http://slidepdf.com/reader/full/compatibility-20rule 1/6
Centro de Competencia Técnica – Sistemas & Comunicaciones
Unity Pro v4.1 - Compatibility rules – Unity Pro and application version
Version X.Y applications: application version corresponding to the processor chosen in the Unity Pro configuration screen(project creation step). • Unity Pro V4.1 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50, V2.60, V2.70; Modicon
M340 V1.0, V2.0, V2.1• Unity Pro V4.0 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50, V2.60; Modicon M340 V1.0,
V2.0• Unity Pro V3.1 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50; Safety Quantum V1.0;
Modicon M340 V1.0• Unity Pro V3.0 handles: Premium/Quantum V2.00 (V2.21), V2.30, V2.40; Modicon M340 V1.0
• Unity Pro V2.3 SP1 handles: Premium/Quantum V2.00 (V2.21) and V2.30• Unity Pro V2.2 handles: Premium/Quantum V2.00 (V2.21) and V2.00 (V2.21) MFB if MFB (Motion Function Block) option
was set up with Unity Pro V2.2• Unity Pro V2.1 handles: Premium/Quantum V2.00• Unity Pro V2.0 handles: Premium/Quantum V2.00
2.1. Table 1 XEF Files on the PC
XEF Files on the PC
Open with Unity Pro
V2.0
Open withUnity Pro
V2.1
Open withUnity Pro
V2.2
Open withUnity Pro
V2.3 SP1
Open with Unity Pro
V3.0
Open with Unity Pro
V3.1
Open withUnity Pro
V4.0
Open withUnity Pro
V4.1
Premium / QuantumV2.00 application*
YES (1) YES (1) YES (1) YES YES YES YES YES
Premium / QuantumV2.30 application (1)
NO NO NO YES YES YES YES YES
Premium / QuantumV2.40 application
NO NO NO NO YES YES YES YES
PremiumV2.50 application
NO NO NO NO NO YES YES YES
Premium / QuantumV2.60 application
NO NO NO NO NO NO YES YES
Premium / QuantumV2.70 application
NO NO NO NO NO NO NO YES
Modicon M340V1.0 application
NO NO NO NO YES YES YES YES
Modicon M340V2.0 application
NO NO NO NO NO NO YES YES
Modicon M340
V2.1 application NO NO NO NO NO NO NO YES
Quantum safetyV1.0 application
NA NA NA NA NA YES NA YES
Quantum safetyV2.0 application
NA NA NA NA NA NO NA YES
NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)* Application version corresponds to the choice of PLC in the Unity Pro configuration screen during the creation of a project (V2.00,V2.30 …)See Unity Pro, application and PLC OS compatibility (Table 7). Restriction: (1) If there are MFBs in the application, these ones are not usable; errors are generated during the build phase, except for UnityPro V2.2 with MFB option.
1Título Documento
Jorge Moreno López – Fecha
8/6/2019 Compatibility 20rule
http://slidepdf.com/reader/full/compatibility-20rule 2/6
Centro de Competencia Técnica – Sistemas & Comunicaciones
2.2. Table 2 STA Files on the PC
STA Files on the PC
Open with Unity Pro
V2.0
Open withUnity Pro
V2.1
Open withUnity Pro
V2.2
Open withUnity ProV2.3 SP1
Open withUnity Pro
V3.0
Open with Unity Pro
V3.1
Open withUnity Pro
V4.0
WithUnity Pro
V4.1
Premium / QuantumV2.00 application
YES(1) YES (2) YES (2) YES (3) YES YES YES YES
Premium / QuantumV2.30 application
NO NO NO YES YES YES YES YES
Premium / QuantumV2.40 application
NO NO NO NO YES YES YES YES
PremiumV2.50 application
NO NO NO NO NO YES YES YES
Premium / QuantumV2.60 application
NO NO NO NO NO NO YES YES
Premium / Quantum
V2.70 application NO NO NO NO NO NO NO YES
Modicon M340V1.0 application
NO NO NO NO YES YES YES YES
Modicon M340V2.0 application
NO NO NO NO NO NO YES YES
Modicon M340V2.1 application
NO NO NO NO NO NO NO YES
Quantum safetyV1.0 application
NA NA NA NA NA YES NA YES
Quantum safetyV2.0 application
NA NA NA NA NA NO NA YES
NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)
Restrictions: (1) Unity Pro V2.0 does not allow to open STA other than those generated with Unity Pro V2.0(2) When application generated doesn’t contain MFB functions, except for Unity Pro V2.2 with MFB option(3) When application contains writing on read only variable, the STA is not opened, the corrections must be done before creatingthe STA
2.3. Table 3: STU Files on PC
STU Files on PC
Open withUnity Pro
V2.0
Open withUnity Pro
V2.1
Open withUnity Pro
V2.2
Open withUnity ProV2.3 SP1
Open withUnity Pro
V3.0
Open withUnity Pro
V3.1
Open withUnity Pro
V4.0
WithUnity Pro
V4.1
Application generatedwithUnity Pro V2.0
YES NO NO NO NO NO NO NO
Application generatedwithUnity Pro V2.1
NO YES YES NO NO NO NO NO
Application generatedwithUnity Pro V2.2
NO NO YES (1) NO NO NO NO NO
Application generatedwithUnity Pro V2.3 SP1
NO NO NO YES NO NO NO NO
Application generated
withUnity Pro V3.0 NO
NO
NO
NO
YES
NO
NO
NO
2Título Documento
Jorge Moreno López – Fecha
8/6/2019 Compatibility 20rule
http://slidepdf.com/reader/full/compatibility-20rule 3/6
Centro de Competencia Técnica – Sistemas & Comunicaciones
Application generatedwithUnity Pro V3.1
NO NO NO NO NO YES NO NO
Application generatedwithUnity Pro V4.0
NO NO NO NO NO NO YES NO
Application generated
withUnity Pro V4.1
NO NO NO NO NO NO NO YES
Restriction: (1) When application contains MFB it can be opened only when MFB option is set up with Unity Pro V2.2
2.4. Table 4: PLC => PC Transfer
PLC => PC Transfer With
Unity ProV2.0
WithUnity Pro
V2.1
WithUnity Pro
V2.2
WithUnity ProV2.3 SP1
WithUnity Pro
V3.0
WithUnity Pro
V3.1
WithUnity Pro
V4.0
WithUnity Pro
V4.1
Premium / QuantumV2.00 application
YES (1) YES (1) YES (2) YES YES YES YES YES
Premium / QuantumV2.30 application
NO NO NO YES YES YES YES YES
Premium / QuantumV2.40 application
NO NO NO NO YES YES YES YES
PremiumV2.50 application
NO NO NO NO NO YES YES YES
Premium / QuantumV2.60 application
NO NO NO NO NO NO YES YES
Premium / QuantumV2.70 application
NO NO NO NO NO NO NO YES
Modicon M340V1.0 application
NO NO NO NO YES YES YES YES
Modicon M340V2.0 application
NO NO NO NO NO NO YES YES
Modicon M340V2.1 application
NO NO NO NO NO NO NO YES
Quantum safetyV1.0 application
NA NA NA NA NA YES NA YES
Quantum safety
V2.0 application
NA NA NA NA NA NO NA YES
NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)
Restrictions: (1) Transfer not possible when application contains MFB(2) Exception: the application switches to "V2.00 MFB Application" level when MFB option is set up with Unity Pro V2.2
2.5. Table 5: PC => PLC Transfer
PC => PLC Transfer(1)
WithUnity Pro
V2.0
WithUnity Pro
V2.1
WithUnity Pro
V2.2
WithUnity ProV2.3 SP1
WithUnity Pro
V3.0
WithUnity Pro
V3.1
WithUnity Pro
V4.0
WithUnity Pro
V4.1
Premium / QuantumV2.00 application
YES YES YES YES YES YES YES YES
3Título Documento
Jorge Moreno López – Fecha
8/6/2019 Compatibility 20rule
http://slidepdf.com/reader/full/compatibility-20rule 4/6
Centro de Competencia Técnica – Sistemas & Comunicaciones
Premium / QuantumV2.30 application
NO NO NO YES YES YES YES YES
Premium / QuantumV2.40 application
NO NO NO NO YES YES YES YES
PremiumV2.50 application NO NO NO NO NO YES YES YES
Premium / QuantumV2.60 application
NO NO NO NO NO NO YES YES
Premium / QuantumV2.70 application
NO NO NO NO NO NO NO YES
Modicon M340V1.0 application
NO NO NO NO YES YES YES YES
Modicon M340V2.0 application
NO NO NO NO NO NO YES YES
Modicon M340V2.1 application
NO NO NO NO NO NO NO YES
Quantum safetyV1.0 application
NA NA NA NA NA YES NA YES
Quantum safetyV2.0 application
NA NA NA NA NA NO NA YES
NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)
Restriction: (1) See application compatibility with the OS table
2.6. Table 6: Online modification
Online modification With
Unity ProV2.0
WithUnity Pro
V2.1
WithUnity Pro
V2.2
WithUnity ProV2.3SP1
WithUnity Pro
V3.0
WithUnity Pro
V3.1
WithUnity Pro
V4.0
WithUnity Pro
V4.1
Premium / QuantumV2.00 application
YES YES YES (1) YES (2) YES (2) YES (2) YES YES
Premium / QuantumV2.30 application
NO NO NO YES YES YES YES YES
Premium / QuantumV2.40 application
NO NO NO NO YES YES YES YES
PremiumV2.50 application
NO NO NO NO NO YES YES YES
Premium / QuantumV2.60 application
NO NO NO NO NO NO YES YES
Premium / QuantumV2.70 application
NO NO NO NO NO NO NO YES
Modicon M340V1.0 application
NO NO NO NO YES YES YES YES
4Título Documento
Jorge Moreno López – Fecha
8/6/2019 Compatibility 20rule
http://slidepdf.com/reader/full/compatibility-20rule 5/6
Centro de Competencia Técnica – Sistemas & Comunicaciones
Modicon M340V2.0 application
NO NO NO NO NO NO YES YES
Modicon M340V2.1 application
NO NO NO NO NO NO NO YES
Quantum safetyV1.0 application NA NA NA NA NA YES NA YES
Quantum safetyV2.0 application
NA NA NA NA NA NO NA YES
NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)
Restrictions: (1) Exception: When MFB option is set up with Unity Pro V2.00 the application switches to "V2.00 MFB" level(2) Adding a new EFB Type needs to update the library in the project (rebuild all)
2.7. Table 7 Unity Pro application and PLC OS compatibility
Unity Pro,
application and PLC OScompatibility
PREMIUM
minimum OSversion
QUANTUM
minimum OSversion
QUANTUM
SAFETYminimum OS
version
M340
minimum OSVersion
2.70 2.70 2.00 2.10
2.60 2.60 x 2.00
2.50 (2) x 1.00 x
2.40 2.40 x 1.00
2.30 2.30 x x
2.21 (1) x x x
2.00 MFB x x x
Unity Pro V4.1
2.00 2.00 x x
PREMIUM QUANTUM QUANTUMSAFETY
M340
2.60 2.60 QuantumSafetyNot supported
2.00
2.50 (2) x x x
2.40 2.40 x 1.00
2.30 2.30 x x
2.21 (1) x x x
2.00 MFB x x x
Unity Pro V4.0
2.00 2.00 x x
PREMIUM QUANTUM QUANTUMSAFETY
M340
2.50 (2) x 1.00 x
2.40 2.40 x 1.00
2.30 2.30 x x
2.21 (1) x x x
2.00 MFB x x x
Unity Pro V3.1
2.00 2.00 x x
PREMIUM QUANTUM QUANTUMSAFETY
M340
2.40 2.40 x 1.00
2.30 2.30 x x
Unity Pro V3.0
2.21 (1) x x x
5Título Documento
Jorge Moreno López – Fecha
8/6/2019 Compatibility 20rule
http://slidepdf.com/reader/full/compatibility-20rule 6/6
Centro de Competencia Técnica – Sistemas & Comunicaciones
2.00 MFB x x x
2.00 2.00 x x
PREMIUM QUANTUM QUANTUMSAFETY
M340
2.30 2.30 x x
2.21 (1) x x x
2.00 MFB x x x Unity Pro V2.3 SP1
2.00 2.00 x x
PREMIUM QUANTUM QUANTUMSAFETY
M340
2.21 (1) x x x
2.00 MFB x x x Unity Pro V2.2
2.00 2.00 x x
PREMIUM QUANTUM QUANTUMSAFETY
M340
Unity Pro V2.1 2.00 2.00 x x
PREMIUM QUANTUM QUANTUM
SAFETY
M340
Unity Pro V2.0 2.00 2.00 x x
The OS version corresponds to the minimum version required to execute a functional level of the application. Higher OS versionsensure compatibility with existing applications (for example: an application version V2.00 generated by Unity Pro V2.20 can beexecuted by a PLC V2.30).
(1) Only TSX P 57 5634 M.(2) Only TSX H57 24 M and TSX H57 44 M
6Título Documento
Jorge Moreno López – Fecha