PROJECT:

TITLE:

DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY

NO.: DATE:REVISION:

DATE: 7.9.2015

SCALE: NTS

DRAWING NUMBER:

US.RSBS.05.01

2 PLY SBS MEMBRANE, INSULATEDCURB WITH NON-REMOVABLE

COUNTERFLASHINGUSAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS.

PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING.

US CORPORATE ADDRESS310 QUADRAL DRIVE

WADSWORTH, OHIO 44281www.soprema.usTel:330.334.0066

W I L L I A M G R A N T G A L L O W A Y

DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING

NOTES:1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL

INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THEDETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES.

2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO THE NRCA CERTA RECOMMENDATIONS, LOCALCODES AND BUILDING OWNER'S REQUIREMENTS FOR HOT WORK OPERATIONS.

3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS4. FLASHING PLIES MUST EXTEND VERTICALLY A MINIMUM OF 8" FROM ROOF SURFACE. FLASHING PLIES EXTENDING VERTICALLY MORE THAN 24" FROM ROOF SURFACE MUST BE ADHERED AND

MECHANICALLY FASTENED ALONG THE TOP LEADING EDGE. REFER TO PUBLISHED DOCUMENTATION.5. FOR 90° TRANSITIONS, FLASHING PLIES MUST MEET THE FOLLOWING REQUIREMENTS: HEAT WELD POLYESTER REINFORCED FLASHING BASE PLIES. HEAT WELD POLYESTER REINFORCED

GRANULE FLASHING CAP SHEET, OR HEAT WELD FOIL/FILM CLAD FLASHING CAP SHEET.

CURB NON-REMOVABLE CURB COUNTERFLASHING

FASTEN AT 8" O.C. ALONG TOP LEADING EDGE

SHEET METAL COUNTERFLASHING

FLASHING CAP SHEET

CAP SHEET

POLYESTER REINFORCED FLASHING BASE PLY

BASE PLY

FLASHING CAP SHEET

CAP SHEET

POLYESTER REINFORCED FLASHING BASE PLY

BASE PLY

BASE SHEET/ANCHOR SHEET

VAPOR RETARDER/AIR BARRIER

COVERBOARD

DECKDECKDECKDECKDECKDECKDECKDECK

FASTEN AT 8" O.C.IN BOTH DIRECTIONS

FASTEN AT 8" O.C.IN BOTH DIRECTIONS

EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CANT

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND FASTENER PLATE

INSTALL FASTENER PLATE A MINIMUMOF 1" FROM CANT AND SPACED A

MAXIMUM OF 12" APART ALONG WALL

EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY

CANT

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CURB

EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY

INSTALL FASTENER PLATE A MINIMUMOF 1" BEYOND BASE OF CURB AND

SPACED A MAXIMUM OF 12" ALONG WALL

EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CURB

EXTEND FLASHING CAP SHEETA MINIMUM OF 1" BEYONDFLASHING BASE PLY

FASTEN AT 8" O.C. ALONG TOP LEADING EDGE

REMOVE/EMBEDSURFACING AS REQUIREDREMOVE/EMBED

SURFACING AS REQUIRED

BASE SHEET/ANCHOR SHEET

INSULATION

INSULATION

INSULATION

THERMAL BARRIER

INSULATION

THERMAL BARRIERTHERMAL BARRIER

VAPOR RETARDER/AIR BARRIER/BACKER PLYBASE SHEET/ANCHOR SHEET/BACKER PLYBASE SHEET/ANCHOR SHEET/BACKER PLY

EXTEND A MINIMUM OF 3" BEYOND BASE OF WALL