3. WIRING DIAGRAM - iPFC
PROGRAMMING GUIDEPower Factor Controller (iPFC)
support@elmeasure.comPh: +91 80 32904489
www.elmeasure.com
1. UNIQUE FEATURES
STAR (Wye)/ DELTA Programmable.
Auxiliary supply of 180 - 300V AC/DC.
PT ratio / CT ratio programmable including CT secondary
3 phase measurement
Capacitor value programmable
6/8/12 stages optional
Automatic or Manual Control
Four Quadrant Operation
Fault Detection
Intelligent Power Factor Controlling based on the capacitor bank
switching history
PG/PFC/V5/0117
2. KEY FUNCTIONS
Key In SET (Programming) mode In RUN (Measurement) mode
Right To select the value and to accept the value
NO ACTION
DOWN To edit the value/system typesdownward in edit mode and scrollthrough the parameters.
To scroll pages in DOWNWARDdirection and view differentparameters
UP To edit the value/system type up-ward in edit mode and scroll through the parameters.
To scroll pages in upward direction and view different parameters.
Star
co
nn
ecti
on
(3E
)3P
has
e 4w
ire
syst
emD
elta
co
nn
ecti
on
(2E
)3P
has
e 3
wir
e sy
stem
AUX
S1 S2
S1 S2
S1 S2
R
Y
B
N
LOADRECEIVEDDELIVEREDLINE
RS 485
AUX
S1 S2
S1 S2
LOADRECEIVEDDELIVEREDLINE
RS 485
Step Actions Display Reads Range/Options/Comments
1 Press RIGHT & UP keys together to enter SETUP
4. ENTERING CONFIGURATION (SETUP) MODE To configure the setup parameters in PFC meter through front panel keys, the
following steps can be followed.
2 Press DOWN key (Password)
with first digit “0” blinking.
3
(default/factory set).
Press UP key once to increment the first digit to “1”.
4 Press RIGHT key four times to accept the password.
(Displays last programmed type)
5 Press RIGHT key to selectrequired system type
(selected mode blinks)
If any other password is already set move up and down key to set the right password
Defines the power system configuration.Options: STAR /DELTA
6 Press UP/DOWN key to select
7 Press RIGHT key to accept
8 Press DOWN key. (PT Primary)
(415.0 -default/factory set)
9 Press RIGHT key to setthe PT primary value
First digit blinking, can be edited using UP/DOWN key.
(PT Primary)
V - A - Hz - W - PF - VAR - Wh
C1 C2 C3 C4 C5 C6 C7 C8
C9 C10 C11 C12
INTELLIGENT PFC
PFC12 08 06
CLR PRG
3Ø Measurements
R
Y
B
N
NVBVYVRABAYARS1 S2 S1 S2 S1 S2
NVBVYVRABAYARS1 S2 S1 S2 S1 S2
Control Wiring : Control Wiring for Capacitor Switching Section
1 2 3 4 5 6 7 8 9
COM
1 2 3 4 5 6 7 8
K8 K6 K4 K2
K7 K5 K3 K1
FreewheelingDiode 1N4007
DC supplyTo Contactor coil
AC supplyTo Contactor coil
RC Snubber R: 330 /3W.c:0.1 F/1kV.
UTILITYMETER
iPFC CAPACITORPANEL
INCOMMER DIAGRAM - iPFC
iPFC
Ωμ
+
-
HO & Unit -1 :
Plot NO.: 47-P, Hardware Park, Huvinayakanahalli KIADB Jala hobli, Bengaluru North, Yelahanka Taluk, Bengaluru District, Karnataka - 562 149 INDIA.
Unit -2 : Goutham Garden, No.4, Veerapandi, Coimbatore - 641 019 INDIAT : 0422 2697200. TF : 0422 2695200. E : contactcbe@elmeasure.com
Sales Offices : BENGALURU CHENNAI COIMBATORE MUMBAI DELHI HYDERABAD USA UAE
Press DOWN key Over current. Range: 0.050 to 99KA
25 Press DOWN key Under voltage. Range: 20 to 999KV
30
26
Press DOWN key Under current. Range: 0.050 to 99KA
27
Press DOWN key Over harmonics. Range: 1% to 200%
28
Press DOWN key Alarm time delayRange: 3 to 99 seconds
29
Press DOWN key Capacitor VAR value for C1.
Press RIGHT key to setthe Capacitor VAR value for C1
First digit blinking can be edited using UP/DOWN key.
31
32
Second digit blinking, can be edited using UP/DOWN key. Press RIGHT key to accept the edited value. Continue the same method till fourth digit.
Press RIGHT key to accept the edited value for first digit.
Range: 500VAR to 9999MVAR
39
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C7
40
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C8
41
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C9
42
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C10
43
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C11
47 Press DOWN key 2nd Analog input parameter
48 Press DOWN key Range :0.001 to 9999M
44
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C12
45 Press DOWN key 1st Analog input parameter
46 Press DOWN key Range :0.001 to 9999M
49 Press DOWN key Defines the baud rate. Option : 1200,2400, 4800, 9600, 19.20k
(baud rate).Communication speed. (9600 -default/factory set)
50 Press DOWN key Internal communication error check EUEn (even)/odd(odd)/no(no parity) Comment: Can change the option using UP & DOWN keys.
51 Press DOWN key Defines the (ID) communications identification number. Option: 1-247
(Device ID)
52 Press DOWN key Caution : If password other than the default or user defined is used, meter will reject programming.CAUTION: Password can only be reset and recalibrated at factory.
Range:1000 -9999. Password user definable.
14 Press DOWN key
(5.000 -default/factory set)Repeat steps 9 to 11 to change the settings.
Range: 0.5A to 6A. If value set is above this limit, it returns to the maximum CT sec value acceptable.
15 Press DOWN key
(Method of VA Selection).
Arithmetic (Arith), Vector harmonics(UEC.H). Vector (VECtor) can be selected using UP/DOWN key.
16 Press DOWN key
(no.of relays)
Range: 1 to 12 (Depends on the No. of stages)
17 Press DOWN key
(Control type)
Auto/Manual
10 Press RIGHT key to accept the edited value for first digit. Second digit blinking, can be
edited using UP/DOWN key. Press RIGHT key to accept the edited value. Continue the same method till fourth digit.
(PT Primary)Program Range for PT Primary : 100V to 999kV
11 Press RIGHT key.
Decimal point blinking. Can be set at appropriate location using UP/DOWN key. Ascertain the correct scale (Kilo/Mega/Giga) is selected. Kilo/Mega/Giga is placed on the right hand side of the display as K/M/G. Press RIGHT key to accept the edited value.
(PT Primary)Eg: To set 11.00kVSet first four digits (1100) as explained above press UP/DOWN key to place decimal point at appropriate location USE UP/DOWN KEY Letter K/M/G will indicate the Kilo/Mega/Giga.
12 Press DOWN key to go to the next parameter.
(PT Secondary) (415.0 - default/factory set) Follow the procedure as described in steps 9 to 11.
Range: 50V to 550V. If value set is above this limit, display returns to the maximum PT sec value acceptable.
13 Press DOWN key
(CT Primary)(5.000 -default/factory set) Repeat steps 9 to 11 to change the settings.
Program Range for CT Primary: 0.5A to 99kA
33
Decimal point blinking. Can be set at appropriate location using UP/DOWN key. Ascertain the correct scale (Kilo/Mega) is selected. Kilo/Mega is placed on the right hand side of the display as K/M. Press RIGHT key to accept the edited value.
Press RIGHT key. Eg: To set 11.00KVAR Set first four digits (1100) as explained above press UP/DOWN key to place decimal point at appropriate location. Use UP/DOWN KEY. Letter K/M will indicate the Kilo/Mega.
34
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C2
35
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C3
36
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C4
37
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C5
38
Follow the procedure as described in steps 30 to 32.
Press DOWN key Capacitor VAR value for C6
53 Starting current value to be displayed in the meter Range: (0.2 to 10 % of full scale)
Press DOWN key
Press DOWN key Relay on time. Range: 4 to 999 seconds
Press DOWN key Relay off time. Range: 4 to 999 seconds
Press DOWN key Discharge time. Range: 4 to 999 seconds
19 Press DOWN key PF limit – Capacitive (leading PF). Range: 0.800 to 0.999
20
21
22
Press DOWN key Average time. Range: 2 to 200 seconds
Press DOWN key Over voltage. Range : 48 to 999KV
23
24
18 Press DOWN key PF limit – inductive(lagging PF).Range: 0.800 to 0.999
C1 - ON
C2 - ON
C3 - ON
C4 - ON
C5 - ON
C6 - ON
C7 - ON
C8 - ON
C9 - ON
C10 - ON
C11 - ON
C12 - ON
Capacitor Bank 1 ON / Relay 1 ON status
Capacitor Bank 2 ON / Relay 2 ON status
Capacitor Bank 3 ON / Relay 3 ON status
Capacitor Bank 4 ON / Relay 4 ON status
Capacitor Bank 5 ON / Relay 5 ON status
Capacitor Bank 6 ON / Relay 6 ON status
Capacitor Bank 7 ON / Relay 7 ON status
Capacitor Bank 8 ON / Relay 8 ON status
Capacitor Bank 9 ON / Relay 9 ON status
Capacitor Bank 10 ON / Relay 10 ON status
Capacitor Bank 11 ON / Relay 11 ON status
Capacitor Bank 12 ON / Relay 12 ON status
10. Display of Parameters:
Power Factor Y Phase
Power Factor B PhaseAverage Power Factor
VAr R PhaseTotal VAR
VAr Y PhaseVoltage line to line
Current RPhaseVoltage line to Neutral
VAr B PhaseVoltage RY Phase
Under VoltageVoltage YB Phase
Over VoltageVoltage BR Phase
Over CurrentVoltage R phase
Over CompensationFrequency
Under CompensationWatts Total
Reverse AmpsPower Factor
Over HarmonicsPower Factor R Phase
Under CurrentCurrent Average
Display Meaning Meaning Display
9. LED INDICATION
LED Status
K - ON
M - ON
K & M - ON
Meaning
Kilo
Mega
Giga
Direct readingK & M - OFF
Lag/Minus
Communication ON
Alarm On
- - ON
- ON
- ON
8. Manual Mode:Press UP and DOWN Keys together, and 'CLEAr' (Clear) is shown on the display. Enter the Password (default password is 1000. Set up and clear has the same password) and it will display “CLr.I”. Press DOWN Key and meter displays “Manual”. Once manual selected it will display C1 OFF or C1.On (depends on whether the capacitor is ON or OFF). Press RIGHT key to make it ON or OFF. Continue this for other no. of relays programmed. Once the required no. of relays are switched ON or OFF display will prompt to “CLEAr.”or Manual . When display prompts to CLEAr press DOWN key and 'n' will display and Press the RIGHT key to come out.
7. Enabling and Disabling of Auto scrolling:Enabling auto scrolling: Press UP key continuously for 5 seconds or until display shows EnbL Au for upward scrolling. Press Down key continuously for 5 seconds or until display shows EnbL Au for downward scrolling.
Disabling auto scrolling: Press any key (RIGHT/UP/DOWN), display show dSbL Au and returns to normal mode.
6. Clearing the Integrator:To Clear parameters from the front panel, Press UP and DOWN Keys together, and 'CLEAr' (Clear) is shown on the display. Enter the Password (default password is 1000. Set up and clear has the same password) and it will display “CLr.I”. Press UP / DOWN Key for selecting CLr.I (Integ Clear). Once the parameter to be cleared is selected it will prompt to 'y' or 'n'. Press UP and DOWN key for changing 'y' or 'n' and Press the RIGHT key to do the operation.
5. The List of parameters can be configured and the range is given below
Default setup Range / Options
UEC.H Arith (Arithmetic) / Vector/ VEC.H (vector harmonics)
VA selection (UA)6
Auto/ManualAutoControl type (C.t)8
10
5.000 0.5A - 99kACT Primary (CP)45.000 0.5A - 6ACT SECondary (CS5
Sl.No. Parameter
STAR STAR/ DELTAConnection mode(EL)1
415.0 100V- 999kVPT Primary (PP)2
415.0 50V - 550VPT Secondary (PS)3
Average PF page to be displayed in the meter. Options: Enable/Disable
54 Press DOWN key
If “n”(no) is selected then Meter enters into RUN mode without memorizing any edited Values in the setup
Display returns to Run mode.
Once the required parameter is programmed press the DOWN key continuously till it reaches SAVE page directly.
60 Press DOWN key
61 Press RIGHT key to store the changes done
Under Compensation condition to be displayed in the meter. Options: Enable/Disable
55 Press DOWN key
Over Compensation condition to be displayed in the meter. Options: Enable/Disable
56 Press DOWN key
Under Amps condition to be displayed in the meter. Options: Enable/Disable
57 Press DOWN key
Over Amps condition to be displayed in the meter. Options: Enable/Disable
58 Press DOWN key
59 Press DOWN key Other warnings to be displayed in the meter. Options: Enable/Disable
12.000 1-6/8/12No.of Relays (nr)7
0.950 0.800 to 0.999PF lag(Lg)9
Dimension Bezel: 96 x 96 mm (Depth 50mm behind Bezel)
Panel Cutout:+2 +290 x 90 mm-0 -0
11. Mechanical Specification:
+290 mm-0
12
13
14
15
16
17
18
19
20
22
11
21
Over current(o.A)
Under current(u.A)
Over Harmonics(O.H)
Alarm delay (A.d)
6.000
0.200
200.0
3.000
0.050 to 99.00 KA
0.050 to 99.00 KA
1 to 150%
3 to 99 seconds
Switch OFF time(oF) 20.00 4 to 999 seconds
Discharge time(t.d) 50.00 4 to 999 secondsAverage Time(t.A) 15.00 2 to 200 seconds
Over voltage(o.u) 498.0 48 to 999KV
Under voltage(uu) 48.00 20 to 999KV
Capacitance(C2) 1000.0 500 VAR to 9999 MVAR
Switch ON time(on) 20.00 4 to 999 seconds
Capacitance(C1) 1000.0 500 VAR to 9999 MVAR (default 1000 VAR = 1 kVAR)
0.950 0.800 to 0.999PF lead(Ld)
Capacitance(C4
Capacitance(C5)
Capacitance(C6)
Capacitance(C7)
Capacitance(C8)
Capacitance(C9)
Capacitance(C10)
Capacitance(C11)
Capacitance(C12)
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
24
25
26
27
28
29
30
31
32
Analog input(An) disA Disable Analog input33Analog input full scale value 1200 0.001 to 9999M34
Analog input(An) disA Disable Analog input35Analog input full scale value(An) 1200 0.001 to 9999M36
Baud rate(b.A) 9600 1200 to 19.2k37
Parity Even Even/ Odd/ no38Device Id (dE) 1.000 39
40
4142
43
45
46
44
Password (PW) 1000 1000 to 9999
Starting Current(St) 0.400 0.2 to 10 %
Average PF (AP)
Under Compensation(UC)
Over Compensation (OC)
Under Amps(UA)
Over Amps(OA)
Other Warnings(OW) dISA
dISA
dISA
dISA
dISA
dISA Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
23 Capacitance(C3) 1000.0 500 VAR to 9999 MVAR
(An)
(PA)
47
Recommended