittings, draw boxes. Provisions shall be such that cables can be
drawn in or replaced without the cables being damaged or conduit
dismantled.
All runs of the conduit shall be truly vertical or horizontal.
Section 6.2
Conduit Saddles
Where conduits are installed on the surface of building fabric they shall be
supported by purpose made conduit saddles or spacer bar saddles.
Supports shall be provided at a maximum spacing of 1500 mm for
galvanized steel conduits and 1200 mm for high impact PVC conduit.
Section 6.3
Smooth Finish of Conduits
The boxes of all the conduits shall be smooth and free from projection which
may injure cables or obstruct their drawing in. ends of conduits shall be so
reamed and when they terminate at boxes, trunking and accessories not fitted with spout entries, shall be so bushed as to obviate abrasion of cables.
8/18/2019 Electrical Skills Lab Manual
52/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Section 6.4
Radius of Bend
The radius of every conduit bend shall not be less than 2.5 times the outside
diameter of the conduit.
Section 6.5
Galvanized Steel Conduits
Galvanized Steel conduit system shall be earthed and connected to the earth-
continuity conductor. All joints shall be made mechanically and electrically
continuous by screwing. The conduit shall not however be used as an earth
continuity conductor and a separate earth continuity cable shall be drawn
into the conduit for every final sub-circuit.
Only Galvanized Steel conduits shall be used in the space between a roof and
suspended false ceiling, in situations subject to fire risk and in surface
mounted industrial installation. PVC conduits shall not be used for such
applications. (Derogation issued in2009 to use PVC conduits)
Galvanized Steel conduits shall not be used under floor tiles of buildings or in
concealed wiring systems embedded in walls or floors. PVC conduits shall be
used for all such applications.
Section 6.6
PVC Conduits and Fittings
PVC conduits and fittings shall be of the unthreaded type. All joints shall be
made with vinyl cement and entries of all conduit fittings shall be designed
such that reliable water tight joints can be obtained.
Surface mounted PVC conduit systems shall be so supported as to allow for
longitudinal expansion and contraction. A cement that shall remain in
adhesive plasticized state shall be used for expansion couplers.
Section 6.7
Flexible Conduits
Flexible conduits shall only be used for the final connection of motors and
other equipment subject to vibration or adjustment of position.
PVC flexible conduits and fittings shall comply with BS 4607 part 3. Metallic
flexible conduits and fittings shall comply with BS 731 Part 1 and shall
preferable be provided with an outer sheath of PVC.
Flexible metal conduit shall not be used as the sole means of providing earth
continuity and a separate earth continuity cable shall be provided.
8/18/2019 Electrical Skills Lab Manual
53/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Where necessary, flexible conduit shall be adequately supported and / or
protected.
In damp or wet situations flexible conduits shall be watertight and remain
impervious to ingress of water or moisture.
The ends of flexible conduit shall be securely anchored to fixed conduit and /or equipment entries by purpose made flexible conduit adaptors.
Section 6.8
Conduit Sizes
Conduits shall be limited to the following sizes
16 mm, 20 mm, 25 mm, 32 mm and 50 mm
8/18/2019 Electrical Skills Lab Manual
54/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Aim: To make the Galvanized Steel conduit to do the wiring for the following
measurement.
1) Making 900 bend from a fixed point.
2) Making two 900 set.
3) Making thread for 1.5 cm at one end.
Tools Required:
1) Steel Pipe Bending Vice - 1 No.
2) Steel Pipe - 1 No.
3) Threading Die - 1 No.
4) Hand File - 1 No.
5) Wire Brush - 1 No.
6) Measuring Tape - 1 No.
7) Marker Pen - 1 No.
Cutting:
Conduit pipes can be cut by using a hacksaw or a pipe cutter as shown in the following
figures:
Procedure:
1. Fix the conduit in the vice so that the vice grips the conduit 50 or 75mm from the
point where the cut has to be made
2. The blade is to be installed so that the cut is made on the forward stroke.
Precautions:a. After cutting by any method the inside edge
of the conduit must be smoothed with half
round file as shown in the figure.
b. Be sure that the ridge is cleared beforeinstalling the pipe for wiring.
c.
8/18/2019 Electrical Skills Lab Manual
55/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Threading:
When short lengths of conduits are to be used for switch or lamp drops, the end of
the pipe needs to be threaded to enable fixing of the conduit to the accessories. The
threads on the conduit in all cases shall be between 11mm to 27mm long.
This threading of conduit is done by using dies and a die-stock.
Note:
1. Apply cutting oil to the end before starting to cut threads.
2. Cutting threads longer than necessary will leave exposed threads that are not
protected from corrosion.
Precaution:
a. Use only a brush to remove the metal burrs from the die. Do not use your hand.
Metal conduit boxes and the symbols used in metal conduit wiring:
The following figure shows different popular outlet boxes used in metal conduitwiring:
8/18/2019 Electrical Skills Lab Manual
56/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Following figure shows the various symbols used for different boxes in a single line
diagram for such a wiring:
The following figure shows the wall and ceiling boxes for conduit wiring, a switching
box is also displayed:
8/18/2019 Electrical Skills Lab Manual
57/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Preparing the boxes for the conduit wiring:
The boxes can be used after removing the knock-outs in the boxes. The knock-outs
can be removed from the boxes by using any of the method shown in the following
figures:
After removing the knockouts the boxes are prepared as shown in the following
figure:
8/18/2019 Electrical Skills Lab Manual
58/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Conduit pipe bending:
It is often necessary to set or bend the conduit to enable it to pass over an
obstruction as shown in the following figure:
The bending can be made by using:
a. Simple bending block:
b. Simple bending hickey:
8/18/2019 Electrical Skills Lab Manual
59/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
c. Using a bending machine:
60 mm80 mm
mm63
8
160
8
d
d = outer diameter of
the bending pulley
Actual radius of bend =
inner radius of the pulley
Pulley
8/18/2019 Electrical Skills Lab Manual
60/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Procedure:
1. Measure diameter of the Galvanized Steel Pipe given for the exercise.
2. Select suitable pulley for bending the pipe.
3. Making 900 bend from a fixed point.
1) Take a steel pipe of length 900 mm and mark 300 mm from the edge or a fixed
point consider that mark as an initial mark.
2) Add th8
1 of the outer circumference of the bending pulley from the initial mark
Example: 300mm + ( 8
160
) =363 mm and consider this as a new mark.
3) Place the tube in the former with the fixed point at the rear and place the pipe
exactly at the new mark which should be aligned with the perpendicular scale.
4) This will give a 900 bend at the required distance from the fixed point to the back
of the bend.
4. Making two 900 set:
1) From initial mark of 300 mm, measure another 300 mm and mark.
900
300
300 63 mm
300
mm
8/18/2019 Electrical Skills Lab Manual
61/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
2) Take this new mark as reference, subtract th8
1 of the outer circumference of the
bending pulley. Consider this as reference mark for the second bend.
3) Now measure the gap between two bends. If you get 300mm from center to
center of the bends means your work is carried out successfully.
5. Making thread at one end:1) Mark the threading length in the steel pipe from the fixed end. Take the die and
fix it with the tool used for making the thread.
2) Place the threading tool at the edge of the pipe and rotate it in forward direction
for one full circle and rotate in opposite direction for one full circle.
300
mm
300 mm
63 mm
300mm
300 mm
300
mm
8/18/2019 Electrical Skills Lab Manual
62/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
3) Repeat the same thing until the full thread is made at one end as per the
measurement.
Results:
1. Mention the various types of conduits.
2. What are the available sizes of conduits used in industry?
3. Mention the applications of various types of conduits.
4. Mention the precautions taken while performing the exercise?
S.No Quantity Measurement
1 Length of pipe used
2 Size of Pipe used
3 The angle made at one end
4 The angle made at other end
5 Radius of the bend
6 Distance between the bends
7 Distance from one end to center of the bend
8/18/2019 Electrical Skills Lab Manual
63/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Exercise 4: Wiring Lighting Circuit
STANDARD OES 4
Section 4.2.10
Connection of Switch and Control Gear
Switches, circuit breakers, fuses, thermostats and similar control devices shall
be connected in live (phase) conductor only, a bolted or screwed link being
connected in the neutral conductor. If the switch or circuit breaker includes an
isolating neutral link, it shall be arranged to make before and open after the
live (phase) poles.
Section 4.2.17
Load on lighting circuits
Load on lighting circuits in domestic installations shall not exceed 1500 W per
final sub circuit.
Section 4.2.20
Lighting Switches
Local switches for lighting points and for appliances not connected to socket
outlets shall have a minimum current rating of 5A. For outdoor and industrial
use, switches shall be metal clad and water tight.
Switches for control of discharge lighting shall have a current rating of not less
than twice the steady state continuous current of the circuit.
All local switches shall be mounted in readily accessible positions with the
dollies at the minimum height of 1250 mm from finished floor level.
In kitchens and in situations other than bathrooms, where water is regularly
used no switch shall be mounted within 2 meters of any tap, basin, sink, if this is
not possible, ceiling mounted insulating cord operated switches shall be used.
In bathroom and toilets, switches shall be of the ceiling mounted insulating
cord operated type. If wall mounted switches are used for control of lighting
and exhaust fans, same shall be located in an accessible position outside the
bathroom or toilet and immediately adjacent to the door. Special wall mounted
switch for control of supply to water heater shall be similarly mounted.
Switches for lighting and fans inside a room shall be mounted inside the room
on the side of the door nearest to the door catch, handle knob or lock
approximately 150mm from the door frame.
8/18/2019 Electrical Skills Lab Manual
64/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Section 5.2
Current Ratings
Current Ratings for single core and multicore cables to be adopted for use in
consumer’s installation are set out in tables 2, 3, 4 and 5 (Appendix IV) of OES4.
The current carried by the cables at any time shall not exceed the specified
ratings.
Section 5.4
Protection against damage
All conductors and cables shall be adequately protected against any risk of
mechanical damage to which they may be liable in normal condition of service.
Where cables pass through hole in metal works, rubbers or plastic grummets or
bushes shall be provided of the edge lined with soft material to prevent
abrasion of the cables.
Section 5.18
Flexible cord and cables
Current ratings for flexible cords and cables are set out in Table 1 (Appendix IV)
of OES4.
Where the apparatus requires to be earthed, flexible with earth core shall be
used.
Where the flexible cables and cords are exposed to the risk of mechanical
damage, they shall as a minimum be sheathed with PVC or rubber and where
necessary shall be armored, the armour not being used as sole means of
providing earth continuity.
Flexible cords and cables shall be connected to plugs, ceiling roses and movable
apparatus with the BROWN core to phase, BLUE core to neutral and
GREEN/YELLOW core to earth terminal of accessory or frame of the apparatus.
In situations where high temperatures are encountered, flexible cables and
cords shall be insulated with silicon rubber type E12 of BS6899/IEC540
Where a flexible cord supports or partially supports a luminaire, the maximum
mass supported by the cord shall not exceed the values given in Table 1
(Appendix IV)
8/18/2019 Electrical Skills Lab Manual
65/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Section 5.19
Colour identification of cable cores
a.
Colour identification of insulated cable cores for fixed installation and of
sleeve, band or disc for bare conductors shall be as follows:
- earthing conductor green and yellow
- phase of a.c. single phase circuit red
- neutral of a.c.single phase or three phase circuit black
- phase R of three phase a.c. circuit red
- phase Y of three phase a.c. circuit yellow
- phase B of three phase a.c. circuit blue
- positive of d.c. 2 wire red
- negative of d.c. 2 wire black
b. Colour identification of flexible cables and flexible cords shall be as follows:
- live brown
- neutral blue
- earthing green and yellow
Mounting Heights of Accessories
Item Height from finished floor level
Lighting Switch 1250 mm
Ceiling Fan Regulator 1250 mm
20Amp, D.P switch for water heater or A/C units 1250 mm
Shaver socket outlets 1250 mm
13Amp switched socket outlet for general purpose 450 mm
13Amp switched socket outlet in kitchen 250 mm
Cooker control unit 1000 mm
8/18/2019 Electrical Skills Lab Manual
66/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Symbols of Electrical Accessories – (Appendix 3 of OES 4)
8/18/2019 Electrical Skills Lab Manual
67/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
68/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
8/18/2019 Electrical Skills Lab Manual
69/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Aim : To connect two lamps in parallel
Objectives:
1) Knowing the OES 4 and its sections pertaining to wiring at different installations
2) Category of load as per OES 4
3) Standards pertaining to wiring of a building for a normal household consumer
4) Standard pertaining to voltage drop, current rating, parallel operation and
protection against damage.
5) Practice of wiring for a normal parallel connected load for domestic application.
Tools Required:
6) Electrical / Manual Driller
7) Screw Drivers
8) Hacksaw frame with Blade
9) Wire Stripper
10) Pliers
Accessories Required:
1) PVC Conduit
2) Conduit Saddles and Screws
3) Elbow or Bend
4) Junction box5) Lamp Holders with Lamps
6) Single pole switch
7) Miniature Circuit Breaker (MCB)
8) Earth Leakage Circuit Breaker (ELCB)
9) 15 Amps , 1 Way Terminal Box
Measuring Instruments:
Multi Meter for measurement of current and voltage
8/18/2019 Electrical Skills Lab Manual
70/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Circuit Diagram:
Line Diagram:
Single Phase240 V, 50 Hz
L
N
S
L1 L2
E
Distribution
Board ELCB MCB Switch
Lamp 1
Lamp 2
8/18/2019 Electrical Skills Lab Manual
71/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Layout Diagram:
8/18/2019 Electrical Skills Lab Manual
72/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
List of Material:
Sr. No. Item SpecificationQuantity
Required
1 Conduit
2 Saddles
3
Cable Red
Cable Black
Cable Yellow and Green
4 Switch
5 Junction box
6 Elbows or Bends
7 Lamp holder
8 MCB
9 ELCB
10 Lamp1
11 Lamp2
12 Clamp meter
8/18/2019 Electrical Skills Lab Manual
73/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Procedure:
1) Connect the items collected per the layout diagram on the work board.
2) Check the tightness of the connections.
3) Never forget to verify the tracing of the wires as per the layout diagram.
4) CHARGE THE CIRCUIT UNDER THE SUPERVISION OF TECHNICIAN.
5) Verify the live terminal at input of the ELCB using line tester.
6) Switch ON the ELCB and using line tester observe that the circuit is live and the
wiring is perfect.
7) Switch on the MCB and observe that the wiring is working perfect.
8) Similarly check that the live terminal at the Lamp Holders turns Live, only on
making the switch ON.
9) Note the Operation of the circuit by visual inspection and record the data in
your report.
10) Note down the reading of Voltage and current in the observation table and
calculate the power.
8/18/2019 Electrical Skills Lab Manual
74/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Measurements and Calculations:
Sr. No. Condition Voltage (V) Current (I)
1
Only Lamp1
(______W,______V)
2Only Lamp2
(______W,______V)
3 Lamp 1 and 2
Calculations:
SlNo
Specification Voltage V
CurrentI
Power
Consumed (P)
1 Lamp 1 (alone): ______W
2 Lamp 2 (alone): ______W
Result: Write how the activity performed meets the requirements of various
sections of OES referred at the beginning of this experiment.
Answer the following questions.
1. What is the use of MCB in the circuit?
2. What is the use of ELCB in the circuit?
3. By observing the Currents drawn by the circuit and bulbs, How the bulbs
are connected?4. What is the use of earth terminal in the circuit?
8/18/2019 Electrical Skills Lab Manual
75/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
5. Exercise 5: Testing Wiring Circuits
GUIDELINES FOR TESTING WIRING CIRCUITS AND CERTIFICATION OF TESTING
The Oman Electricity Standard, OES 4 in Section 11 guides on the testing and inspection of
the electrical installation.
STANDARD, OES4
Section 11.1 General
Every installation and major alteration to an existing installation shall on
completion and before being energized, be inspected and tested to verify
compliance with MEW regulations.
Section 11.2 Visual Inspection
A visual inspection shall be carried out to verify if the installation is in
accordance with approved drawings and the execution of the work andworkmanship and the installation methods adopted meet the requirements of
the MEW regulations.
Section 11.3 Colour Identification
It shall be verified that the correct colour identification has been adopted for all
wiring and the fuses and switches are connected in the live conductors only and
links or linked switches are connected in the neutral conductor.
Section 11.4 Earth Continuity Test
Earth continuity test shall be carried out between the consumer’s earthing
terminal and the remote end earth continuity conductors.
The resistance value obtained shall not exceed 0.5 ohm.
Section 11.5 Insulation Resistance Test
Insulation resistance test shall be carried out on the installation. For purpose of
these tests large installations must be divided into groups each containing 50
outlets. A 500V DC test voltage shall be applied.
The insulation resistance to the earth shall not be less than 1 mega ohm, when
measured with all poles and phases of wiring connected together and switchesand fuses all in place. The insulation resistance when measured between all the
conductors connected to any one pole or phase of supply and in turn all
conductors connected to each other pole or phase shall not be less than 1 mega
ohm.
8/18/2019 Electrical Skills Lab Manual
76/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Section 11.6 Continuity Test
Test shall be made to verify the continuity of all conductors including the earth
continuity conductor of every ring circuit.
Section 11.7 Earth Electrode Resistance Measurement
Earth Electrode Resistance Measurement shall be carried out in accordance
with method described in Appendix VI. The resistance shall not exceed 50 Ohms.
Additional electrodes shall be provided where necessary to obtain this value.
Section 11.8 Protection Test
Tests shall be carried out to verify effective and correct operation of all earth
leakage circuit breakers, close excess current protection of circuit breakers and
fuse links and other protective devices.
Section 11.9 Completion CertificateFollowing the inspection and testing, a completion certificate in the attached
format shall be submitted by the electrical contractor to MEW signed by
contractor’s competent engineer. The installation will then be further inspected
and tested by MEW inspector and if found satisfactory, the installation will be
permitted to be connected to supply.
8/18/2019 Electrical Skills Lab Manual
77/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
COMPLETION CERTIFICATE
(Completion certificate to be given by the Electrical Contractor and signed by
Contractor’s Competent Engineer/ Supervisor):
I hereby certify that the electrical installations at:
has been completed, inspected and tested in accordance with the regulations
for electrical installations issued by the Ministry of Electricity and Water,
Sultanate of Oman and is now ready for connection to mains supply.
The results are given in the attached forms.
Signed: ___________________________________ Date:__________________
For and on behalf of : _____________________________________________
_______________________________________________
_______________________________________________
Address: ______________________________________________
________________________________________________
_______________________________________________
MEW Registration No. and Date: _____________________________________
8/18/2019 Electrical Skills Lab Manual
78/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
FORM A
Particulars of the installation covered by this Certificate:
New Installation. Alteration / Extension to existing installation.
Installation Drawing:
It is anticipated that the installation would comprise the following:
S. No. Description No.kW
Unit Total
1 Light Points
2 Air conditioners
3 Fans
4 Single Phase Motors
5 Three Phase Motors
6 Water Heaters
7 Refrigerators
8 Freezers
9 Cookers
10 13 A Socket Outlets
11 Other Loads
12 …………………………………
13 …………………………………
Comment (if any) on existing installation (where the certificate relates to an
alteration or addition)
Signed:____________________________________ Date:_________________
8/18/2019 Electrical Skills Lab Manual
79/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
FORM B
INSPECTION AND TEST REPORT
1. Compliance with drawings:
2.
Standard of Installation:
Material:
Workmanship:
3.
Colour identification of wiring:
4.
Polarity Checks:
Switches:
Breakers:
Links:
Linked Switches:
5. Resistance of Earth Continuity
Conductor from remote end to
main earthing point:
6.
Insulation Resistance:
- With all poles and phases
connected together and
switches, fuses and breakers
all in place
- With all conductor on one
phase connected together
and in turn all conductors
connected to each other.
– Red:
– Yellow:
– Blue:
– Neutral:
8/18/2019 Electrical Skills Lab Manual
80/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
7. Continuity of all Conductors
- Red:
- Yellow:
- Blue:
- Neutral:
- Earth:
8.
Continuity of earth continuity conductor in ring circuit for socket outlet.
9. Earth Electrode Resistance:
10.
Earth Leakage Circuit Breakers(Residual Current Operated Type)
Continuous Rating Operating Current
(A)
(mA)
Main Subsidiary 1)
2)
11. Load Balance
Red Yellow Blue
- Lights
- Refrigerators
- Air conditioners
- Freezers
- Cooker
- Motors
- Water Heaters
- 13A Socket Outlet
- Other Loads
Signed:_____________________________________ Date:_________________
8/18/2019 Electrical Skills Lab Manual
81/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Objectives: At the end of the exercise the student should be able to understand the
following:
1) Understanding the need for Testing and Inspection of wiring in electricalinstallations
2) Understanding the different types of Testing and Inspection procedures as perOES 4
3) Preparing ‘Completion Certificate’ pertaining to Testing and Inspection ofelectrical wiring as per OES 4
4) Inspection & Testing procedure required to follow as per OES 4, for a givenelectrical circuit.
Aim : To Connect a 3 Pin Plug connection and perform following tests
1) Visual inspection
2) Color Identification
3) Earth Continuity Test
4) Continuity Test and
5) Protection Test
Tools Required:
1) Electrical / Manual Driller
2) Screw Drivers
3) Hacksaw frame with Blade
4) Wire Stripper
5) Pliers
6) Line Tester
Accessories Required:
1) Conduits
2) Conduit Saddles and Screws
3) Elbow or Bend
4) Red, Black and Yellow/ Green Cable
5) Junction box6) 3 Pin Plugs with Switches
7) Miniature Circuit Breaker (MCB)
8) Earth Leakage Circuit Breaker (ELCB)
9) 15 Amps , 1 Way Terminal Block
8/18/2019 Electrical Skills Lab Manual
82/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Measuring Instruments:
Multi Meter (KYORITSU KEW SNAP 2017)
8/18/2019 Electrical Skills Lab Manual
83/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Circuit Diagram:
Line Diagram:
Single Phase
240 V, 50 Hz
AC Supply
DistributionBoard
ELCB
MCB 1
Switch Socket
Outlet 1
MCB 2
Switch Socket
Outlet 2
8/18/2019 Electrical Skills Lab Manual
84/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Layout Diagram:
8/18/2019 Electrical Skills Lab Manual
85/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
List of Material:
Sr. No. Item SpecificationQuantity
Required
1 Conduit
2 Saddles
3 Elbows or Bends
4
Cable Red
Cable Black
Cable Yellow and Green
5 Switch Socket Unit
6 Junction box
7 Terminal Box
8 MCB
9 ELCB
10 Clamp meter
8/18/2019 Electrical Skills Lab Manual
86/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Procedure:
Visual Inspection Test:
Observe the following points in this test and write observations.
1. The installation is as per the layout diagram.
2. The installation comprises of the protection devices as shown in the line
diagram.
3. Accessories used are of standard quality and note down the standards printed
(if any)
4. Connections and joints of the cable are firm/ tight and appropriately insulated.
5. Cables are protected against mechanical damage.
6. Switches are mounted at a minimum height of 1250 mm from finished ground
surface.
Colour Identification:
Observe that appropriate colour code is used in the electrical installation. Write the
observations below,
1. Colour of the cable used for Live/ phase wire:__________________
2. Colour of the cable used for Neutral wire: _____________________
3. Colour of the cable used for Earth wire: _______________________
Earth Continuity Test:
Write observation in the table below.
Sr.
No.Connection of the multimeter
ObservationComment
Sound Resistance
1
Earth terminal of Socket Outlet
1 and Earth terminal of the
Distribution board
2
Earth terminal of Socket Outlet
2 and Earth terminal of the
Distribution board
8/18/2019 Electrical Skills Lab Manual
87/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Continuity Test:
Sr.
No.Connection of meter
ObservationComment
Sound Resistance
1 Line terminal of outlet 1 and Lineterminal of outlet 2
2Neutral terminal of outlet 1 and
Neutral terminal of outlet 2
3Line terminal of outlet 1 and Line
terminal of Distribution Box
4
Neutral terminal of outlet 1 and
Neutral terminal of Distribution
Box
5Line terminal of outlet 1 andEarth terminal of Distribution Box
6Neutral terminal of outlet 1 and
Earth terminal of Distribution Box
Protection Test:
Press the test button of the ELCB and note your observation:
8/18/2019 Electrical Skills Lab Manual
88/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Answer the following questions
1. What is Visual Electrical Inspection?
2. Explain color identification procedure for electrical installation
3. What is Earth continuity test?
4. What should be the Insulation resistance as per OES-4?
5. What is continuity test?
6. How much should be the earth resistance as per OES -4?
8/18/2019 Electrical Skills Lab Manual
89/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Exercise 6: Connection of Fluorescent Tube Light
Objectives: At the end of the session the student should be able to,
1) Draw the circuit diagram of a single tube fluorescent lamp
2) State the function of each component in the circuit3) State probable causes for different problems in the circuit malfunctioning
Aim: To study the working principle, assemble, connect and check the fluorescent tube
light.
Tools Required:
1) Line Tester
Accessories Required:
1) Fluorescent Tube Light 20 W
2) Tube light fitting
3) Ballast
4) Starter
5) Connecting wires
Types of lamps:
8/18/2019 Electrical Skills Lab Manual
90/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Construction:
The fluorescent tube light consists, a sealed glass tube. The tube contains very
small amount of Mercury mixed with an inert gas, typically Argon, kept under very
low pressure.
The tube also contains a Phosphor powder, coated along the inside of the glass.
8/18/2019 Electrical Skills Lab Manual
91/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
The tube has two electrodes, one at each end, which are connected to the electrical
supply through bi-pin plugs at both ends of the tube.
Ballast/ Choke: Starter:
Circuit diagram:
Starter
CapacitorCathode
Ballast/
Choke
Switch
240V, AC
Supply
Bi-PinPlug
Cathode
Bi-PinPlug
8/18/2019 Electrical Skills Lab Manual
92/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
Features of Fluorescent Tube Light:
require a ballast
have a range of color temperatures and color rendering capabilities have low surface brightness compared to point sources
have a cooler operation are more efficacious compared to incandescent ambient temperatures and convection currents can affect light output and life all fixtures installed indoors must use a Class P ballast that disconnects the ballast in
the event it begins to overheat; high ballast operating temperatures can shorten
ballast life
have options for starting methods and lamp current loadings require compatibility with ballast low temperatures can affect starting unless a "cold weather" ballast is specified
Working of the Fluorescent Tube Light Circuit:
The electrical circuit is connected to an alternating current (AC) supply of 240V, 50 Hz.
When the switch is turned ON, the path of least resistance is through the bypass
circuit, and across the starter switch. In this circuit, the current passes through the
electrodes on both ends of the tube. These electrodes are simple filaments, like you
would find in an incandescent light bulb. When the current runs through the bypass
circuit, electricity heats up the filaments. This boils off electrons from the metal
surface, sending them into the gas tube, ionizing the gas.
8/18/2019 Electrical Skills Lab Manual
93/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
At the same time, the electrical current sets off an interesting sequence of events in
the starter switch. The conventional starter switch is a small discharge bulb,
containing neon or some other gas. The bulb has two electrodes positioned right
next to each other. When electricity is initially passed through the bypass circuit, an
electrical arc (essentially, a flow of charged particles) jumps between these
electrodes to make a connection. This arc lights the bulb in the same way a larger
arc lights a fluorescent bulb
One of the electrodes is a bimetallic strip that bends when it is heated. The small
amount of heat from the lit bulb bends the bimetallic strip so it makes contact with
the other electrode. With the two electrodes touching each other, the current
doesn't need to jump as an arc anymore. Consequently, there are no charged
particles flowing through the gas, and the light goes out. Without the heat from the
light, the bimetallic strip cools, bending away from the other electrode. This opens
the circuit.
By the time this happens, the filaments have already ionized the gas in the
fluorescent tube, creating an electrically conductive medium. The tube just needs avoltage kick across the electrodes to establish an electrical arc. This kick is provided
by the lamp's ballast , a special sort of transformer wired into the circuit.
8/18/2019 Electrical Skills Lab Manual
94/112
EEPW 2241: Electrical Skills Lab Manual Shinas College of Technology
Updated by Mr. Murali Krishna Boddu & Mr. Mahesh Aphale
When the current flows through the bypass circuit, it establishes a mag