12-104 Molded Case Circuit Breakers800 - 2500 AmperesR-Frame
Cutler-HammerJanuary 2001
Vol. 1, Ref. No. [0570]
Digitrip RMS 510 Electronic Circuit Breakers with Interchangeable Rating PlugsOrder as individual components: Breaker Frame (which includes Trip Unit) and Rating Plug.
Table 12-160. Digitrip RMS 510 Electronic Circuit Breakers with Interchangeable Rating Plugs '
MaximumContinuousAmpereRating@40°C
Circuit Breaker Frame OnlyL - Adjustable Long Delay Pickup (lr) with Adjustable Long Delay TimeS - Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)1 - Adjustable Instantaneous PickupG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I2t or Flat Response)LI LS LSI | LIG LSG | LSIGCatalog Number
Digitrip Rating Plug OnlyRatedCurrent('n>
FixedRating Plug
Catalog Number
3-Pole Standard Interrupting Capacity 600V AC Rated 65 kAIC © 480V AC1600
2000
2500
RD316T51W
RD320T51W
RD325T51W
RD316T53W
RD320T53W
RD325T53W
RD316T52W
RD320T52W
RD325T52W
RD316TB4W
RD320T54W
RD325T54W
RD316T55W
RD320T55W
RD325T55W
RD316T56W
RD320T56W
RD325T56W
800100012001600
1000120016002000160020002500
RP6R16A080RP6R16A100RP6R16A120RP6R16A160RP6R20A100RP6R20A120RP6R20A160RP6R20A200RP6R25A160RP6R25A200RP6R25A250
3-Pole High Interrupting Capacity 600V AC Rated 100 kAIC @ 480V AC1600
2000
2500
RDC316T51W
RDC320T51W
RDC325T51W
RDC316T53W
RDC320T53W
RDC325T53W
RDC316T52W
RDC320T52W
RDC325T52W
RDC316T54W
RDC320T54W
RDC325T54W
RDC316T55W
RDC320T55W
RDC325T55W
RDC316T56W
RDC320T56W
RDC325T56W
800100012001600
1000120016002000160020002500
RP6R16A080RP6R16A100RP6R16A120RP6R16A160
RP6R20A100RP6R20A120RP6R20A160RP6R20A200RP6RZ5A160RP6R25A200RP6R25A250
® See Table 12-161 below for prices.Note: Instruction Leaflet/FRED Number 29C107 for Breaker; Number 29C885 for Digitrip 510 Trip Unit
Table 12-161. Digitrip RMS 510 Electronic Circuit Breakers with Interchangeable Rating Plugs Prices
CatalogNumber
RDC316T51WRDC316T52WRDC316T53WRDC316T54WRDC316T55WRDC316T56WRDC320T51WRDC320T52WRDC320T53WRDC320T54W
PriceU.S. $
17,750.19,990.18,120.20,640.21,050.22,790.19,180.21,450.19,560.22,010.
CatalogNumber
RDC320T55WRDC320T56WRDC325T51WRDC325T52WRDC325T53WRDC325T54WRDC325T55WRDC325T56WRD316T51WRD316T52W
PriceU.S. S
22,450.24,250.25,750.27,600.26,120.28,230.28,600.30,090.15,980.18,070.
CatalogNumber
RD316T53WRD316T54WRD316T55WRD316T56WRD320T51WRD320T52WRD320T53WRD320T54WRD320T55WRD320T56W
PriceU.S. S
16,300.18,380.16,430.20,770.17,260.19,490.17 ,610 .20,150.20,560.22,300.
CatalogNumber
RD325T51WRD325T52WRD325T53WRD325T54WRD325T55WRD325T56WRP6R16A080RP6R16A100RP6R16A120RP6R16A160
PriceU.S.$
23,260.25,120.23,630.20,560.26,110.27,600.
1 1 2 .1 1 2 .1 1 2 .1 1 2 .
CatalogNumber
RP6R20A100RP6R20A120RP6R20A160RP6R20A200RP6R25A160RP6R25A200RP6R25A250
PriceU.S.S
1 1 2 .1 1 2 .1 1 2 .1 1 2 .1 1 2 .1 1 2 .1 1 2 .
Discount Symbol, CB-2
F:T» For more information contact Cutler-Hammer at: www.ch.cutler-hammer.coni/catalog CAT.200.01.T.E
12-2
For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
January 2001
12
Product Line OverviewVol. 1, Ref. No. [0468]
Product Line DescriptionCutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems. They are described by NEMA as, “. . . a device for closing and inter-rupting a circuit between separable contacts under both normal and abnormal conditions,” and furthermore as, “. . . a breaker assembled as an integral unit in a supporting and enclosing housing of insulating material.” The NEC describes them as, “A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overload of current, without injury to itself when properly applied within its rating.”
So designed, Cutler-Hammer circuit breakers protect conductors against overloads and conductors and con-nected apparatus, such as motors and motor starters, against short circuits.
In low voltage distribution systems, there are many varied applications of molded case circuit breakers. Cutler-Hammer offers the most comprehensive family of molded case circuit breakers in the industry.
This family of circuit breakers includes:
■ Thermal Magnetic Trip Breakers■ Electronic rms Trip Breakers■ Molded Case Switches■ Motor Circuit Protectors■ Current Limiting Breakers■ Special Application Breakers■ World Breakers
Special CalibrationSpecial non-UL-listed calibrations are available for certain ambient temperatures other than 40°C and for frequencies other than 50/60 Hz or DC. Reduced interrupting ratings will apply for 400 Hz applications. Maximum thermal calibration is limited to 135A at 400 Hz.
50°C CalibrationAdd suffix V to Catalog Number for complete breaker, listed above, when ordering listed ampere ratings for breakers to be used in 50°C ambients.
Moisture-Fungus TreatmentAll circuit breaker cases are molded from glass-polyester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment.
Freeze-Tested Circuit BreakersThe circuit breakers may be ordered with freeze testing. This option uses special lubrication and mechanical operation is verified at -40°C.
Marine ApplicationsF-Frame circuit breakers can be sup-plied to meet the following marine specifications:
■ U.S. Coast Guard CFR 46 ABS — American Bureau of Shipping IEEE 45
These specifications generally require molded case circuit breakers to be supplied with 50°C ambient calibration, special nameplating, and plug-in adapter kits. When plug-in adapter kits are used, no terminals need be supplied.
Circuit breakers can also be supplied to meet UL489 Supplement SA (Marine Use) and UL489 Supplement SB (Naval Use).
UL489 Supplement SA applies to vessels over 65 feet in length. Requirements include 40°C ambient calibration, spe-cial labeling, and no use of aluminum conductors or terminals.
UL 489 Supplement SB requires 50°C ambient calibration, vibration testings, special nameplating and no use of aluminum conductors or terminals.
Standards and CertificationsMolded case circuit breakers are designed to conform with the follow-ing standards:
■ Underwriters Laboratories, Inc., Standard UL489, Molded Case Circuit Breakers and Circuit Breaker Enclosures
■ National Electrical Manufacturers Association Standards Publication No. AB1-1993, Molded Case Circuit Breakers
■ Australian Standard AS 2184, Molded Case Circuit Breakers
■ British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1: Circuit Breakers
■ Canadian Standards Association Standard C22.2 No. 5, Service Entrance and Branch Circuit Breakers
■ International Electrotechnical Commission Recommendations IEC 157-1, Circuit Breakers
■ Japanese T-Mark Standard Molded Case Circuit Breakers
■ South African Bureau of Standards, Standard SABS 156, Standard Specification for Molded Case Circuit Breakers
■ Swiss Electro-Technical Association Standard SEV 157-1, Safety Regula-tions for Circuit Breakers
■ Union Technique de l’Electricite Standard NF C 63-120, Low Voltage Switchgear and Control Gear Circuit Breaker Requirements
■ Verband Deutscher Elektrotechniker (Association of German Electrical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers
Conformance with these standards satisfies most local and international codes, assuming user acceptability and simplified application.
Molded case circuit breakers equal or exceed Federal Specification Classifi-cation W-C-375b requirements for the particular class associated with the cir-cuit breaker frame being considered.
Note: For further information, see Circuit Breaker, CD-ROM SA.74A.01.T.E.
Suffix H01 400 Hz 20% Adder
Suffix J01 Fungus Treated $325. + 20% Adder
Suffix F01 Freeze Tested 20% Adder
Suffix H08 “Marine” 10% Adder
Suffix H09 “Naval” 10% Adder
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog
12January 2001 Product Line OverviewVol. 1, Ref. No. [0471]
Table 12-1. Industrial Circuit Breakers (Continued)
� N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit.� Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250V DC.
CircuitBreakerType
Cont.AmpRating@ 40°C
No.Poles
Volts Type of Trip �
Federal Spec.W-C-375b
UL Listed Interrupting Ratings rms Symmetrical Amperes PageNumberAC DC AC Ratings Volts DC �
120 120/240 240 277 480 600 125 250 125/250
R-FrameRD 1600CRD 1600RD 2000RD 2500CRD 2000RDC 1600CRDC 1600RDC 2000RDC 2500CRDC 2000
800 – 1600800 – 1600
1000 – 20001000 – 25001000 – 2000800 – 1600800 – 1600
1000 – 20001000 – 25001000 – 2000
3, 43, 43, 43, 43, 43, 43, 43, 43, 43, 4
600600600600600600600600600600
— —————————
N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.
24a24a24a24a24a25a25a25a25a25a
— —————————
— —————————
125,000125,000125,000200,000125,000200,000200,000200,000200,000200,000
— —————————
65,00065,00065,00065,00065,000
100,000100,000100,000100,000100,000
50,00050,00050,00050,00050,00065,00065,00065,00065,00065,000
— —————————
— —————————
— —————————
12-10012-10312-10012-10012-10312-10212-10312-10212-10212-103
Series C HMCP Motor Circuit Protectors 12-118
Current Limit R Current Limiting Circuit Breakers — Non-Fused TypeFCL 15 – 100 2, 3 480 — N.I.T. — — — 200,000 — 150,000 — — — — 12-129
LCL 125 – 400 2, 3 600 — N.I.T. — — — 200,000 — 200,000 100,000 — — — 12-130
Tri-Pac Current Limiting Circuit Breakers — Fused TypeFB 15 – 100 2, 3 600 250 N.I.T. 16a, 16b,
17a, 26a— — 200,000 — 200,000 200,000 — — 100,000 12-132
LA 70 – 400 2, 3 600 250 I.T. 16a, 16b,17a, 26a
— — 200,000 — 200,000 200,000 — — 100,000 12-133
NB 300 – 800 2, 3 600 250 I.T. 16b, 17a,26a
— — 200,000 — 200,000 200,000 — — 100,000 12-135
PB 600 – 1600 2, 3 600 250 I.T. 17a, 26a — — 200,000 — 200,000 200,000 — — 100,000 12-137
Cutler-HammerJanuary 2001Vol. 1, Ref. No. [0563]
Molded Case Circuit Breakers800 - 2500 AmperesR-Frame
12-97
ContentsDescription
Product Description .Technical Data
and Specifications .Dimensions/WeightsProduct Selection ...
Page12-97
12-9712-9912-99
R-Frame Product DescriptionR-Frame Circuit Breakers are avail-able as frame (which includes tripunit), rating plug and terminals.
All R-Frame circuit breakers aresuitable for reverse feed use.
Typical R-Frame Circuit Breaker
Technical Data and SpecificationsTable 12-148. UL489/CSA Interrupting Capacity RatingsCircuitBreakerType
RDCRD®RDCCROC®
Numberof Poles
3,43,43,4
3,4
Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)240
125
125
200
200
277
——
—
—
480
65
65
100
100
600
50
50
65
65
® Utilization Category A circuit breakers.® 100% Rated breakers.Note: See Page 12-98 for Trip Unit Specifications.
Table 12-149. IEC 947-2 Interrupting Capacity Ratings <CircuitBreakerType
RDleuIcsRDCleuIcs
Number ofPoles
3,4
3,4
Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)240
135100
200100
415
7050
10050
690
2513
3518
® Utilization Category A circuit breakers.
CAT.200.01.T.E For more information contact Cutler-Hammer at www.ch.cutler-hammer.com/catalog F.T-iy
Cutler-HammerJanuary 2001Vol. 1, Ref. No. [05651
H Molded Case Circuit Breakers 17 qq• 800 -2500 Amperes
R-Frame
Dimensions/WeightsTable 12-151. Dimensions in Inches (mm)Numberof Poles
34
'
Width Height
15.5(394) 16(406)20 (508) 16 (406)
Depth
9.75 (248)
9.75 (248)
^ ' i
Table 12-152. Approximate Shipping Weight, Lbs. (kg)BreakerType
Complete BreakerNumber of Poles3 4
1600ARD, CRD, RDC, CROC 102(46.3) 135(61.2)
2000ARD, RDCCRD, CROC
102 (46.3)130 (59.0)
135(61.2)175 (79.4)
2500ARD, RDC 135(61.2) 182 (82.6)
Product SelectionThis information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbersfor circuit breakers or trip units.
Table 12-153. Circuit Breaker/Frame Catalog Numbering System ______ _______ ________________ _____
RD 3 16 T32 W
Numberof Poles
3 = 3 Poles4 = 4 Poles
rCircuit Breaker/
Frame Ampere Rating16= 1600A20 = 2000A
J JTrip Type ®
T32T53T65T86T96T106T107
= Digitrip RMS 310 LSI= Digitrip RMS 510 LS= Digitrip RMS 610 LSG= Digitrip RMS 810 LSIG= Digitrip RMS 910 LSIG= Digitrip OPTIM 1050 LSIG= Digitrip OPTIM 1050 LSIA
SuffixW = Without TerminalsP = 100% Protected Neutral PoleR = Ground Fault Remote
(310 Only)K = Molded Case Switch
® For complete list of available trip types refer to Pages 12-100-12-113 .I ••.•.
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T'N