SecoBloc IEC OEM Modules3.3kV - 17.5kV, Type BC & BV
GEIndustrial Solutions
The next generation of reliability, performance and sustainability
2
GEGE is a diversified organization covering myriad market segments, including infrastructure and finance. From energy, water, transportation and health to access to money and information, GE serves customers in more than 100 countries and employs more than 300,000 people worldwide.
The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the original index in 1896.
Industrial SolutionsIndustrial Solutions, a GE heritage business, is leading the future of electrifica-tion with advanced technologies that protect and control the distribution of electricity throughout a facility’s infrastructure. We provide customers across various industries with end-to-end product and service solutions that ensure the reliability and protection of the electrical infrastructure; from the substation, to a facility’s critical equipment, and all the power technologies in between.
Honors
2013 World’s Most Admired Companies 2010 World’s Most Innovative Companies
2012 Best Global Brand 2012 World’s Most Respected Companies
2010 World’s Most Respected Companies
3
More Than 90 Years of Interrupter ExperienceGE was a pioneer in experimental vacuum interrupters in the 1920s. Over the years, we refined the design and introduced the world’s first 15kV vacuum circuit breaker in the 1960s. This interrupter design has been a world leader in vacuum technology, with over 55 years of reliable field service.
Universal ApplicationsSecoBloc is designed, assembled and tested to meet or exceed applicable IEC standards. It is suitable for applications in all major industries including Transmission and Distribution, Oil & Gas, Automotive, Processing plants, Iron and Steel mills, Mining, and Commercial buildings.
SecoBloc provides protection for all types of applications including coble, overhead lines, motors, capacitors, transformers and bus bar sections.
World Class QualityManufactured, assembled and tested all in the same facility, SecoBloc is the product of sophisticated manufacturing processes assured by ISO 9001:2008 and ISO 14001 certification. Precision tooled parts, computer aided design and advanced production techniques, as well as the protection of the ‘E Coat’ (cathodic electro coating) paint process have resulted in a standard of excellence unmatched in the industry.
Environmental ConsciousnessSelecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used instead of SF6 gas for SecoVac series MV embedded pole vacuum circuit breakers.
5
Table of Contents
SecoBloc OEM Modules Overview and Applications ............6
Type BC and BV 3.3kV – 17.5kV Module Features ..................7
Technical Characteristics
Interlocking Systems ..............................................................................9
Optional Interlocking ...........................................................................10
Environmental Conditions.................................................................11
Construction ............................................................................................11
Standards .................................................................................................11
Selection Table .......................................................................................11
Scope of Supply - Optional Supply Details ...........................12
Technical Data
SecoBloc Type BC and BV Characteristics ................................13
SecoVac Embedded Pole Vacuum Circuit Breaker
Features, Benefits, Applications .....................................................14
Circuit Breaker Characteristics .......................................................15
Internal Wiring Diagram ....................................................................16
Internal Wiring Diagram (UVR) ........................................................17
SecoVac Vacuum Fuse Contactor ..........................................18
Fuse Contactor Characteristics ......................................................18
Internal Wiring Diagram ....................................................................19
Earthing Switch and Disconnect Truck Characteristics .........................................20
Components and Controls ......................................................21
SecoVac Checklist .....................................................................22
SecoVac FC Checklist ...............................................................23
SecoBloc BC and BV Modules Checklist ................................24
6
SecoBloc OEM modules are designed and manufactured with advanced technology and have been comprehensively and successfully type-tested.
Designed specifically for use by OEM switchgear manufacturers building IEC designs, SecoBloc OEM modules offer greater configuration flexibility than traditional full height sections.
SecoBloc modules are rated for 3.3kV - 17.5kV applications, 630A - 3150A and up to 40kA short circuit rating. They are designed to house GE’s SecoVac embedded pole vacuum circuit breakers.
IEC SecoBloc modules include two different versions. The SecoBloc BV is a complete module that includes the apparatus and lower compartment. The SecoBloc BC module offers an apparatus compartment.
ApplicationsUtilities and Power Plants Power generation stations Transformer stationsSwitching stationsMain and auxiliary switchgear E-House
IndustrialOil & Gas MiningPulp and PaperCementTextilesChemicalsAutomotivePetrochemicalData CentersMetallurgy
TransportationAirportsPortsRailwaysUnderground Transportation
Services Supermarkets Shopping mallsHospitalsLarge infrastructure and civil works
Seco
Bloc
OEM
Mod
ules
Ove
rvie
w a
nd A
pplic
atio
ns
MarineDrilling & ExplorationMerchantCruiseFPSONaval
7
Features• Air insulated OEM blocs in a compact design• Complete interlocking system to prevent
incorrect operation and to improve safety
• Tested in accordance with the IEC International Standards
• Utilizes embedded pole SecoVac vacuum circuit breakers
• Designed for universal OEM applications
Innovative in design, SecoBloc compact blocs are the next generation of reliability, performance and sustainability from GE. Fully IEC tested to IEC 62271-100 and IEC 62271-200, they meet the requirements of LSC2B. SecoBloc is suited to provide OEMs with a simple, cost effective solution that is easy to order and assemble.
SecoBloc Type BC1 and BV 3.3kV – 17.5kV Modules
3
2
4
5
6
8
9 10
1112
7Upper spout
Lower spout
Earthing switch
Earthing switch drive
Earthing switch lugs
Apparatus compartment door
Emergency trip
Viewing window
Apparatus racking operating aperture
Earthing switch operating aperture
Lower compartment1
Lower compartment door
1
7
2
8
3
9
4
10
5
11
6
12
Control socketControl plug interlock
Wiring duct coverBus bar side shutter
Cable side shutter
Shutter mechanismRail
Service/Test position mechanical indicator
1
7
2
8
3
4
5
6
1
3
2
4
5
6
87
1
1. BC Module does not include lower compartment
Module Interior
Type
BC
and
BV
3.3k
V –
17.5
kV M
odul
e Fe
atur
es
8
Built to the highest quality standards SecoBloc is designed and fully tested to 2014 IEC standards. It utilizes GE’s latest SecoVac vacuum circuit breaker, third-party tested in accordance with IEC 62271-100. Manufactured in accordance with high quality standards, GE engineers have integrated core technologies. Circuit breaker and mechanism design, vacuum arc control technology, insulation technology and electrical field control and analysis combine to create a highly reliable and compact system. SecoBloc reflects GE’s best MV switchgear design practices.
Construction type and IP rating SecoBloc Type BC/BV is designed and constructed to meet the requirements IEC 62271-200 for Indoor installations. SecoBloc offers IP43 protection from penetration of solid objects and liquids on the front side with its door closed.
Earthing SwitchThe SecoBloc earthing switch can be closed under short-circuit up to 40kA. The earthing switch isolators are provided with a capacitive voltage sensor for connection with the voltage presence indication system.
SecoVac MechanismThe SecoVac circuit breaker utilizes a compact, spring charged operating mechanism. The open and close mecha-nisms are combined into a single, small and easily replaceable module.
Automatic ShuttersThe SecoBloc OEM blocs are equipped with grounded metal shutters in front of the primary bushings. The shutters are automatically operated by the circuit breaker movement. When the circuit breaker is racked out to the test or disconnect positions, the shutters automatically close to isolate the fixed primary contacts. As an option, shutters are available with a safety interlock, which in the absence of a withdrawable apparatus, will prevent manual activation.
Marine ApplicationSecoBloc has been tested for Marine applications according to the IEC 60068-2-6 and IEC 60092-504.
Inclination Test– Determines that SecoBloc can continue operating as intended, even when inclined at an angle up to 25 degrees on all four sides.
Vibration Test - The operating conditions on marine platforms and shipping installations require the capability to work in environments
affected by vibrations. SecoBloc was exposed to a resonance search and endurance random, which consists of a random vibration test according to IACS E10.
Vibration Sweep Test:• From 2 to 13.2 Hz displacement
1.0 (peak value)
• From 13.2 to 100 Hz acceleration amplitude of 0.7 g
• Vibration Endurance Test - 90 minutes
The exposure to these severe service conditions confirms the suitability of SecoBloc to unstable marine conditions. The SecoBloc Marine version includes a handrail in the breaker compartment door as well as doorstoppers.
Type
BC
and
BV
3.3k
V –
17.5
kV M
odul
e Fe
atur
es
9
Technical CharacteristicsInterlocking SystemsSecoBloc is designed with a number of interlocking systems to help prevent mis-operation:
• The circuit breaker can only be moved from test to connect position and vice versa when the circuit breaker is in the Open position
• The earthing switch cannot be closed when the circuit breaker is in the connect position or in the traveling position between test and connect
• For BV modules, the cable compartment door can only be opened when the earthing switch is closed
• For BV modules, the earthing switch can be opened only when the cable compartment door is closed
• The secondary plug can only be inserted or removed when the circuit breaker is in the test position
• The circuit breaker cannot be closed when it is in-between the connected, test or disconnect positions
• When the circuit breaker is moved from the connect position, the metal shutters will close automatically
• The circuit breaker can only be racked-in when the Apparatus Compartment door is closed
• The Apparatus Compartment door can only be open when the circuit breaker is in test position
Description of Interlock System Key Condition
Functional truck racking-out lock
Key will be free when the truck is in the connected positionKey will be trapped when the truck is in the disconnected/ test position
Functional truck racking-in lock
Key will be free when the truck is in the disconnected/ test positionKey will be trapped when the truck is in the connected position
Earthing switch closing lock
Key will be free when earthing switch is openKey will be trapped when the earthing switch is closed
Earthing switch opening lock
Key will be free when the earthing switch is closedKey will be locked when the earthing switch is open
up/downstream key free with CB withdrawn
key free with CB rack-in from test position
key free with ES close
up/downstream key free with ES Open
Tech
nica
l Cha
ract
eris
tics
10
Optional InterlockingSecoBloc provides various levels of safety operation with enhanced interlock system.
Category Condition Interlocking TypeSecoBloc 17.5kV
Standard Optional
Apparatus closing & opening
Apparatus could be closed only when:
1 Apparatus in service or test position and not in any intermediate position
Mechanical ✓
Electrical ✓
Apparatus could be opened without conditions.Padlocks allowance
1 Access to open button Padlock ✓
2 Access to close button Padlock ✓
Apparatus racking in/out locking from service to test positions
Apparatus could be Rack-Out from connected to test position only when:
1 Apparatus is openMechanical ✓
Electrical ✓
2 Key-lock A for VCB rack in is turned captive Key ✓
Apparatus could be Rack-In from test to connected position only when:
1 Apparatus is openMechanical ✓
Electrical ✓
2 Apparatus control plug is connected Electrical ✓
3 Earthing switch is openMechanical ✓
Electrical ✓
4 Apparatus compartment door is closedMechanical ✓
Electrical ✓
5 Key-lock B for VCB rack-in is turned captive Key ✓
Padlocks allowance1 Access to insert crank lever Padlock ✓
Earthing Switch closing & opening
Earthing switch could be closed only when:
1 Apparatus in test positionMechanical ✓
Electrical ✓
2 Permissive blocking magnet is energized Electrical ✓
3 Key-lock C for earthing switch is turned captive Key ✓
Earthing switch could be open only when:
1 Cable compartment door closed Mechanical ✓
Electrical ✓
2 Key-lock D for earthing switch is turned captive Key ✓
Padlocks allowance1 Access to insert operation lever Padlock ✓
Apparatus compart-ment door closing & opening
Apparatus compartment door could be opened only when:1 Apparatus in test position Mechanical ✓
Apparatus compartment door could be closed without conditions
Cable compartment door closing & opening
Cable compartment door could be opened only when:1 Earthing switch is closed Mechanical ✓
Cable compartment door could be closed without conditions
Shutters
Shutters could be opened only when:1 Activated by apparatus undercarriage Mechanical ✓
Shutters could be closed without conditions.Padlocks allowance
1 Padlock opening or closing Padlock ✓
Control PlugApparatus control plug could be connected / disconnected only when:
1 Apparatus is in test position Mechanical ✓
Note: Available Key interlocking brands: Castell, Fortress, Ronis
Tech
nica
l Cha
ract
eris
tics
Technical Characteristics
11
Technical CharacteristicsStorage conditionsIn order to retain all of the functional unit’s qualities when stored for prolonged periods, we recommend that the equip-ment is stored in its original packaging, in dry conditions sheltered from the sun and rain between –15°C and + 40°C.
Normal operating conditionsSecoBloc is designed for the normal service conditions in indoor switchgear per IEC Standards:
• Temperature
– Maximum Ambient: +40°C
– Minimum Ambient: -30°C
• Humidity
– Maximum Relative: 95%
• Altitude
– Maximum: 1000m a.s.l.
– High Altitude: At altitudes above 1000m, consult IEC 60071-2 for derating factors applicable to dielectric and current values.
Construction• Indoor construction, up to IP43
• All the metal surfaces in the panels are painted or plated for corrosion protection
• Panels are produced using Alu-Zn steel sheet
IEC StandardsSecoBloc complies with the standards and specification for OEM assembled switchgear and has been tested in accor-dance with the IEC publication below:
• IEC 62271-200: AC Metal enclosed switchgear and control gear for rated voltages above 1kV and up to 52kV
SecoBloc Selection Table Type
Incoming / Feeder Bus Tie
Bus Riser/ Direct Arrival
Bus Bar VT (Measurement)
Single Line Diagram
Lower Compartment Apparatus Compartment
YES(VT Included or VT
Provision or Empty)
SecoVac VB2+ 17.5kVBV-B
N/A
N/A
Disconnect TruckSecoVac FC 12kV BV-C N/AEmpty N/A BV-E
NO
SecoVac VB2+ 17.5kVBC-B
N/ADisconnect TruckSecoVac FC 12kV BV-C
N/AWithdrawable VT Truck N/A BC-VEmpty BC-E N/A
• IEC 62271-102: High-voltage alternating current disconnector and earth switches
• IEC 62271-1: The common specification for high voltage switchgear and control gear standards
• IEC 60529: Degrees of protection as provided by enclosures (IP Code)
• IEC 60068-2-6: Environmental testing - Part 2.6: Test FC Vibration (Sinusoidal)
• IEC 60092-504: Electrical installation in ships - Part 504: special features; control and Instrument
Tech
nica
l Cha
ract
eris
tics
12
Scope of Supply - Optional Supply DetailsEarthing SwitchOptional supply allows earthing the elements connected to the earthing switch lugs. It is typically used to earth incoming/outgoing power cables. When earthing switch is provided additional elements may also be provided:
• Mechanical interlock that prevents the SecoVac breaker to be racked-in from test to service position with the earthing switch closed, and prevents closing the earthing switch with the SecoVac breaker in service or any intermediate position, can be complemented with an optional supply redundant electrical interlock for the same purpose.
• On BV modules, earthing switch can be provided with a motor that allows opening and closing remotely.
• Voltage sensor is always provided together with the earthing switch and allows the customer to detect the presence of voltage of the elements electrically connected to the earthing switch lugs. Voltage sensor requires a voltage indicator display.
Emergency Pushbutton• Provides a mechanical trip of the circuit breaker with the SecoBloc module
apparatus door closed. It is typically used to open the breaker in case of loss of auxiliary voltage.
Marine Options• Handrails and door stoppers: Located in the apparatus compartment door
and door stoppers for the SecoBloc BC or BV module
• IP43 Cover: Metallic cover for the ESW operating aperture. The front side of the SecoBloc module achieves Ingress Protection Degree IP43.
Voltage TransformersSecondary windings, connection, accuracy class can be configured from multiple options
Mechanical InterlocksOptional safety interlocks for increased operational safety:
• Shutter Interlock: Prevents manual activation of the shutters, which will be only activated by the apparatus truck.
Key InterlocksKey interlocks provide the capability to have operation logic between multiple SecoBloc modules or upstream/downstream elements of the system. Available selections include Castell, Fortress and Ronis commercial brands.
• ESW Key Interlock: Up to two locks are available for the earthing switch. Either one or both of the two locks can be configured, providing multiple possible combinations for the condition of the key, trapped or released, when the ESW is in open position.
• VCB Key Interlock: Up to two locks are available for the VCB condition. Either one or both of the two locks can be configured, providing multiple possible combinations for the condition of the key, trapped or released, when the VCB is in test position.
Scop
e of
Sup
ply
- O
ptio
nal S
uppl
y D
etai
ls
13
Technical DataSecoBloc Type BC and BV Characteristics Module Type SecoBloc BC SecoBloc BVRated Voltage (kV) 7.2 / 12 /15 / 17.5 7.2 / 12 /15 / 17.5
Rated Insulation LevelPower Frequency Withstand Voltage (kV) 20 / 28 / 36 / 38 20 / 28 / 36 / 38
Lightning Impulse Withstand Voltage (kV) 60 / 75 / 95 / 95 60 / 75 / 95 / 95
Rated Current (A at 40º)
630 ✓ ✓
1250 ✓ ✓
1600 ✓ ✓
2000 ✓ ✓
2500 ✓ ✓
3150 ✓ ✓
Breaking Capacity (kA)25 ✓ ✓
31.5 ✓ ✓ ✓ ✓ ✓ ✓
40 ✓ ✓ ✓ ✓
Short time Withstand Current (kA/3s)25 ✓ ✓
31.5 ✓ ✓ ✓ ✓ ✓ ✓
40 ✓ ✓ ✓ ✓
Dimensions (mm)Width [A] 600 750 1000 600 750 1000Height [B] 1135 1135 1135 1680 1680 1680Total Depth [C] 1055 1043 1043 1055 1043 1043Earthing Switch Lug Depth [D] 1003 991 991 1003 991 991Module Depth [E] 716 704 704 716 704 704Distance Between Phases 150 210 275 150 210 275Weight (kg)Estimated Weight 200 300 400 250 350 450
Side/Front View
E
B
DC
AE
B
DC
A
A
E
E
D
D
C
C
B
B
Type BC
Type BV
Tech
nica
l Dat
a
14
SecoVac Embedded Pole Vacuum Circuit Breaker Reliability and high performance in a compact package
Modular design
Features and benefits• Environmentally friendly design
• Conformance to the current 2014 IEC standards
• Numerous safety features for maximum personnel protection
• User friendly operation with easy access and minimal inspection required
• Compact and cost effective
• Flexible with a full line of accessories and OEM Solution
Applications• Serving global 50 Hz and 60 Hz systems
• All segments of the electrical industry: industrial, commercial, utility, mining, marine and off-shore
• Protecting transformers, capacitor banks, motors, busbar sections and cables
• Contact GE sales office for special environment conditions: shock, vibration and high ambient temperature
Operation ToolRack handle for truck
Earthing switch handle
Seco
Vac
Embe
dded
Pol
e Va
cuum
Circ
uit B
reak
er
15
Type Name (GE) Rated Voltage Resistance Value (Ω) Rated Current (A) Inrush Current (A) Maximum Power (W)P-CAX 120 Vac 45 2.78 16.67 347.22P-CBX 240 Vac 320 0.72 - 0.75 4.32 - 4.5 165.89 - 180P-C5X 36 Vdc 3.12 11.54 69.23 415.38P-C6X 48 Vdc 3.1 15.48 92.9 743.23P-C7X 60 Vdc 10.78 5.57 33.4 333.95P-C1X 110 Vdc 51 2.16 12.94 237.25P-C2X 220 Vdc 198 1.11 6.67 244.44
Rated Voltage (V) Normal Operation Voltage Range (%) Charging Time at Rated Voltage (s) Input Power (W)110 Vac 85 - 110 < 15s 150125 Vac 85 - 110 < 15s 150220 Vac 85 - 110 < 15s 150230 - 240 Vac 85 - 110 < 15s 15024 Vdc 85 - 110 < 15s 15030 Vdc 85 - 110 < 15s 15048 Vdc 85 - 110 < 15s 15060 Vdc 85 - 110 < 15s 150110 Vdc 85 - 110 < 15s 150125 Vdc 85 - 110 < 15s 150220 Vdc 85 - 110 < 15s 150230 - 240 Vdc 85 - 110 < 15s 150
Item ValueRated Current (A) 1250~1600 2000~4000Resistance (μΩ) ≤ 45 ≤ 25
Coil Characteristics
Motor Characteristics
Main Circuit Resistance
Circuit Breaker CharacteristicsSpecifications DataRated Voltage (kV) 7.2 / 12 / 15 / 17.5Rated Power Frequency Withstand Voltage (1 min) (kV) 20 / 28 / 36 / 38Rated Lightning Impulse Withstand Voltage (1.2/50μs) (kVp) 60 / 75 / 95 / 95Rated Frequency (Hz) 50 / 60Rated Current (A) 630 / 1250 / 1600 / 2000 / 2500 / 3150Rated Short-circuit Breaking Current (kA) 25 / 31.5 / 40Percentage of DC Component Up to 50%Rated Short-circuit Closing Current (kAp) 65 / 82 / 104Rated Short-time Withstand Current (kA) 25 / 31.5 / 40Rated Peak Value Withstand Current (kAp) 65 / 82 / 104Rated Duration Time for Short-circuit (s) 3Opening Time (ms) 20 ~ 50Closing Time (ms) 30 ~ 70Rated Auxiliary Control Voltage (V) 36 / 48 / 60 / 110 / 220 Vdc - 110 / 220 VacOperation Sequence O – 0.3s – CO – 180s – CO / O – 0.3s - CO – 15s – COMechanical Life Operations (Quantity) 15.000 (M2)Electrical Endurance Class E2Single Capacitor Bank Switching Current (A) 400Rating Earthing Switch Short-time Withstand Current (kA 1s) 40
Seco
Vac
Embe
dded
Pol
e Va
cuum
Circ
uit B
reak
er
16
S9: Limit switch (connected position) CC: Closing coil KO: Anti-pumping relay (optional)
S8: Limit switch (test position) TC: Trip coil BC: Electromagnet for locking (optional)
S4: Electromagnet for locking auxiliary switch M: Spring charge motor ZC: Electromagnet for locking truck (optional)
S5: Auxiliary switch V1–V4: Rectifier
S1–S3: Energy storing limit switch
Notes:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.3. Rectifier will be removed if DC supply voltage is being used.
SecoVac Vacuum Circuit Breaker Internal Wiring Diagram
Spar
e Pa
rts
SecoGear 3.3kV-27kV Air Insulated Switchgear
S9
512221
44S522 S5
4321
13
14
11
1250 4914 48 58 56
81
82S514
13
S5
14S8 S8
34 24S8
13 33 23
S854
53
2434
33 23
S9 54
53
S9 S9
2 474 57 55
36 34 35 20
(21)(13)(21)
S3(14)S3(22) S1(22)
(52)
(51)
V1
2426 25
V2
Spring Charge Motor Closing Circuit
10
53 54 31 32
S844
43
44 S9
43
371513 1917 33 3938
S4
S5(74)
S5(54)
(2)(5)
(3)K0
(53)
S5
(73)
(12)
(11)
S5
(13)
(14) S2
CCK0
TC
6472 624232
4131 6371 61
8424 34
8323 33
S5
V4 V3
Breaker Interlock Circuit
52
Opening Circuit
30 273 5 97 23 2928
92
91
94
93
16
6
18
8
40
Truck Interlock Circuit
1
M BC
A~
D~
2
1
C+ B-
ZC
V5
Y4
SecoVac Vacuum Circuit Breaker Internal wiring diagram (AC) 17.5kV/27kV
S9: Limit switch (working position) CC: Closing coil KO: Anti-pumping relay (optional)
S8: Limit switch (testing position) TC: Trip coil BC: Electromagnet for locking (optional)
S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor ZC: Electomagnet for locking truck (optional)
S5: Auxiliary switch V1~V4: Rectitier
S1~S3: Energy storing travel switch
Note:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.
Spring Charge Motor Closing Circuit Opening CircuitBreaker Interlock Circuit Truck Interlock Circuit
Seco
Vac
Embe
dded
Pol
e Va
cuum
Circ
uit B
reak
er
17
S9: Limit switch (connected position) CC: Closing coil UM: UVR
S8: Limit switch (test position) TC: Trip coil KO: Anti-pumping relay (optional)
S4: Electromagnet for locking auxiliary switch M: Spring charge motor ZC: Electromagnet for locking truck (optional)
S5: Auxiliary switch MM: UVR PCB (optional) V1–V4: Rectifier
S1–S3: Energy storing travel switch BC: Electromagnet for locking (optional)
Notes:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.
SecoVac Vacuum Circuit Breaker Internal Wiring Diagram (UVR)
Spar
e Pa
rts
SecoGear 3.3kV-27kV Air Insulated Switchgear
SecoVac Vacuum Circuit Breaker Internal wiring diagram (AC) 17.5kV/27kV (with UVB)
S9: Limit switch (service position) CC: Closing coil UM: UVR
S8: Limit switch (test position) TC: Opening coil
S4: Electromagnet for locking's A.S. M: Motor K0: Anti-pumping relay (optional)
S1~S3: Energy storing travel switch MM:UVR PCB(optional) ZC: Electromagnet for locking truck(optional)
S5: Auxiliary switch BC: Electromagnet for locking (optional)
Note:1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.2. The polarity in dashed frame should be connected to common DC voltage terminal.
S9
44 512221
44S522 S5
4321
13
14
43 11
1250 4914 48 58 56
81
82S514
13
S5
14S8 S8
34 24S8
13 33 23
S854
53
2434
33 23
S9 54
53
S9 S9
2 474 57 55
36 34 35 20
(21)(13)(21)
S3(14)S3(22) S1(22)
(52)
(51)
V1
2526 24
V2
10
53 54 31 32
S844
43
44 S9
43
371513 1917 33 3938
S4
S5(74)
S5(54)
(2)(5)
(3)K0
(53)
S5
(73)
(12)
(11)
S5
(13)
(14) S2
CCK0
TC
6472 624232
4131 6371 61
8424 34
8323 33
S5
V4 V3
52 30 273 5 97 23 2928
92
91
94
93
16
6
18
8
40
1
M BC
UMMM
motor circuit closing circuit locking circuit opening circuit latch circuit
UVR circuit
A~
D~
2
1
C+ B-
ZC
V5
Y4
Spring Charge Motor Closing Circuit Opening CircuitBreaker Interlock Circuit Truck Interlock Circuit
UVR Circuit
Seco
Vac
Embe
dded
Pol
e Va
cuum
Circ
uit B
reak
er
18
Seco
Vac
Vacu
um F
use
Con
tact
or
SecoVac Vacuum Fuse Contactor
Features• Withdrawable type
• Conformance to the latest IEC standards. IEC 62271-1 and IEC 62271-106
• Comformance to IEC 60282-1 for high voltage fuse
• With/without mechanical latch
• HV fuse protection
• Interlocking features for safety
• Compact and robust
SecoVac fuse contactors are provided in withdrawable type and include high voltage fuses.
Specifications DataRated Voltage (Kv) 12Rated Frequency (Hz) 50/60 Hz±5%Rated Power Freq Withstand Voltage (1min) (kV) 28Rated Lightning Impulse Withstand Voltage (kV) 75Rated Currents for Contactor (A) 400Rated Short-time Withstand Current (3s) (kA) 4Rated Making Current (kA) 4Rated Peak Withstand Current (kA) 10.4Maximum Rated Breaking Current (A) 3200Minimum Rated Breaking Current (A) 80Use Type AC3/AC4Latch Type (Both Latched & Non-Latched Required) MechanicalMechanical Life (Times) 300kNumber of Auxiliary Contacts 5a/5bMinimum Auxiliary Contacts Rating AC 110V/10A, AC 220V/5A or DC
Control Voltage 48/110/125/220/230 VDC 110/125/220/230 VAC
Undervoltage and Tripping Coil for Mechanical Latched Type Contactor RequiredAnti-pumping Relay RequiredDrop-out Voltage of Contactor AC 85%/DC 70%SC Breaking Capacity for Fuse (kA) 50Rated Take-over Current (A) 3200
Specifications Unit EFEN SIBARated Current A 200 250Thermal Current A 140 160
Specifications Unit Fuse ContactorRated Current A 400Withdrawable μΩ ≤ 250
Fuse Contactor Characteristics
High Voltage Fuse Characteristics
Main Circuit Resistance of Fuse Contactor
Applications• Serving global 50 Hz and 60 Hz systems
• Segments of industry: Power generation, marine, water treatment, mining
• Medium voltage motor control applications
• Suitable for special environment conditions: Shock, vibration, high ambient temperature
• Suitable for marine applications
19
Seco
Vac
Vacu
um F
use
Con
tact
or
SecoVac Vacuum Fuse ContactorInternal Wiring Diagram for Mechanical Latch Type Contactor
SecoGear 3.3kV-27kV Air Insulated Switchgear
AC control circuit scheme
Internal wiring diagram for mechanical latch type contactor
SC
SB
SA
Close circuit
13
14
29
39
23
24
24
34
33
34
53
54
53
54
57
58
13
14
16
6
23
24
36
26
33
34
52
51
53
54
56
55
43
44
14
43
44
Work position
Test position
11
12
30
31
21
22
3
13
31
32
5
15
51
52
46
12
41
42
28
38
53
54
9
19
23
24
8
18
33
34
23
33
43
44
7
17
14
13
14
13
14
13
KM1
10
20
41
49
KM2
YC2
YC1 YT
1 2
Open circuit Close start
4
KM1
KM2 JSQ
27 43
13
14
Open start
48
12
11
12
11
12
11
SA
SB
SC
44
SA SB SC
S8
S9
22
21
22
21
22
21
QF
KM1
SC
SB
SA
Close circuit
13
14
29
39
23
24
24
34
33
34
53
54
53
54
57
58
13
14
16
6
23
24
36
26
33
34
52
51
53
54
56
55
43
44
14
43
44
Work position
Test position
11
12
30
31
21
22
3
13
31
32
5
15
51
52
46
12
41
42
28
38
53
54
9
19
23
24
8
18
33
34
23
33
43
44
7
17
14
13
14
13
14
13
10
20
41
49
KM2
YC2 YC1 YT
1 2
Open circuit Close start
4
KM1
KM2JSQ
27 43
13
14
Open start
48
12
11
12
11
12
11
SA
SB
SC
44
SA SB SC
S8
S9
22
21
22
21
22
21
QF
KM1 KM2
QF: Spindle auxiliary contact
YT: Open coil S8: Test position auxiliary contact
YC1, YC2: Close coil S9: Work position auxiliary contact
KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers
JSQ: Electro-magnetic counter
QF: Spindle auxiliary contact
YT: Open coil S8: Test position auxiliary contact
YC1, YC2: Close coil S9: Work position auxiliary contact
KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers
JSQ: Electro-magnetic counter
SecoGear 3.3kV-27kV Air Insulated Switchgear
AC control circuit scheme
Internal wiring diagram for mechanical latch type contactor
SC
SB
SA
Close circuit
13
14
29
39
23
24
24
34
33
34
53
54
53
54
57
58
13
14
16
6
23
24
36
26
33
34
52
51
53
54
56
55
43
44
14
43
44
Work position
Test position
11
12
30
31
21
22
3
13
31
32
5
15
51
52
46
12
41
42
28
38
53
54
9
19
23
24
8
18
33
34
23
33
43
44
7
17
14
13
14
13
14
13
KM1
10
20
41
49
KM2
YC2
YC1 YT
1 2
Open circuit Close start
4
KM1
KM2 JSQ
27 43
13
14
Open start
48
12
11
12
11
12
11
SA
SB
SC
44
SA SB SC
S8
S9
22
21
22
21
22
21
QF
KM1
SC
SB
SA
Close circuit
13
14
29
39
23
24
24
34
33
34
53
54
53
54
57
58
13
14
16
6
23
24
36
26
33
34
52
51
53
54
56
55
43
44
14
43
44
Work position
Test position
11
12
30
31
21
22
3
13
31
32
5
15
51
52
46
12
41
42
28
38
53
54
9
19
23
24
8
18
33
34
23
33
43
44
7
17
14
13
14
13
14
13
10
20
41
49
KM2
YC2 YC1 YT
1 2
Open circuit Close start
4
KM1
KM2JSQ
27 43
13
14
Open start
48
12
11
12
11
12
11
SA
SB
SC
44
SA SB SC
S8
S9
22
21
22
21
22
21
QF
KM1 KM2
QF: Spindle auxiliary contact
YT: Open coil S8: Test position auxiliary contact
YC1, YC2: Close coil S9: Work position auxiliary contact
KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers
JSQ: Electro-magnetic counter
QF: Spindle auxiliary contact
YT: Open coil S8: Test position auxiliary contact
YC1, YC2: Close coil S9: Work position auxiliary contact
KM1, KM2: DC contactor SA, SB, SC: Limit switches for fuse strikers
JSQ: Electro-magnetic counter
AC control circuit scheme
DC control circuit scheme
FC: Opened and in working position QF: Spindle auxiliary switch
YT: Open Coil S8: Test position auxiliary contact
YC1, YC2: Close coil S9: Work position auxiliary contact
KM1, KM2: DC Contactor SA, SB, SC: Limit switches for fuse strikers
JSQ: Electromagnetic counter
FC: Opened and in working position QF: Spindle auxiliary switch
YT: Open Coil S8: Test position auxiliary contact
YC1, YC2: Close coil S9: Work position auxiliary contact
KM1, KM2: DC Contactor SA, SB, SC: Limit switches for fuse strikers
JSQ: Electromagnetic counter
20
Voltage Transformer TruckThe withdrawable trucks also allow fuse replacement with the switchboard in service. Truck racking out with the door closed automatically operates closure of a metallic segregation shutter between the live parts of the switchgear and the instrument compartment.
Disconnect TruckDisconnect truck is used to disconnect primary circuit and normally coupling with bus bar tie breaker to achieve two section power supply. Disconnect truck can be provided with bus tie/ riser panels.
Earthing SwitchThe earthing switch can be operated from the front of the module. It is mechanically interlocked with the circuit breaker truck so that the earthing switch can only be operated when the circuit breaker is open in the test/disconnect position. The switch is also mechanically interlocked with the cable compartment door for additional safety.
Earthing Switch Characteristics
Disconnect Truck Characteristics
Specifications DataRated Voltage (kV) 7.2 / 12 / 15 / 17.5Rated Work Frequency Withstand Voltage (1 min) (kV) in open condition of switch 20 / 28 / 36 / 38Rated Lightning Impulse Withstand Voltage (peak value) in open condition of switch (kAp) 60 / 75 / 95 / 95Rated Short-time Withstand Current (3s) (kA) 31.5 / 40Rated Peak Value Withstand Current (kAp) 82 / 104Rated Short-circuit Making Current (kAp) 82 / 104Center Distance Between Phases (mm) 170 / 210 / 275Electric Endurance Class E1Mechanical Endurance (times) 2000
Specifications DataRated Voltage (kV) 17.5Rated Power Frequency Withstand Voltage (1 min) (kV) 38Rated Lightning Impulse Withstand Voltage (kV) 95Rated Frequency (Hz) 50 / 60Rated Current (A) 1250 / 1600 / 2000 / 2500 / 3150Rated Short-time Withstand Current (kA) 31.5 / 40 / 40 / 40Rated Peak Value Withstand Current (kAp) 82 / 104 / 104 / 104Rated Duration Time for Short-circuit (s) 3Dimensions As same current rating VCB
Earthing Switch and Disconnect Truck CharacteristicsEa
rthi
ng S
witc
h an
d D
isco
nnec
t Tru
ck C
hara
cter
istic
s
21
Current TransformerCurrent transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteris-tics for measuring metering and protec-tion purposes.
Current < 1250A the CT type is LZZB-17 150A1 or A4
Current > 1250A the CT type is LMZB1-17
HV Components
Ground Fault Sensing CTThe ground fault sensing CT is insulated in resin and is used to supply measure-ment and protection devices. These CTs can be furnished in either a solid or split core design. They can be used either for measuring phase currents or for detecting the ground fault current. They conform to the IEC 60044-1 Standards.
CT type: LMZC
Voltage TransformerVoltage transformers are cast in resin and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different character-istics for measuring, metering and protection purposes.
LV Components GE Industrial Solutions offers additional LV switchgear components for the completion of the switchgear control compartment, such as the voltage presence indicator display and a complete range of LV modular and control products.
Protection, Control and CommunicationGE Digital Energy offers a complete and extensive portfolio of hardware and software solutions including Multilin protection IEDs, communication devices and substation automation systems solutions.
Components and Controls
Com
pone
nts
and
Con
trol
s
22
SecoVac Checklist1 & 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Seco
Vac
VB2+
Bre
aker
Dev
ice
Type
Stru
ctur
e
Phas
e D
ista
nce
& V
olta
ge
Rate
d Cu
rren
t
Brea
king
Cur
rent
(kA)
Ope
n Co
il
Clos
e Co
il
Char
ging
Mot
or
Anti
Pum
p
Clos
e In
terl
ock
Truc
k In
terl
ock
Doo
r In
terl
ock
& P
adlo
ck
Und
er V
olta
ge
Seco
nd O
pen
Coil
Mot
oriz
ed R
ack
In/o
ut
Seco
ndar
y W
irin
g
DescriptionSV SecoVac VB2+ Breaker
I IEC SecoVac VB2+ G IEC/IEEE SecoVac VB2+G
W WithdrawableF Fixed
0 17.5kV, Pole Distance 150mm1 17.5kV, Pole Distance 210mm2 17.5kV, Pole Distance 275mm5 27kV, Pole Distance 210mm6 27kV, Pole Distance 275mm8 40.5kV, Pole Distance 275mmD 15kV Type G IEC/IEEE Pole Distance 210mmE 15kV Type G IEC/IEEE Pole Distance 275mm
0 630A1 1250A2 1600A3 2000A4 2500A5 3150A6 4000A
0 25kA1 31.5kA2 40kA3 50kA
X 0 0 0 0 0 0 None1 1 1 1 1 1 1 AC/DC110V2 2 2 2 2 2 2 2 AC/DC220V3 3 3 3 3 3 3 DC24V4 4 4 4 4 4 4 DC30V5 5 5 5 5 5 DC36V6 6 6 6 6 6 6 DC48V7 7 7 7 7 7 7 DC60V8 8 8 8 8 8 8 AC/DC125V9 9 9 9 9 9 9 AC/DC230-240V
Z Provided1 Door Interlock2 Padlock3 Door Interlock + Padlock
1 Through terminal block above SecoVac frame2 Through secondary plug with socket3 Through secondary socket above SecoVac frame with plug
Seco
Vac
Che
cklis
t
23
SecoVac FC Checklist
Seco
Vac
FC C
heck
list
1 & 2 & 3 4 5 6 7 8 9 10 11 12 13 14 15
Prod
uct C
ode
Rate
d Vo
ltage
Latc
h M
echa
nism
Cont
acto
r Cu
rren
t Rat
ing
Cont
rol V
olta
ge o
f Ope
n/Cl
ose
Coil
Auxi
liary
Con
tact
s
Fuse
Cur
rent
Rat
ing
Fuse
Vol
tage
Rat
ing
Fuse
Sho
rt C
ircu
it Ca
paci
ty
Fuse
Typ
e
Oth
er
Fuse
Bra
nd
Mot
oriz
ed R
ack
In/O
ut
WFC SecoVac FC Withdrawable, IEC Standard1 12kV2 7.2kV
E Electrical LatchM Mechanical Latch
1 400AA AC110VB DC110VC AC220VD DC220VE AC125VF DC125VG AC230VH DC230VI DC48V
0 None2 6 open & 6 closed4 5 open & 5 closed
A 200AB 250AC 224AD 160AE 125AF 100AG 80AH 90AI 31.5AJ 150AK 63AL 315AM 71AN 50AO 112AP 16AQ 40AR 355AS 25AZ None
0 None1 12kV2 7.2kV
0 None1 50kA
0 NoneM MotorT TransformerC Capacitor
0 NoneA Close Door Operation
1 Siba2 EFEN3 Xirong (Chinese Bussman)4 None (fuse not required)
0 None1 AC/DC110V2 AC/DC220VE 120VAC/125VDCF 240VAC/250VDC
24
SecoBloc BC and BV Modules Checklist 1 - 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Seco
Bloc
Upp
er C
ompa
rtm
ent T
ype
Bloc
Wid
th
Rate
d Vo
ltage
Rate
d Cu
rren
t
Shor
t-Ci
rcui
t Cur
rent
Eart
hing
Sw
itch
Volta
ge S
enso
r
Elec
tric
al In
terl
ocki
ng V
olta
ge
Key
Inte
rloc
k Br
and
Key
Inte
rloc
k fo
r ES
W
Key
Inte
rloc
k fo
r Ap
para
tus
Ra
ckin
g In
/out
Opt
iona
l Int
erlo
cks
Opt
iona
l Ele
men
ts
Mar
ine
Vers
ion
VT T
ruck
DescriptionBC IEC Module with Apparatus CompartmentBV IEC Module with Apparatus and Lower Compartments
B Breaker ApplicationC Contactor ApplicationV VT ApplicationE Empty Application
1 600mm2 750mm3 1000mm
1 7.2kV2 12kV3 17.5kV7 15kV
0 200A1 400A2 630A3 1250A4 1600A5 2000A6 2500A7 3150AN 0 0 0 0 0 0 0 0 0 0 None
0 25kA1 31.5kA2 40kA3 50kA
1 Manual ESW with Electrical Interlock2 Manual ESW without Electrical Interlock3 Electrical ESW with Electrical Interlock4 Electrical ESW without Electrical Interlock
1 3.3kV2 6.6kV3 10kV4 11kV5 20kV6 25kVA 4.16kVB 7.2kVC 13.8kVD 15kVE 15.5kVF 25.8kV
1 AC/DC110V2 AC/DC220V3 DC24V4 DC30V5 DC36V6 DC48V7 DC60V8 AC/DC125V9 AC/DC230-240V
1 Castell2 Fortress3 Ronis
1 1 Key + 1 Lock - 1 Key trapped Earthing Switch Open 2 1 Key + 1 Lock - 1 Key released Earthing Switch Open 3 2 Keys + 2 Locks - 1 Key trapped & 1 Key released Earthing Switch Open4 2 Keys + 2 Locks - 2 Keys trapped Earthing Switch Open 5 2 Keys + 2 Locks - 2 Keys released Earthing Switch Open
1 1 Key + 1 Lock - 1 Key trapped Apparatus in Test Position2 1 Key + 1 Lock - 1 Key released when the Apparatus in Test Position3 2 Keys + 2 Locks - 1 Key trapped & 1 Key released Apparatus in Test Position4 2 Keys + 2 Locks - 2 Keys trapped Apparatus in Test Position5 2 Keys + 2 Locks - 2 Keys released when the Apparatus in Test Position
1 Shutter Interlock to prevent manual activation1 Emergency trip push button2 Breaker compartment heater3 Emergency trip + Heater
1 Marine Version (Handrail + Door Stopper)2 IP43 Earthing Switch Apperture Cover3 Marine Version + IP43 Cover
1 With VT truck (w/o VT) on Lower Compartment2 With VT truck (w/ VT) on Lower Compartment3 With VT truck (w/o VT) on Apparatus Compartment4 With VT truck (w/ VT) on Apparatus Compartment
Seco
Bloc
BC
and
BV
Che
cklis
t
25
IEEE OEM Modules 5 - 15kV for SecoVac Vacuum Circuit Breakers
For more information on GE’s SecoBloc IEEE OEM Modules, please refer to the following publications:• DEA-612: SecoBloc IEEE OEM Modules Brochure
• DEQ-211: SecoBloc IEEE OEM Modules Factsheet
• DEH-50002: SecoBloc IEEE OEM Modules User Manual
• DEH-50001: SecoVac IEEE VCB User Manual
Specifications 1200/31.5 1200/40 2000/40 3000/40Rated Current (A) 1200 1200 2000 3000
Rated Voltage (kV) 4.76 / 8.25 / 15 4.76 / 8.25 / 15 4.76 / 8.25 / 15 4.76 / 8.25 / 15
Rated Power Frequency (1 min)Phase to Phase and to Earth (kV) 36 36 36 36
Between Isolating Distance (kV) 36 36 36 36
Rated Lighting Impulse (1.2/50μs)Phase to Phase and to Earth (kV) 95 95 95 95
Between Isolating Distance (kV) 95 95 95 95
Rated Frequency (Hz) 60 60 60 60
Rated Short Time Withstand (kA) 31.5 40 40 40
Rated Peak Value Withstand Current (kAp) 82 104 104 104
Rated Duration Time for Short-circuit (s) 2 2 2 2
IP Level for Door NEMA 250 Type 1 /Type 1+2 (IEC IP4X)
DimensionsWeight (kg / lbs) 350 / 772 350 / 772 362 / 796 382 / 840
Phase to Phase Distance (mm / in) 254 / 10 254 / 10 254 / 10 275/10.8
A (mm/in) 914 / 36.0 914 / 36.0 914 / 36.0 914 / 36.0
B (mm/in) 1100 / 43.3 1100 / 43.3 1100 / 43.3 1100 / 43.3
C (mm/in) 947 / 38.3 934 / 36.8 934 / 36.8 934 / 36.8
D (mm/in) 1025 / 40.4 1012 / 39.8 1012 / 39.8 1012 / 39.8
E (mm/in) 1205 / 47.4 1205 / 47.4 1205 / 47.4 1205 / 47.4
F (mm/in) 1283 / 50.5 1283 / 50.5 1205 / 47.4 1205 / 47.4
Technical Data
Front/Side View
1205
1283
914
1100
947
468
275
1025
1205
1283
914
1100
947
468
275
1025
914
1100
1205
1283
483
310
934
1012914
1100
1205
1283
483
310
934
1012
1200/31.5kA or 1200/40kA
A AC CD D
E EF F2000/40kA
275mm 10.80in
468mm 18.40in
310mm 12.20in
483mm 19.02in
To view the entire Medium Voltage Seco Product Offering please visit: www.geindustrial.com
Seco Cube Seco RMU Seco Gear SecoBloc SecoVac
*SecoBloc is a trademark of General Electric Company
Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions.
4.15 DEA-605
Imagination at work
GE Industrial Solutions 41 Woodford Avenue Plainville, CT 06062 www.geindustrial.com