3-1
Chap.3
Chapter 3 Specifications of HG2F
1 Product List................................................................................................3-2 1.1 Main Unit..................................................................................................................... 3-2 1.2 Accessories ................................................................................................................... 3-2 1.3 Options ......................................................................................................................... 3-2
2 Part Names and Functions ........................................................................3-4 2.1 Front............................................................................................................................. 3-4 2.2 Rear .............................................................................................................................. 3-5 2.3 Layout of Touch and CC SWITCH .............................................................................3-6
3 Main Unit Specifications ............................................................................3-7 3.1 Applicable Standards .................................................................................................. 3-7 3.2 General Specifications................................................................................................. 3-7 3.3 External Dimensions................................................................................................... 3-9 3.4 Function Specifications ............................................................................................. 3-11 3.5 Display Specifications ............................................................................................... 3-12 3.6 Operation Specifications ........................................................................................... 3-13 3.7 Power supply Input Specifications ........................................................................... 3-13 3.8 Serial Interface1 Specifications ................................................................................ 3-14 3.9 Serial Interface2 Specifications ................................................................................ 3-15 3.10 USB (Mini-AB) Interface......................................................................................... 3-16 3.11 Compact Flash(CF) interface specification............................................................ 3-17 3.12 Expansion Interface Specifications ........................................................................ 3-18 3.13 O/I link Interface Specifications ............................................................................. 3-18
4 Installation and Wiring .............................................................................3-19 4.1 Installation Location ................................................................................................. 3-19 4.2 Installation................................................................................................................. 3-19 4.3 Wiring......................................................................................................................... 3-20
5 Inspection ................................................................................................3-21
Chapter3 Specifications of HG2F
3-2
1 Product List
1.1 Main Unit
Main Unit
Display
type Operating Type
CF
Slot
Maintenance
port Type No.
Touch switch - RS-
232C
HG2F-
SS22VF
Touch switch 1
Slot
RS-
232C
HG2F-
SS22VCF
Touch switch 1
Slot USB
HG2F-
SS22VDF
Touch switch
& CC SWITCH -
RS-
232C
HG2F-
SS52VF
Touch switch
& CC SWITCH
1
Slot
RS-
232C
HG2F-
SS52VCF
Color
Touch switch
& CC SWITCH
1
Slot USB
HG2F-
SS52VDF
Touch switch - RS-
232C
HG2F-
SB22VF
Touch switch 1
Slot
RS-
232C
HG2F-
SB22VCF
Touch switch 1
Slot USB
HG2F-
SB22VDF
Touch switch
& CC SWITCH -
RS-
232C
HG2F-
SB52VF
Touch switch
& CC SWITCH
1
Slot
RS-
232C
HG2F-
SB52VCF
Mono
chrome
Touch switch
& CC SWITCH
1
Slot USB
HG2F-
SB52VDF
1.2 Accessories
Type No. Notes HG9Z-2K1 Mounting Clip (4) B-855, 856 Operating Instruction Sheet (1)
1.3 Options
Configuration software (WindO/I-NV2)
Type No. Description HG9Y-B1118 Japanese manual HG9Y-B1119 English manual SW1A-W1C CD-ROM
Maintenance Cable
Type No. Description
HG9Z-XCM22 2m D-sub 9P socket (PC side) for Windows PC
Mounting Clip
Type No. Description HG9Z-2K1PN04 Mounting Clip (HG9Z-2K1),
4 pieces per package
PLC Connecting Cable
Type No. Description PF3S-KS1 For IDEC FA3S Link Unit, 5m FC4A-KC2C For IDEC MicroSmart, 5m HG9Z-3C115 For IDEC MICRO3, 5m HG9Z-3C125 For IDEC MICRO3C,
OpenNet Controller MicroSmart, 5m
HG9Z-3C135 RS-232C (25pin, D-sub), for Mitsubishi, Omron, etc. link unit, 5m
HG9Z-3C145 RS-232C (9pin, D-sub), Mitsubishi, etc. link unit, 5m
HG9Z-3C155 RS-232C (9pin, D-sub), Omron etc. RS-232C I/F, 5m
HG9Z-3C165 For Mitsubishi A and FX series programming port, 5m
1 Product List
3-3
Chap.3
Protective Sheet
Type No. Description HG9Z-2D2 Protective sheet for touch switch
type (5 sheets per package for HG2F)
Replacement Backlight
Type No. Description HG9Z-2B1 Backlight for HG2F
Expansion Unit
Type No. Description HG9Z-2P101 Digital I/O
(16 inputs and 16 outputs) HG9Z-2PNL1 LONWORKS network unit
O/I Link Unit
Type No. Description HG9Z-2G1 Dedicated communication unit
CF Card
Type No. Description HG9Z-MF128 CF Card (128MB)
Chapter3 Specifications of HG2F
3-4
2 Part Names and Functions
2.1 Front
HG2F-S*22VF (Touch Switch Type)
Touch switches
HG2F-S*52VF(CC SWITCH Type)
Touch switches CC SWITCH
CC SWITCH refers to thin switches installed on the display screen that provide a tactile 'click' that is similar to that of conventional mechanical push-button switches. They are physically rugged and designed to minimize input errors.
2 Part names and Functions
3-5
Chap.3
2.2 Rear
No. Name Description
1 Power Supply and Function Ground European-type terminal block 3P Serial Interface 2 Mini-DIN 8P connector
2 USB Interface Mini-AB USB connector
3 Expansion Interface 60P connector 4 Serial Interface 1 D-sub25P connector 5 O/I Link Interface Special connector 6 CF Interface Connects the Compact Flash 7 Access Stop Switch CF extraction permission switch 8 Access Lamp 9 Rubber Packing
10 Nameplate
(10)
(4)
(3)
(9)
(5) (1)
(2)
(8)
(7)
(6)
Chapter3 Specifications of HG2F
3-6
2.3 Layout of Touch and CC SWITCH
Touch and CC Switch can be placed on the block grids. The physical switch layout is as shown in the illustration below.
・ HG2F-S*22VF
・ HG2F-S*52VF
320
20
20
240
20
20
160
40
320
72
3 Main Unit Specifications
3-7
Chap.3
3 Main Unit Specifications
3.1 Applicable Standards
Safety Standards UL508, UL1604, CSA C22.2 No.1010.1, No.213IEC/EN61131-2
EMC Standards IEC/EN6100-6-4, IEC/EN61131-2
3.2 General Specifications
Electrical Specifications
Rated Operating Voltage
24VDC
Power Voltage Range
85% to 120% of rated voltage (including ripple)
Power Consumption
10W max.
Allowable Momentary Power Interruption
10ms max.: Level PS-2 (IEC/EN61131)
Inrush Current 20A max. Dielectric Strength 1000VAC 10mA, 1 minute
(between power terminals and FG)
Insulation Resistance
50MΩ min. (500VDC mega) (between power terminals and FG)
Environmental Specifications
Operating Ambient Temperature (operation)
0 to 50°C (no freezing)
Operating Relative Humidity (operation)
10 to 95%RH (no condensation)
Storage Ambient Temperature
-20 to +60°C (no freezing)
Storage Relative Humidity
10 to 95%RH (no condensation)
Altitude 0 to 2000m (operation), 0 to 3000m (transport) (IEC61131-2)
Vibration Resistance
10 to 20Hz amplitude 0.625mm,20 to 55 Hz, 9.8 m/s2 [2 hours each in 3 axes] (IEC60068-2-6)
Shock Resistance 147 m/s2, 11 ms [5 shocks each in 3 axes] (IEC60068-2-27)
Pollution Degree 2 (IEC60664-1) Corrosion Immunity
Free from corrosive gases
Effect of Incorrect Connection
Reversal of DC power supply polarity
No damage but the equipment will not operate
Connection to AC supply that exceeds ratings
Permanent failure likely
Earthing
Function earth Wire to ensure stable equipment operation
Chapter3 Specifications of HG2F
3-8
Construction
Installation Buried panel Protection IP65 (at the front of the
installation panel), NEMA TYPE 13
Terminals Power supply input: M3 screw Tightening torque: 0.5 to 0.6Nm
Dimensions 172(W) x 136(H) x 56(D) mm Weight 800g (approx.)
Noise Specifications
Electrostatic Discharge
ESD-3 (RH-1) level 3 Contact +/-6KV/ Air +/-8KV
IEC/EN61000 -4-2
Electro- magnetic Field
10V/m 80MHz to 1GHz 1.4 to 2GHz 80%AM
IEC/EN61000 -4-3
Fast Transient Burst Withstand- ability
Common mode: Level 3 Power supply: +/-2KV Communication line: +/-1KV
IEC/EN61000 -4-4
Damped Oscillatory Wave
Serial mode: Power supply: +/-1KV
IEC/EN61000 -4-12
Power-up Surge Immunity
Between 500V Line-FG
IEC/EN61000 -4-5
Radiated Emission
IEC/EN6100-6-4
3 Main Unit Specifications
3-9
Chap.3
3.3 External Dimensions
HG2F-S*22V*
172.0
162.0
136.
0
126.
0
6.0
56.0
Chapter3 Specifications of HG2F
3-10
HG2F-S*52V*
172.0
162.0 13
6.0
126.
0
56.0
6.0
3 Main Unit Specifications
3-11
Chap.3
3.4 Function Specifications
Number of screens
Base Screens: 3,000 screens Popup Screens: 3,000 screens
Screen memory
Approx. 2Mbytes max. (Flash memory)(including the optional fonts)
Screen types
Base Screen, Popup Screen, System Screen
Number of parts
480/screen (Base Screen) 480/screen (Popup screen)
Number of host devices
256 read, 512 write/screen (Base Screen) 64 read, 128 write/screen (Popup Screen)
Parts Bit Button Word Button Goto Screen Button Print Button Key Button Multi button Keypad Selector Switch Potentiometer Numerical Input Character Input Pilot Lamp Multi-State Lamp Picture Display Message Display Message Switching Display Alarm List Display Alarm Log Display Numerical Display Bar Graph Trend Chart Pie Chart Meter Calendar Bit Write Command Word Write Command Goto Screen Command Print Command
Screen Script Command Multi Command Timer
Operation modes
Run Mode: Normal operation
Data Transfer Mode: Data upload and download
System Mode: Initial setting,
clock setting,
system information,
self diagnosis and debug
Screen creation andoperation settings
WindO/I-NV2 software application
Calendar Year, Month, Day, Hour, Min., Sec. and Day-of-week +/-30 sec. per month (at 25°C)
Power failuremaintenance
Maintenance object: Calendar, Alarm Log Data: 1024 points (max.), Data Log Data: approx. 3000 points (max.), 1024 keep internal relay/1024 resister
Maintenance period: 1 month (at 25°C)
Chapter3 Specifications of HG2F
3-12
3.5 Display Specifications
Display Functions
Color 5.7 inch STN color LCD
(transparent type) Display
Monochrome 5.7 inch STN monochrome
LCD (transparent type)
Effective display area 118.2 (W) x 89.4 (H) mm
Display resolution 320 (W) x 240 (H) dots
Pixel pitch 0.36 (W) x 0.36 (H) mm
Color 256 Display colors Monochrome 16
Contrast adjustment Can be adjusted from the front
touch panel Size/number 1/4 size: 8 x 8 dots/
40 characters x 30 lines 1/2 size: 8 x 16 dots/ 40 characters x 15 lines Full size: 16 x 16 dots/ 20 characters x 15 lines Double size: 32 x 32 dots/ 10 characters x 7.5 lines
Character Display
Types
8 x 8 dots, 8 x 16 dots: English, Katakana, Symbols (JIS8 bit code), ISO-8859-1(European), ANSI1250(Central European), ANSI1257(Baltic), ANSI1251(Cyrillic)
16 x 32 dots, 24 x 48dots, 32 x 64 dots: ISO-8859-1(European)
16 x 16 dot: Japanese: 1st and 2nd level JIS, Chinese, Korean, Taiwanese
32 x 32 dots: Japanese: 1st and 2nd standard JIS
Character attributes
Magnification: 0.5, 1, 2, 3, 4 and 8 (ver. and hor.) Attributes: Blink, reverse, bold, embossed
Types Line, rectangle, Polyline
polygon, circle, ellipse, pie,
arc, polygon (3, 4, 5, 6, and 8
sided), bitmap image and paint
Line types Solid, dotted, dashed, long
dashed, long dashed dot and
long dashed dot dot
Line width 1,2,3 and 5 dots
Graphics Display
Graphic symbol attribute
Blink switch display
between specified colors
(1 or 0.5 second period)
Presumed Life Of Display
50,000 hours (min.) (at 25°C)
Backlight
Light Source Cold-cathode tube Presumed Life Of Back Light
Standard 40,000 hours* *Luminance drop to half after continuous lighting at room temperature
Replacement Possible Control Auto off
3 Main Unit Specifications
3-13
Chap.3
3.6 Operation Specifications
Touch Switches
Switch mechanism Touch switches Switch method Matrix resistive
film type Composition 16 x 12 (16 x 8 for the
CC SWITCH type) Operation force 0.2 to 0.8N Life 1,000,000 cycles min. Confirmation Electronic buzzer
CC SWITCH
Switch mechanism CC SWITCH Switch method Matrix resistive
film type Quantity (per screen) 4 Operation force 2.5 to 5.0N Stroke 0.5mm (approx.) Life 1,000,000 cycles min. Confirmation Electronic buzzer
3.7 Power supply Input Specifications
Wiring UL1007 AWG18 1 Cable: AI 1-8* 2 Cable: AI-TWIN 2 x 1-8* UL1015 AWG20 1Cable: AI 0.5-8* 2Cable: AI-TWIN 2x0.5-8* *Phoenix Contact Maintain separation between the input wiring and the power, output and communications wiring.
Connector M3 screw
Connector Pin Layout
Connector Pin Functions
Symbol Function + Power supply +24V DC - Power supply -24V DC
Function ground
Ground the functional ground terminal to
ensure stable operation.
+
-
Chapter3 Specifications of HG2F
3-14
3.8 Serial Interface1 Specifications
RS-232C
Electrical characteristics
EIA RS-232C compliant
Transmission speed
1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200bps
Synchronization Asynchronous Communication method
Half or full duplex
Control system Hardware control/none Protocol (1) PLC-link protocol for a variety
of PLCs and communicationunits
(2) DM Link Transmission distance
15m (5m when connected to a PLC programming port)
Connection format
1:1
RS-485 (422)
Electrical characteristics
EIA RS-485 (422) compliant
Transmission speed
1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200bps
Synchronization Asynchronous Communication method
Half or full duplex
Control system Hardware control/none Protocol (1) PLC-link protocol for a variety
of PLCs and communicationunits
(2) DM Link Transmission distance
300m (5m when connected to a PLC programming port)
Connection format
1:1 or 1:N
Only one of the RS-232C or RS-485 (422) ports can be used at one time.
Connector
Connector D-sub 25P connector (socket)
Connecting and disconnecting cycles
500 cycles (min.)
Connector Pin Layout
3 Main Unit Specifications
3-15
Chap.3
Connector Pin Functions No. Name Function
1 FG Frame Ground
2 SD Send Data (RS-232C)
3 RD Receive Data (RS-232C)
4 RS Send Demand (RS-232C)
5 CS Clear to Send (RS-232C)
6 – –
7 SG Signal Ground
8 – –
RS-485 RS-422
9 TERM Terminator*1 TERM Terminator*1
10 RDA Receive Data A RD+ Receive Data
(+)
11 SDA Send Data A SD+ Send Data (+)
12 – – – –
13 – – – –
14 – – – –
15 SDB Send Data B SD- Send Data (-)
16 RDB Receive Data B RD- Receive Data
(-)
17 – – – –
18 CS– Clear to Send (-)
19 RS– Request to
Send (-)
20 ER Data Terminal Ready (RS-232C)
21 CS+ Clear to Send
(+)
22 RS+ Request to
Send (+)
23 – – – –
24 – – – –
25 – – – –
*1 To enable the 330Ω built-in terminator, connect terminal No.9 [TERM] and terminal No.10 [RDA/RD (+)] together.
3.9 Serial Interface2 Specifications
Electrical characteristics
EIA RS-232C compliant
Transmission speed
9600, 19200, 38400, 57600 and 115200bps
Synchronization Asynchronous Communication method
Half duplex
Protocol Dedicated protocol Connector Mini DIN8P connector Connection and disconnection cycles
1000 cycles (min.)
Chapter3 Specifications of HG2F
3-16
Connector Pin Layout
Connector Pin Functions
No. Name Function 1 RS Request to send 2 ER Data terminal ready 3 SD Send data 4 RD Receive data 5 DR Data set ready 6 EN Use as needed 7 SG Signal ground 8 NC No connection
Connect pin 6 (EN) and pin 2 (ER) unless performing maintenance communications for downloading project data. Use Printer connection cable (FC2A- KP1C) when the HG2F be connected with the printer. (Refer to the printer instruction manual for details.)
3.10 USB (Mini-AB) Interface
Connector Pin Layout
No. Name Function 1 VBUS Power supply 2 D- Data line (-) 3 D+ Data line (+) 4 ID Plug check 5 GND Ground
CAUTION USB Port is used for corrective maintenance only and not for permanent use at a Hazardous Location.
6
3
4
7 8
5
2 1
1 2 3 4 5
3 Main Unit Specifications
3-17
Chap.3
3.11 Compact Flash(CF) interface
specification
Connector Pin Layout
Pin No. Name Pin No. Name
1 GND 26 CD1# 2 D3 27 D11 3 D4 28 D12 4 D5 29 D13 5 D6 30 D14 6 D7 31 D15 7 CE1# 32 CE2# 8 A10 33 VS1# 9 OE# 34 IORD# 10 A9 35 IOWR# 11 A8 36 WE# 12 A7 37 IREQ# 13 VCC 38 VCC 14 A6 39 CSEL# 15 A5 40 VS2# 16 A4 41 RESET 17 A3 42 WAIT# 18 A2 43 INPACK# 19 A1 44 REG# 20 A0 45 BVD/SPKR# 21 D0 46 BVD1/STSC
HG# 22 D1 47 D8 23 D2 48 D9 24 WP_IOIS16# 49 D10 25 CD2# 50 GND
Make sure the access lamp is turned OFF before removing the CF (Compact Flash) card by following either of the steps below. 1. Push the red access stop switch located at the back of the operator interface. 2. Wait until the HG special relay is (LSM20) is turned ON. Note: If the CF card is removed while the Access Lamp is ON, data may be destroyed. In this case, it may be necessary to reformat the CF card.
25
Eject button
26 1 50
Chapter3 Specifications of HG2F
3-18
3.12 Expansion Interface
Specifications
Method Dedicated Interface to Expansion Unit
Compatible Unit
Digital I/O unit, LONWORKS unit
Electrical characteristics
HG Series dedicated bus
Connector Dedicated connector
Outline
The HG2F can be used in conjunction with optional units.
(Refer to the Expansion Unit instruction manual for details.)
3.13 O/I link Interface Specifications
Method Dedicated interface to O/I link Unit
Connector Dedicated connector Recommended cable
0.3mm2 Twisted-pair shielded cable Conductor resistance:85Ω/km maximum Shield resistance:20Ω/km maximum
Outline
The HG2F Operator Interface can be connected to an O/I Link Unit for 1:N communication with a PLC. This allows high-speed communication with the PLC host.
4 Installation and Wiring
3-19
Chap.3
4 Installation and Wiring Be aware of the following when mounting the HG Series main unit and wiring it to the host unit.
4.1 Installation Location
Operating Environmental Considerations
To ensure reliable and safe operation of the equipment, avoid the types of installation locations listed below.
・ Places where there is a lot of dust, salt or iron
filings.
・ Places where the equipment will be splashed
with oil or chemicals.
・ Places where the equipment will be exposed to
direct sunlight.
・ Places where corrosive or flammable gasses
are present.
・ Places where vibration will be directly
transmitted to the equipment.
・ Places where condensation may occur due to
sudden temperature changes.
Ambient temperature considerations
・ Allow sufficient space for ventilation, and install
the equipment away from heat sources.
・ Allow at least 100mm between the HG2F and
walls or other equipment, and make enough
clearance below the HG2F to plug in and out
the CF.
・ If installing the HG2F in a location where the
ambient temperature will exceed the allowed
rating, install cooling fans or air-conditioning
equipment.
・ The HG2F has been designed to use natural
airflow for cooling when installed vertically. If
you install it using any other orientation, use
forced-air cooling, or lower the ambient
operating temperature.
4.2 Installation
Place the HG2F in a panel cut-out and fasten with the attached mounting clips at four places to a torque of 0.15 to 0.2 N·m uniformly. Do not tighten excessively, otherwise the HG2F may be damaged. Take into consideration the viewing angle and switch operation factors when choosing the installation height.
If the installation screws are not installed so that they are at right angles to the panel, the unit may separate from the panel.
HG2F
PanelMounting Clip
Chapter3 Specifications of HG2F
3-20
Panel Cut-out Dimensions [Dimension: mm]
4.3 Wiring
Wiring Considerations
・ Do not install the HG2F close to high-voltage or
arc-generating equipment (such as circuit
breakers etc.).
・ Install the unit at least 200mm from the high
input voltage of the power supply.
・ In the case of DC power supply models, keep
the distance between the unit and the power
supply as short as possible.
・ Use separate power supplies and wiring for
electromotive equipment and I/O equipment.
・ A host connection cable is provided with the
equipment. Please specify your requirement.
・ If you will use your own cable for connecting to
the host, ensure that the connector and wiring
are of the recommended type. Also, do not
exceed the recommended length for the
cable.
Wiring to the Power Supply Terminals
・ Terminal No. allocation is as follows.
Symbol Function + Power supply +24VDC - Power supply -24VDC
Function ground
+ -
Panel Thickness: 1.6 to 5
126.
5+0.
5
162.5+0.5
4-R2.0 max
0
0
5 Inspection
3-21
Chap.3
・ Use Phoenix Contact AI Series bar-type
pressure contact terminals.
・ The tightening torque range is 0.5N.m to
0.6N.m.
・ Twist the AWG18 (1mm2) power supply wires
as tightly together as possible, and keep the
wiring distance between the power supply
and the unit as short as possible.
・ Use separate power supplies and wiring for
electromotive equipment and I/O equipment.
・ For safety, earth the Function earth terminal of
the unit.
・ When exporting the HG2F to Europe, use an
EN60127 (IEC60127) approved fuse or an
EU-approved circuit protector.
Wiring Serial Interface 1
・ The appropriate connector is the recommended
connector (connector: JBZ-25P-90(JST),
cover: J-C25-C2(JST)).
・ Perform the wiring in accordance with the
requirements of the communication method.
This will minimize the influence of external
electrical noise and electrical noise generated
by the wiring itself. EMC evaluation has not
been done for the cables.
・ Use shielding for the cables, and install line
clamp filters near each end of the cable.
Example TDK: ZCAT2035-0930
5 Inspection Periodically inspect the HG2F to keep it in the best operating condition at all times.
・ The HG2F display screen and protective sheet
are easily damaged. Never attempt to operate
the unit with tools or other hard objects.
・ To clean the display screen, wipe it with a soft
cloth moistened with a mild detergent or
alcohol. Never attempt to clean the display screen
using paint thinner, ammonia, strong acid, strong alkaline, or other powerful solvents.
・ Terminals and connectors
Check for loose screws, loose connectors and
damaged wiring.
・ Installation
Check the installation brackets and screws for
warping and looseness.
Recommended