A D D R E S S A B L E

L I N E A R H E A T D E T E C T I O N

▪ Innovations

▪ Solutions

▪ SupportLinear Heat Detection

Now for Use on ANY Addressable Panel

Just Add an Addressable Contact Monitor Module

Compatible with ANY Conventional Fire Alarm Panel

Better

Up to 10,000 Linear Feet (3,000m) of SafeCable per Zone

RF Tested up to 10,000 Linear Feet (3,000m)

Longer Spool Lengths Available

Farther

Lower Material Costs

Less Installation Time

No Expensive Linear Heat Detection Panels to Buy and Maintain

Lower Cost

Up to 10,000 Linear Feet per Zone

▪ Longer Runs

▪ Less Resistance

▪ Lower cost

Advanced Design Allows Up to 10,000 Linear Feet of SafeCableper Zone

Tri-Metallic Core Reduces Resistance to Only .05 ohms/ftResistance per Twisted Pair Wire

Designed to be Compatible with ALL Addressable andConventional Fire Alarm Control and Releasing Panels

Reduce Material and Installation Costs with Less Splicing,Longer Spool Lengths, and Easier Installation

Multiple alarm temperatures can be combined on the samezone

Total zone length replacement unnecessary after alarm

Pro

du

cts

Detection

Temperatures:

155 F (68 C)

172 F (78 C)

190 F (88 C)

220 F (105 C)

Nylon - UV protected for outdoor applications and extradurable for harsh industrial environments.

Polypropylene – For chemically harsh and causticenvironments such as wet benches.

GuideWire – For spanning distances up to 250 ft. (76m)with supports every 15 ft. (4.6m).

Up to 10,000 Linear Feet per Zone

▪ Longer Runs

▪ Less Resistance

▪ Lower cost

Detection

Temperatures:

155 F (68 C)

172 F (78 C)

190 F (88 C)

220 F (105 C)

TC155NG

Temperature

Nylon

Guidewire

Multiple Outer Coverings Available for Specific Hazards

Alarm Point Distance Locating

Up to 10,000 Linear Feet per Zone

▪ Longer Runs

▪ Less Resistance

▪ Lower cost

Detection

Temperatures:

155 F (68 C)

172 F (78 C)

190 F (88 C)

220 F (105 C)Alarm Point Distance Locating Displays in Both Feet and Meters

May be Used for Both Class “A” and “B” Applications

Only .05 ohms/ft resistance per Twisted Pair

▪ Longer Runs

▪ Less Resistance

▪ Lower cost

Pro

du

cts

SPACING AND TEMPERATURE

Temperature Rating UL, C-UL-US FM

155 F (68 C) 35’ (10.7m) 30’ (9.1m)

172 F (78 C) 35’ (10.7m) 30’ (9.1m)

190 F (88 C) 35’ (10.7m) 30’ (9.1m)

220 F (105 C) 35’ (10.7m) 25’ (7.6m)

35’ (10.7m)

17’6” (5.3m).7x

Area Spacing

Listed Spacing

▪ Any Panel

▪ Addressable

▪ ConventionalSystem Components

Co

mp

on

en

ts

▪ Any Panel

▪ Addressable

▪ ConventionalTypical System Configurations

ADDRESSABLE SYSTEM

CONFIGURATION

CONVENTIONAL SYSTEM

CONFIGURATION

Installation Accessories

▪ Mounting

▪ Connecting

▪ Splicing

Acc

ess

ori

es

Clamps, Clips, Ties, Mounts, Adhesive

Mounting

Junction Boxes and Fittings

Connecting

Terminal Blocks, Tapes, Sealers

Splicing

▪ Commercial

▪ Industrial

▪ UtilitiesFlexibility to Adapt to Your Environment

Addressable / Conventional Linear Heat Detection

▪ Any Panel

▪ Addressable

▪ Conventional

Linear Heat Detection

One Company, Five Great Products

Recommended