Condensing Unit30/10/2011 / All data subject to change.Compressor Selection: Condensing UnitsInput ValuesCooling capacity 10kW SeriesStandard Refrigerant R134a Reference temperature Dew point temp. Evaporating SST-24C

Ambient temp. 32C Suct. gas superheat 10K

Power supply400V-3-50Hz

Useful superheat 100% Capacity Control 100%

Application Limits

OutputUnit typeLH135/LH135/LH135/LH135/

4J-22.2Y-40P4J-13.2Y-40P4H-25.2Y-40P4H-15.2Y-40P

Cooling capacity

Evaporator capacity9.28 kW

9.28 kW9.84 kW

9.84 kW10.79 kW

10.79 kW11.97 kW

11.97 kW

Power input* Current (400V) Voltage range Mass flow Condensing SDT Liquid subcooling Operating mode5.15 kW

13.03 A

380-420V

232 kg/h

36.3 C

2.67 K Standard4.98 kW

11.45 A

380-420V

246 kg/h

36.4 C

2.68 K Standard5.97 kW

16.31 A

380-420V

271 kg/h

37.0 C

2.75 K Standard6.18 kW

12.71 A

380-420V

302 kg/h

37.4 C

2.81 K Standard

*Power input compressor, power input fan see ''T. Data''