This presentation is illustrated the existing short circuit value in PEA power system.
Citation preview
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 1/24
Current Status and Fault Issues inPEA’s Network
Wirote Buaklee
Deputy Director of System Planning Department
Provincial Electricity Authority, Thailand
September 29, 2015
Joint TNC-CIGRE & IEEE-PES Seminar
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 2/24
Topics
I. Overview of PEA Power System
II. Overview of PEA Fault Calculation
III. Current Status of Fault Level
IV. Problem and Issue on Fault Current
2
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 3/24
I. PEA Power System Overview
Substation 534 substations
Sub-Transmission 11,414 ckt-km
Distribution 296,809 ckt-km
Control Center 13 centers
PEA 2014
3
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 4/24
No. of Customers 17,679,995 Cust.
Energy Sale 116,501 M-unit
Electrified Village(%) 99.98
4
PEA Service Information
PEA 2014
Peak Demand 17,724 MW
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 5/24
SAIFI : 6.46 occ/cust/yr
SAIDI : 217.89 min/cust/yr
LOSSES : 5.46 %
5
PEA Service Information
PEA 2014
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 6/24
6
Current Status of SPPs in PEA System
Area Project SellingPower(MW)
InstalledCapacity
(MW)
North
5
191.00
202.50
Northeast 10 394.50 485.40
Central
41
2,664.30
4,082.43
South 3 220.20 253.56
Total 59 3,450.00 5,023.89
Sept 2015
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 7/24
Fuel Type
Connected Non-Connected
Project Power (MW) Project Power (MW)
Biomass 126 775 123 725
Biogas 127 222 97 183
Solar 251 922 176 964
Waste 18 43 38 206
Wind 6 9.65 8 50
Hydro 6 1.2 9 14
Other 2 4.5 2 18
Total 536 1,977 453 2,160 7
Current Status of VSPPs in PEA System
Source: Alternative Energy Encouragement Division on Sept 2015
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 8/24
Status of VSPPs Interconnected to PEA System
39.2%
11.2%
46.6%
2.2%
0.5% 0.1%
0.2%
Solar922 MW
Biogas222 MW
Biomass775 MW
8
Wind 9.65 MW
OTHERS 4.5 MWWaste 43 MW
Hydro 1.2 MW
Status : Sept 2015
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 9/24
II. Overview of PEA Fault Calculation
• Objective: equipment selection and protection
coordination.
• Annually Calculation
• Use IEC60909-2001 Method with “c-voltage
factor” equal to “1.0”
• Get EGAT driving point data from “System
Operation Department” as a source of PEA
power system
• Only Initial symmetrical short circuit current:
Ik” value will be calculated
• In the future, Peak short circuit current: Ip will
also be calculated
9
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 10/24
Example of PEA Short Circuit Report
10
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 11/24
Typical Configuration Between EGAT and PEA
• 22/33kV Control Station
• 115kV Substation
11
EGAT
PEA 22-33 kV
EGAT
PEA 115 kV
PEA Substation
115 kV Customer
G 115 kV SPP
G VSPP
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 12/24
PEA Standard of Rated Short Circuit
12
Type VoltageLevel
Breaking Current(kA_rms)
Making Current(kA_peak)
Circuit Breaker
115
31.5/40
80/100
22/33
25
63
LBS/ RCS
22
12.5
31.25
33 10 25
Recloser
22
12
31.25*
33 10 25*
RMU 22/33 16 40
* Assumed value due to lack of data
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 13/24
III. Current Status of Fault Level: All PEA Service
Area
13
3-Phase Fault(kA) Max Min
115 kV 38.46 0.86
22/33 kV
20.06
2.20
532
2 0
315
5513
0
100
200300
400
500
600
<50% 50-80% ≥80%
N o . o f S u
b s t a t i o n
Isc/Icb
22 kV
115 kV
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 14/24
Current Status of Fault Level: Northern Region
14
3-Phase Fault(kA) Max Min
115 kV 22.46 0.86
22 kV
12.10
2.52
108
0 0
60
2 00
20
4060
80
100
120
<50% 50-80% ≥80%
N o . o f S u
b s t a t i o n
Isc/Icb
22 kV
115 kV
Nakhon Sawan Area
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 15/24
Current Status of Fault Level: Northeastern Region
15
3-Phase Fault(kA) Max Min
115 kV 18.05 1.39
22 kV
13.23
2.68
102
2 0
59
1 00
20
40
60
80
100
120
<50% 50-80% ≥80%
N o . o f S u
b s t a t i o n
Isc/Icb
22 kV
115 kV
Nakhon Ratchasima Area
Udon Thani Area
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 16/24
Current Status of Fault Level: Central Region
16
3-Phase Fault(kA) Max Min
115 kV 38.46 1.39
22 kV
20.06
3.93
223
0 0
133
52
11
0
50
100
150
200
250
<50% 50-80% ≥80%
N o . o f S u
b s t a t i o n
Isc/Icb
22 kV
115 kV
Rangsit Area
Ayutthaya AreaSaraburi Area
Amata Area
Ao Phai Area
Leamchabang Area
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 17/24
Current Status of Fault Level: Southern Region
17
3-Phase Fault(kA) Max Min
115 kV 36.72 1.44
22/33 kV
10.77
2.20
99
0 0
63
0 20
20
40
60
80
100
120
<50% 50-80% ≥80%
N o . o f S u
b s t a t i o n
Isc/Icb
33 kV
115 kV
Ratchaburi Area
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 18/24
IV. Problem and Issue on Fault Current
18
• 13 substations have a high fault level
• PEA has no remedial actions/plans to mitigate the problem
• High fault current will reduce both security and quality of supply
• There are a lot of approaches to control the short circuit current
• Network Reconfiguration
• Bus Splitter
• Install Fault Current Limiter (FCL) such as Current Limiting Reactor (CLR),
Is-Limiter, Solid State FCL(SSFCL) Superconducting FCL(SCFCL) and
Magnetic FCL (MFCL)etc.
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 19/24
The Status of FCL Technologies
19•
A Neumann, “Application of Fault Current Limiters”, Department for Business Enterprise & RegulatoryReform(BERR), 2007.
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 20/24
Thank you
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 21/24
Characteristics of short-circuit currents
21
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 22/24
Characteristics of short-circuit currents
22
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 23/24
Characteristics of short-circuit currents
23
7/17/2019 Current Status and Fault Issues in PEA's Networks
http://slidepdf.com/reader/full/current-status-and-fault-issues-in-peas-networks 24/24
Characteristics of short-circuit currents