I
Preface
First of all thank you for purchasing DR300 series inverter!This instruction manual describes how to properly use DR300 series inverter. Please read
the instruction manual carefully before using(Before installation,operation,maintenance andinspection).Besides, please use the product after understanding the safety precautions.
Note matter
The drawings presented in this instructions are sometimes shown withoutcovers or protective guards.Always replace the equipment’s cover orprotective guard as specified first,and the operate the products in accordancewith the instructions.
The drawings presented in the instructions are typical examples and may notmatch the product you received.
These instructions are subject to change due to productimprovement,specification modification, specification modification.
If you want to order the manual due to loss or damage, please contact ourcompany agents in each region or our company customer service centerdirectly.
If there is still any problem during using the product, please contact our companycustomer service center directly.
Our Service Hotline:0510-8380 9006
Fax :0510-8380 9007
IntroductionDR300 series inverter is a versatile general-purpose inverters which was developed for the
needs of a wide range of generic customers through a market research by Wu Xi DayuanGuangsheng electric Co., Ltd.The whole series of DR300 inverter has independent ventilation,which can be installed outside or inside the radiator cabinet;perfect user passwordprotection ,directly input DC bus terminal and DC powered fan that enable the non-standard
DR300 User's manual
II
products to be compatible with the DC bus running mode that makes the complex applicationdebugging and operation was very easy, reliable, safe.
Input/output terminal
7 digital inputs (X7 can select for high-speed pulse input/ digital input)Three analogue inputs (AI1 can choose forvoltage/current input)Two digital output (Y1 can choose for high speed pulseoutput/open collector output)Two analog output (AO1 can choose for voltage/currentoutput)A relay output
Control mode V/F,SVC
Analog reference mode Straight line mode
MS-speed Be able to realize 16S speed
Simple PLC Be able to realize 7-segment timing run
S-curve control Available
Communication functionComes with RS485 communication port (standardModbus protocol)
PID control Available
V / F mode Straight line, square, multi-point
In order to facilitate debugging the whole series of DR300 not only with a local keyboard,external keyboard can also be through a standard RJ45 port of the external operator panelinterface. All these features reflect that the DR series inverter strictly complies with the principle“Respect the Customers” during the design process.This manual for DR300 operating instructionmanual.This manual provides the user with related precautions and instructions for theprototyping, installation, parameter setting, on-site commissioning, and routine Repair andMaintenance of inverter. In order to use this series of inverter correctly, please read this manualcarefully prior to operation and keep it properly for future use. The supporting equipmentcustomers shall distribute this manual together with the equipment to the final users .Unpacking and inspection:
Upon unpacking, please confirm the following:1) If the model and inverter rated values on the nameplate are the same as your order. The
box contains the equipment, certificate of conformity, user manual and warranty card.2) If the product is damaged during the transportation. If there is any omission or
damage,please contact our company or the supplier immediately.First time use:The users use this product for the first time should read this manual carefully. For any doubt
on certain functions and performances, please contact the technical support personnel of ourcompany for help so as to use this product properly.
III
With commitment to the constant improvement of the inverter products, our company maychange the information provided without additional notice.
DR300 series inverter complies with the following international standards:ICE certification IEC/EN61800-5-1:2003 “Safety Regulations on Commissionable Electric
Drive System” ;
IEC/EN 61800-3:2004 Commissionable Electric Drive System;
Third Part: Electromagnetic Compatibility Standard and Specific Testing Method for theProduct (Comply with IEC/EN61800-3 standard under correct installation and use as per Article7.3.2 and 7.3.6)
DR300 User's manual
IV
Contents
Preface................................................................................................................................................I
Introduction.......................................................................................................................................I
IEC/EN 61800-3:2004 Commissionable Electric Drive System;............................................... III
Contents...........................................................................................................................................IV
Chapter 1 Safety information and precautions............................................................................2
1.1 Security matters..................................................................................................................................21.2 Notes......................................................................................................................................................5
Chapter 2 Product information......................................................................................................8
2.1 Naming rules..........................................................................................................................................82.2 Nameplate..............................................................................................................................................82.3 DR300 series Inverter............................................................................................................................92.4 Technical Specifications........................................................................................................................92.5 Product outline;The size of installation holes.....................................................................................122.6 The choice of accessories....................................................................................................................162.7 The daily maintenance of the inverter.................................................................................................172.8 Warranty description of the inverter....................................................................................................182.9 Selection guidance...............................................................................................................................182.10 Guide of brake component selection.................................................................................................19
Chapter 3 Mechanical and electrical installation.......................................................................21
3.1 Mechanical Installation.......................................................................................................................213.2 Electrical Installation...........................................................................................................................23
Chapter 4 Operating And Display...............................................................................................36
4.1 Operation and display interface...........................................................................................................364.2 View Function Code; Description of Modify Method........................................................................374.3 State parameter check method.............................................................................................................384.4 Password setting..................................................................................................................................384.5 Keyboard lock and unlock...................................................................................................................38
Chapter5 Function Parameter List.............................................................................................39
Chapter6 Parameter Description..............................................................................................68
V
F0 :Basic Function.................................................................................................................................68F1: Motor parameters, V / F, the control parameters................................................................................80F2:Input Terminal...................................................................................................................................85F3 Groups:Output terminals...................................................................................................................90F4 Group:start and stop buttons display....................................................................................................95F5 Group: PID function.............................................................................................................................99F6 Group: the PLC run............................................................................................................................105F7 Group: multi-speed, multi-segment Acceleration and deceleration time, digital frequencyadjustment...............................................................................................................................................109F8 Group: vector control torque is given................................................................................................115F9 Group:Communication....................................................................................................................118F10 Group:Fault and Protection...........................................................................................................120F11 group:Accessibility.......................................................................................................................126F11.17Analog ADT1 hysteresis:The analog ADT1 input level lag select .Hysteresis is definedas single-phase down, so the actual action point ADT1 is analog ADT1 (F11.16) value minus thevalue of the analog ADT1 hysteresis (F11.17). Such as:When F11.15=2 、F11.16=25.00、F11.17=5.00,the analog ADT1 is effective when the analog input terminal AI2 input voltagesignal to 2V (10V × 25%-10V x 5% = 2V) , then by the relay output terminals or multi-functionoutput terminal output indicator or alarm signal.....................................................................................130F12 Group:Quick menu list..................................................................................................................131F13 Group:Analog enhancements........................................................................................................133ER Group:Fault History.......................................................................................................................136H0 Group:Monitoring parameters........................................................................................................138
Chapter 7 EMC (Electromagnetic Compatibility)..................................................................139
7.1 Definition..........................................................................................................................................1397.2 EMC Standard Description...............................................................................................................1397.3 EMC Guide.......................................................................................................................................140
Chapter 8 Fault Diagnosis and Solution...................................................................................142
8.1 Fault Alarm and Countermeasures....................................................................................................1428.2 Common faults and their treatment...................................................................................................150
Appendix I DR300 series inverter ModBus communication protocol................................151
Appendix II Keyboard installation dimension drawing......................................................... 158
DR300User'smanual
1
Grounding
Grounding
Motor
Output sideNoise filter
Dayuan inverter
Input sideNoise filter
AC reactor
Electromagnetic contactor
Non-fuse breaker(MCCB)
Three-phase AC powerPlese use the power wthinthe frequency
Due to the current input,inverter will flow into thebig current impact,so itneeds the selected circuitbreaker.
Breaking unit(optional)
Breaking resistance
Reatrain high orderharmonic,improve the power factor.
To prevent getting onelectric shock,invertermust be good grounding.
Can give the full play tothe regenaration of theinverter,please useaccording to needing
Please don't useelectromagnetic contactorto start and stopinverter,it will reduce theinverter life.
Example of the connection of the machine and peripheralDon't install capacitors or surge suppressor in the output side of the inverter , this will lead to abreakdown or cause capacitance and the damaged of the surge suppressor.The inverter input / output (the main circuit ) contains harmonic components, it may interferewith inverter communication equipment. Therefore, installing anti interference filter to minimuminterference. The details of the peripheral devices and options refer to the selection manual of peripheralequipment.
DR300 User's manual
2
Chapter 1 Safety information and precautions
Safety definition:
In this manual, Safety cautions are divided into two types:Danger: since not according to the requirements of the operating cause danger,
may result in serious injury or death.Note:since not according to the requirements of the operating cause danger, may
cause moderate damage or minor injuries, and equipment damage..Please users carefully reading this chapter and must according to the requirements of
safety cautions in this chapter to operate when you install, debug and maintain thissystem. it is nothing to do with our company If appear any damage and loss due toviolate compasses operation.
1.1 Security matters
1.1.1 Before installation
Danger
Found control system fill into water when unpacking , lack of component or componentparts damaged, please do not install!Packing list with real names do not match, please do not install!
Danger
Handling should light , or damage the equipment of danger! Please don't use damaged or lack of parts inverter . A risk of injury! Don't use hand to touch control system’s components, it may cause electrostatic damage!
1.1.2 Installing
Danger
Please install in metal flame retardant objects; Away from the fuel. Or it may cause a fire!Shall not turned the standing bolt of equipment components casually, especially with redmarking of bolt!
DR300User'smanual
3
1.1.3 Wiring
Danger
Please comply with the guidance of this manual, installing by the professional electricalengineering staff , otherwise it will appear unexpected danger!The power supply and the inverter should be separated, or it may cause fire!Please confirm the power supply in zero energy state before connection , or you will get anelectric shock risk!Please according to the standard of inverter for correct standard grounding, or you will getan electric shock risk!
Danger
Don’t connected the power to the output terminals (U, V, W) the inverter. Note terminalsmark, do not take the wrong line! Otherwise it will cause the damage!Ensure that the circuit match with EMC requirements and afety standards.please referencemanual Suggestions the wire line diameter . Or you could accident!Don’t directly connect braking resistance by dc bus (+), () between terminals. Otherwise itwill cause fire!Encoder must use the shielded wire, and shielding layer must ensure that the single-endedreliable grounding!
1.1.4 Before energizing
Danger
Please confirm the input power supply voltage grade; Please confirm the connectionbetween the power input terminals (R, S, T) and output terminals (U, V, W) are correct; AndBe aware of any short in the outside circuit connected to the inverter, whether the line istighten, or it will cause the damage to the inverter!Any part of the inverter need not to carry on pressure test, the factory has done this beforeleaving factory . Otherwise it will cause accidents!
Danger
The inverter must be covered before power on. Or it may cause a shock!All peripheral accessories of wiring must abide by this manual guidance and connectaccording to the manual provided circuit connection method. Otherwise it will causeaccident!
1.1.5 After energizing
DR300 User's manual
4
Danger
After power up don't open cover plate. Or it can get an electric shock ! Don't use wet hand to touch inverter and its peripheral circuit. Or it can get an electricshock ! Don’t touch any of the inverter’s input and output terminals. Or it can get an electric shock!At the beginning of the power on,the automatic system of the inverter will check the highvoltage outside, at this time,you should never touch the U, V, W terminals or motor terminalsof inverter, or it will get an electric shock!
Danger
If the motor parameters need to be identified, please pay attention to the danger when themotor rotating. Or it may cause accident! Please don’t change inverter’s manufacturer parameters optionally . Otherwise it maycause equipment damaged!
1.1.6 Running
Danger
Please don’t touch the cooling fans and the discharge resistance in order to testtemperature. Or it may cause burns!Amateur technicians don’t test signals when inverter running. Or it may cause a personalinjury or damage to the equipment.
Danger
Avoiding anything fall into the equipment when the inverter running . Or it will cause theequipment damaged. Don’t use contactor to control the inverter. Or it will cause equipment damaged.
DR300User'smanual
5
1.1.7 Maintenance
Danger
Please don’t repair or maintain the equipment. Or it can get an electric shock!Confirm in less than 36V voltage inverter to implementation in the maintenance and repair,when the power to fifteen minutes shall prevail. Otherwise the remnants of the charge to thecapacitance will cause damage!Without professional training personnel don’t repair and maintain inverter . Otherwise itwill cause personal injury or damage to the equipment.Please set parameters value after changing the inverter , all the pluggable must be insertedafter power off.
1.2 Notes
1.2.1Motor insulation inspectionThe motor insulation must be inspected when motor for the first time used or unused for a
long time, in case the effectiveness of the winding insulationto damage the inverter. Motorattachment must separate from inverter when insulated inspection, suggested the 500 V voltagetype megameter, guarantee the insulation resistance not less than 5 M Ω.
1.2.2Motor of the thermal protection
If choose motor and converter does not match the rated capacity, especially the rated powergreater than motor inverter power rating, be sure to adjust the inverter motor protection in relatedparameters value or in motor with thermal relay to before to motor protection.
1.2.3power frequency above operation
This inverter can provide 0 Hz ~ 600 Hz output frequency. If the customer needs to be infrequency 50 Hz above operation, please consider the strength of the mechanical device.
1.2.4The vibration of mechanical device
Inverter may meet load machinery’s mechanical resonance point in some outputfrequency place,it can be set hopping frequency and parameters within the inverter to avoid.
1.2.5 Motor fever and noise
Because the inverter’s output voltage is PWM waves, contain certain harmonic , therefore,the rise of temperature of the motor, noise and vibration frequency will run little increase.
1.2.6 When therer are pressure sensitive devices or capacitance to improve the powerfactor on the output side
Inverter is PWM waves, the output side such as the capacitor with improving electricalpower factor or the lightning protection with pressure sensitive resistance, it easy causeinstantaneous inverter over current even damage inverter, please do not use.
1.2.7The input and output terminal contactor of switching element etc
DR300 User's manual
6
If contactor is between the power and inverter input side , it is not allowed to use thiscontact device control inverter to the rev. Stop. It need to use this contractor to control theinverter rev. Stopping , interval an hour at least. Frequent charge-discharge is easily reduce theinverter of the capacito the service lifer. If the output and motor with contact between the switchdevice, shall ensure that no output inverter in the hige operation, or it easily cause invertermodule damaged.
1.2.8 Rated voltage value the use of outside
Not suitable for user manual in the provisions of the voltage range allowed outside use DRseries inverter, it easily cause the inverter device damaged . If it necessary, please use thecorresponding or step down device to deal with variable pressure
1.2.9 Change the three-phase input into the two phase input
Don’t change the three-phase inverter into the two phase in DR series. Otherwise it willlead to malfunction or damage the inverter
1.2.10 Lightning shock protection
This series of inverter is equipped with a lightning over current protection device, havingcertain ability of self-protection for indirect lightning.In the frequent lightning place, pleaseinstall the protective devices at the front end of the inverter.
1.2.11 The altitude and derating using
At an altitude of more than 1000m area, because thin air cause the inverter cooling effectbecoming poor,so it is necessary to derate use. Please consult our company for technique in thissituation.
1.2.12 Some special usage
If the customer was using when required to book recommendations provided by methodsother than when wiring diagram, such as dc bus, etc, please consult our company
1.2.13Converter scrap note
The main loop of the electrolytic capacitor and printed circuit boards electrolytic capacitorson incineration can explode. Plastic incinerator will produce toxic gases. Please as industrialwaste processing.
1.2.14 Adapter motor
1)Standard adapter electric quadrupole squirrel-cage asynchronous induction motor. If themotor please press the motor rated current selection of inverter. If you need to drive permanentmagnet synchronous motor of the occasion, please consult our company.
2)A variable frequency motor cooling fan and rotor shaft is coaxially connected, speed isreduced when the fan cooling effect is reduced, therefore, the motor overheat the occasionshould be equipped with strong exhaust fan or replacement for variable frequency motor.
3)Converter has a built-in adaptation motor standard parameters, according to the actualsituation it is necessary to motor parameter self identification or modify the default values so asto accord with the actual value, otherwise it will affect the running effect and protectionperformance.
DR300User'smanual
7
4)Because the cable or motor internal short circuit can cause inverter alarm, even fryingmachine. Therefore, please first for the initial installation of the motor and cable insulation shorttest, routine maintenance is often required for this test. Note, doing this test must be tested partof inverter and disconnect all.
DR300 User's manual
8
Chapter 2 Product information
2.1 Naming rules
DR300 - T 3 - 011 G / 015 PInverter series
Code Voltage levelTS
Three-PhaseSingle-Phase
23611
220V380V660V
1140V
GP
Inverter typeUniversal typeFan pump type
7R5011015018022030
Adapter motor power (KW)
7.51115
18.52230
Code Voltage level
Code
Code
Figure 2-1 Naming rules2.2 Nameplate
MODEL:DR300-T3-011G/015PINPUT: 3PH AC 380V 50/60HZOUTPUT1:11KW 26A 0.00-600.0HZOUTPUT2:15KW 34A 0.00-600.0HZSER NO:
Wuxi Dayuan Guangsheng Electric Co., LTD
Figure 2-2 Inverter brand of the data
DR300User'smanual
9
2.3 DR300 series Inverter
inverter typeInput
voltage
Powersupply
capacity(KVA)
Inputcurrent(A)
Rated outputcurrent
(A)G/P
Adaptermotor
(KW)
DR300-S2-0R4G Single-phase 220 Vrange:
-15%~20%
1.0 5.4 2.3 0.4DR300-S2-0R7G 1.5 8.2 4.0 0.75DR300-S2-1R5G 3.0 14.0 7.0 1.5
DR300-S2-2R2G 4.0 23.0 9.6 2.2
DR300-T3-1R5G/2R2P
Three-phase 380 V
range:-15%~20%
3.0 8.0 4.8/6.2 1.5/2.2DR300-T3-2R2G/4R0P 4.0 11 6.2/10 2.2/3.7DR300-T3-4R0G/5R5P 8.9 15 10/13 3.7/5.5DR300-T3-5R5G/7R5P 11 20 13/17 5.5/7.5DR300-T3-7R5G/011P 17 27 17/26 7.5/11DR300-T3-011G/015P 21 35 26/34 11/15DR300-T3-015G/018P 24 43 34/41 15/18.5DR300-T3-018G/022P 30 50 41/48 18.5/22DR300-T3-022G/030P 40 62 48/60 22/30DR300-T3-030G/037P 57 76 60/75 30/37DR300-T3-037G/045P 69 92 75/90 37/45DR300-T3-045G/055P 85 118 90/115 45/55DR300-T3-055G/075P 114 157 115/150 55/75DR300-T3-075G/093P 134 190 150/180 75/93DR300-T3-093G/110P 160 224 180/220 93/110DR300-T3-110G/132P 192 268 220/265 110/132DR300-T3-132G/160P 231 314 265/310 132/160DR300-T3-160G/185P 250 385 310/360 160/185DR300-T3-185G/200P 260 403 360/380 185/200DR300-T3-200G/220P 280 430 380/420 200/220DR300-T3-220G/250P 355 480 420/470 220/250DR300-T3-250G/280P 396 539 470/530 250/280DR300-T3-280G/315P 445 610 530/600 280/315DR300-T3-315G/355P 500 665 600/660 315/355DR300-T3-355G/400P 565 765 660/740 355/400DR300-T3-400G/450P 630 843 740/820 400/4502.4 Technical Specifications
Project Specification
Basicfunctions
The highestfrequency
600Hz
DR300 User's manual
10
Carrierfrequency
1.0kHz~16.0kHz ; Depending on the load characteristics,andautomatically adjust the carrier frequency.
Inputfrequencyresolution
Digital set:0.01HzSimulation set:The highest frequency×0.025%
Control mode V/F Control,Flux vector control
Startingtorque
150%
range of speedregulation
1:50
Steady speedaccuracy
±1%
Overloadability
G type machine150%rated current60s,P type machine 120%ratedcurrent60s
Torque boost Automatic torque boost;Manual torque boost 0.1%~30.0%
V/F Curve Straight line V/F,Multi-point V/F,Square V/F
Accelerationand
decelerationcurves
Linear acceleration and deceleration , S-curve acceleration anddeceleration;Four groups acceleration and deceleration time;Acceleration and deceleration time range 0.00s~600.00min
DC brakingDC brake frequency:0.00Hz~highest frequency,Braking time:0.00s~30.00s,Braking action voltage:0.00%~30.00%
Point startcontrol
Point control frequency range:0.00Hz~The highest frequency;Point control acceleration and deceleration time0.00s~600.00s
Simple PLC、Multi-speed
operation
To realize 16 section of speed operation by the built-in PLC orcontrol terminals
Internal PID To realize closed loop control system
Automaticvoltage
regulation(AVR)
When the voltage change, automatic output voltage can keepconstant
Over-current control
“Excavator” characteristics,automatically limit the current duringoperation,to prevent frequent over-current trip
Fast currentlimit function
Minimize the over-current fault,and protect the normal operationof the inverter
DR300User'smanual
11
Personalizationfeatures
MK key
Programming point control;Positive/Negative input switchingfunction;code display switch function、Rev. Stop order switch、Free parking and emergency stop,the specific function set pleasereference to the fifth chapter of the function code F0.26
Self-definedfaultfunction
Users can define the analogue or the digital quantity faultaccording to the requirement
Displaymodeswitch
The display mode can be quickly menu mode or the differentvalue modes, and can be debugged convenient
Running
Operationcommandchannels
Three channels:Operation panel given、Control terminals given、Serial communication given. Through various ways switch
Frequencysource
8 kinds of frequency source : Digital given;Simulation voltagegiven;Simulation current given;Pulse given;variety ofspeedPLC; PID;Serial communication given
Inputterminals
Seven digital input terminals,one can be high speed pulse inputFour simulation input terminals,AI0 is potentiometer input,AI1can be both voltage input and current input,both AI2 and AI3 arethe voltage input
Outputterminals
Two digital output terminals,Y1 can be DO high-speed pulseoutput or open collector digital outputOne relay output terminalsTwo simulation output terminals,AO1 can choose 0~20mA or0~10V output
Displayand
keyboard
LEDdisplay
This machine comes with LED keypad,to realize the parametersettings and the status monitoring function
Others
Protectionfunction
Overcurrent protection、Overvoltage protection、Undervoltageprotection、Overheat protection、Overload protection and so on
Choice ofaccessories
External keyboard(you have has two choices about the externalkeyboard: with potentiometer or without potentiometer) ;Brakecomponents;keyboard line to the external
Environment
Use placeIndoor, avoide the direct sunlight,no dust、 corrosive gas、flammable gas、oil mist、water vapor、dripping or salt and so on
Altitude 1000m,please derating when higher than 1000m
DR300 User's manual
12
Ambienttemperature
-10~+40( Please derating when the ambient temperature isbetween +40~+50)
Humidity Less than 95%RH,no condensing
Vibration Less than 5.9m/s2(0.6g)
Storagetemperature
-20~+60
2.5 Product outline;The size of installation holes
2.5.1 Product outline:
Uppercoverplate
lowercoverplate
Input/output hole
Operation panel
Nameplate of inverter
Bottom mouting hole
Figure 2-3 Inverter’s outline drawing
DR300User'smanual
13
Figure 2-4 DR300-S2-0R4G~DR300-T3-7R5G/011P Envelop dimensionsand installation size schemes
Figure 2-5 DR300-T3-011G/015P~DR300-T3-400G/450P Envelop dimensionsand installation size schemes
2.5.2 The size of installation holes
Table 2-4 DR300 The size of inverter installation holes(mm)
Model
Mountingholes
locationsDimensions
Diameter of
mounting holeW1 H1 H W D1 D
DR300-S2-0R4G
120 231.5 255 141 158 171 φ6
DR300-S2-0R7GDR300-S2-1R5GDR300-S2-2R2GDR300-T3-0R4G/0R7PDR300-T3-0R7G/1R5PDR300-T3-1R5G/2R2PDR300-T3-2R2G/4R0PDR300-T3-4R0G/5R5P
DR300 User's manual
14
DR300-T3-5R5G/7R5P 149 256 273 168.5 168.5 182 φ7DR300-T3-7R5G/011PDR300-T3-011G/015P
180 377 396.5 235 219 232 φ7DR300-T3-015G/018PDR300-T3-018G/022P
200 476 496 281 256 259 φ9DR300-T3-022G/030PDR300-T3-030G/037PDR300-T3-037G/045P
200 578 600 353 286 299 φ11DR300-T3-045G/055PDR300-T3-055G/075P
300 620 645 380 297 310 φ11DR300-T3-075G/090PDR300-T3-090G/110P
350 755 780 515 340 350 φ11DR300-T3-110G/132PDR300-T3-132G/160P
450 1010 1055 605 420 430 φ15DR300-T3-160G/185PDR300-T3-185G/200PDR300-T3-200G/220P
450 1155 1200 680 420 430 φ19DR300-T3-220G/250PDR300-T3-250G/280P
600 1210 1250 750 420 430 φ19DR300-T3-280G/315PDR300-T3-315G/355P
700 1210 1250 800 420 430 φ19DR300-T3-355G/400PDR300-T3-400G/450P 700 1210 1250 800 420 430 φ19
Figure 2-6 The size of DR300 series inverter’s keypad
DR300User'smanual
15
Figure 2-7 The size of DR300 series inverter’s large keyboard
F
D C
BA
C
E
Figure 2-8 The size of external reactor
Table 2-5 The outer reactor size table(mm)
Converter model A B C D E F G Mounting holes
Copper barconnection
DR300-T3-075G/090P 160 190 125 161 192 255 195 10*15 φ12
DR300-T3-132G/160P 160 190 125 161 192 255 195 10*15 φ12
DR300 User's manual
16
DR300-T3-200G/220P 190 230 93 128 250 325 200 13*18 φ15
DR300-T3-250G/280P 190 230 93 128 250 325 200 13*18 φ15
DR300-T3-315G/355P 224 250 135 165 260 330 235 12*20 φ14
Note:Special requirements can be customized non-standard
The installation of external DC reactor:The DR300 series inverter, produced by DaYuanGuangSheng Electric Co., Ltd in Wuxi,
users need to remove the short-circuit copper bars between the inverter main circuit terminal P1and (+) when they are installing the external DC reactor,and connect the external DC reactorbetween P1 and (+),the lines connect the reactor terminal and inverter terminal P1 and (+) areno polarity.The short-circuit copper bars between P1 and (+) are no longer in use afterconnecting the reactor.
2.6 The choice of accessories
Table 2-6 DR300 The choice of the inverter accessories
Name Model Function Remarks
Internalbrake unit
Equipped with internal brake unitaccording to the standards of the
015G/018P machine
Internal brake unit inthree-phase
0.75kW~15G/18.5P arestandard configuration
Externalbrake unit
DRBU External brake unit above 018G/022P Optional
LEDoperation
panelDRLE LED display and operate keyboard RJ45 interface
LCDoperation
panelDRLC LCD display and operate keyboard RJ45 interface
Extensioncable DRCAB The standard 8-core cable as the
external keyboard extension cableOptional
Note:If you need the above-mentioned options, please note when ordering.
DR300User'smanual
17
2.7 The daily maintenance of the inverter
2.7.1 The daily care
Due to the influence of environmental temperature, humidity, dust and vibration,the inverter’sinternal device will be aged,the life of the inverter will be reduced and the potential fault of theinverter will occur.So it’s necessary to maintain the inverter periodicity.
Note
Due to the high voltage on the filter capacitor after disconnecting the power,the invertercan not immediately be maintained.Must wait until the charge lamp goes out and the busvoltage does not exceed 36V on the multimeter.
Daily inspection project:
1)Motor running sound is abnormal;2)Whether there was a vibration in the motor running3)Whether the inverter installation environment is changed;4)Whether the cooling fan of the inverter is normal work5)Whether the inverter is overheating.
Daily clean:
1)Always keep the inverter in clean condition;2)Cleaning the dust of inverter effectively,prevent the dust fall into the inverter , especially
the metal powder;3)Effectively eliminates grease on the cooling fan of the inverter.
2.7.2 Regular inspection
Please regularly check places where is difficult to check when running,Regular inspectionproject:
1)Check the duct and clean regularly;2)Check whether the screws have loosened;3)Check whether the inverter to be corroded;4)Check the arc traces on the terminal;5)The insulation test of main loop.Remind:When measureing the insulation resistance with megger(Please ues 500V DC
power supply),disengage the main circuit and the inverter.Do not use the insulation resistance tomeasure the control circuit insulation.Do not have to carry out high-voltage test( It has beencompleted in factory).2.7.3 The replacement of fragile device
Cooling fan and electrolytic capacitor are the fragile devices of the inverter,Its life is closerelated to the environment and the maintenance condition.The general life is:
Life time
Fan 2~3years
DR300 User's manual
18
Electrolytic capacitor 4~5years
Users can determine the replecement periodaccording to the running time.1)Cooling fan
Possible causes of damage:Bearing’s wear、Blade’s aging.Criterion:Whether the fan blades have cracks,Boot sound is abnormal vibration.
2)Filtering electrolytic capacitorPossible causes of damage:Poor quality of input power、high ambient temperature,frequectload transition、electrolyte aging.Criterion:Whether there isliquid leakage、Whether the safety valve has protruding ,
Determination of the electrostatic capacitance,Determination of insulation resistance.
2.7.4 Storage of the inverter
For the inveter, temporary storage and long-term storage must note the following:1)As far as possible to make the original packing.2)Long-term storage will lead to the deterioration of electrolytic capacitors,Must ensure the
power-on at least once within 2 years,the power-on time shoule be at least 5 hours,Theinput voltage regulator must be slowly rised to standard value.
2.8 Warranty description of the inverter
Free warranty refers only to the inverter.1)In normal use, fault or damage, my company is responseble for 18 months warranty〔From thedate of manufacture factory,on the bar code shall perbail〕,more than 18 months, will charge areasonable of the cost of maintenance;2)In 18 months, if has the following circumatance, should charge some of the cost ofmaintenance:
a) Users don’t use the provisions in the manual, bring machine damage ;
b) Due to the fire,flood,earthquake and damage caused by force majeure;c) Damage caused by the abnormal use of the inverter.
The service fees are according to the manufacturer uniform standard,if there is acontract, all should be according to the contract principle priority.
2.9 Selection guidance
It must be clear that the technical requirements of the system on frequency control;inverterapplications;the specific circumstances and the load characteristics when you select the inverter,taking deep consideration of the adaptation motor, the output voltage, rated output current andother factors,and then choose to meet the requierments of the model and determine the runningmode.
Basic principle: the motor’s rate load current must not exceed the rated current of theinverter.Under normal circumatances according to the instructions to select the motor capacity,Attention to the rated current of the motor and the inverter.Inverter overload ability is
DR300User'smanual
19
meaningful for the process of starting and stopping.Any short-system overload duringoperation will cause the change of the load speed, please consider to enlarge the next level. Ifyou require a relatively high speed precision , please choose the DR500 modular vector controlseries
Type of fan and pump:Overload ability is in the low required,because the load torque isdirectly proportional to the square of the speed,so the load is lighter at the low speed(Except forthe Roots blower)and because there is no special requirements on the speed precision for thiskind of load,choose the square torque V/F.
Constant torque load:most load with constant torque characteristics,but the requirementson the speed accuracy and the dynamic performance are generally not high.Such as extruders,mixers, conveyors, factory transport trams, cranes and translation agencies.The multi-V/Foperation mode can be selected during selecting the model.
2.10 Guide of brake component selection
Table 2-7 is guide data,Users can choose a different resistor and power according to theaccording to the actual situation〔But the resistance must not be less than the recommendedvalue in the table, the power can be more.〕,the selection of the braking resistor is according tothe power of the generator in the practical application system, it’s related to the systeminertia, deceleration time, and the energy of potential energy load , Users need to selectaccording to the actual situation.The greater the inertia of the system, the shorter thedeceleration time, and the more frequent of the brake, braking resistor need to select the higherpower and the smaller resistance.
2.10.1 Selection of resistance
Regenerative energy is almost entirely consumed by the braking resistor during braking.The braking power can be calculated according to the formula:U*U/R=Pb.U—The braking voltage of the stable brake system(Different systems are not the same, and 380VAC systems generally take 700V)Pb----Braking power(Different systems are not the same for 380 VAC systems generally take 700V)Pb----- braking power
2.10.2 The power of the braking resistance choice
Theory, the power of braking resistor and braking power, but given the drop amounted to70% .According to the formula can be:0.7*Pr=Pb*D
Pr---- Resistance of power D---- Braking frequencyElevator ----- 20% to 30%
Open book and take the volume ---- 20 ~ 30%Centrifuge ------- 50% to 60%Occasional brake load ---- 5%
Generally the 10%
DR300 User's manual
20
Table 2-7 DR300 series inverters braking component selection table
Inverter Models
Brakingresistancerecommendpower
Braking resistancerecommend resistance Brake unit Remarks
DR300-S2-0R4G 80W ≥200Ω
Standardbuilt-in
UnlessOtherwiseSpecified
Herein
DR300-S2-0R7G 80W ≥150ΩDR300-S2-1R5G 100W ≥100ΩDR300-S2-2R2G 100W ≥70ΩDR300-T3-0R4G/0R7P 200W ≥360ΩDR300-T3-0R7G/1R5P 200W ≥360ΩDR300-T3-1R5G/2R2P 400W ≥180ΩDR300-T3-2R2G/4R0P 400W ≥180ΩDR300-T3-4R0G/5R5P 800W ≥90ΩDR300-T3-5R5G/7R5P 1.0kW ≥60ΩDR300-T3-7R5G/011P 1.0kW ≥60ΩDR300-T3-011G/015P 2.0kW ≥30ΩDR300-T3-015G/018P 2.0kW ≥30ΩDR300-T3-018G/022P 2.0kW ≥30Ω external
DRBU-045DR300-T3-022G/030P 4.0kW ≥15Ω externalDR300-T3-030G/037P 4.0kW ≥15Ω externalDR300-T3-037G/045P 4.0 kW ≥15Ω externalDR300-T3-045G/055P 6.0 kW ≥10Ω externalDR300-T3-055G/075P 8.0 kW ≥7.5Ω external
DRBU-160
DR300-T3-075G/090P 8.0 kW ≥7.5Ω externalDR300-T3-090G/110P 4.5 kW×2 ≥8Ω×2 externalDR300-T3-110G/132P 5.5 kW×2 ≥8Ω×2 externalDR300-T3-132G/160P 6.5 kW×2 ≥8Ω×2 externalDR300-T3-160G/185P 16kW ≥2.5Ω externalDR300-T3-185G/200P 18kW ≥2.5Ω external
DRBU-315
DR300-T3-200G/220P 20 kW ≥2.5Ω externalDR300-T3-220G/250P 22 kW ≥2.5Ω externalDR300-T3-250G/280P 12.5 kW×2 ≥2.5Ω×2 externalDR300-T3-280G/315P 14kW×2 ≥2.5Ω×2 externalDR300-T3-315G/355P 16kW×2 ≥2.5Ω×2 externalDR300-T3-355G/400P 17kW×2 ≥2.5Ω×2 external
DRBU-560DR300-T3-400G/450P 14 kW×3 ≥2.5Ω×3 externalNote: x2 said two braking resistance parallel use, with x2 x3
DR300User'smanual
21
Chapter 3 Mechanical and electrical installation
3.1 Mechanical Installation
3.1.1 Installation Environment,
1〕Environmental temperature: the ambient temperature has a great influence, should alwayskeep the environment temperature under the inverter’s allowed temperature range (-10 to 50Degrees Celsius).
2〕When inverter installed in flame retardant surface, it need to have enough space ,because when inverter working, it is easily to produce a lot of heat and screw vertically on theinstallation bearings.
3〕Please install in the place is not easy to vibration which should be no more than 0.6g ,special attention away from the punch equipment.
4) Avoid installed in direct sunlight, moisture, drops a place.5) Avoid installed in the air with corrosive;flammable or explosive gas places.6) Avoid installed in place of greasy dirt, dust, metal dust.
A A
B V100mm
B V100mm
V100mm
Figure 3-1 DR300 inverter installation schemes
Description: A Size can not be considered when the inverter power is not more than 22KW.When more than 22KW A greater than 50 mm
Description: When the inverter upper and lower installation, please install the insulation baffleicon.
Power levelMounting dimensions
B A
DR300 User's manual
22
≤15kW ≥100mm Can not make the requirements
18.5kW-30kW ≥200mm ≥50mm
≥37kW ≥300mm ≥50mm
The heat dissipation problem should be taken into consideration in mechanical installation , Soplease note the following:
1) Please install the inverter vertically, easy to heat up distributing. But can not be inverted.If the cabinet has more inverters, preferably side by side. Where the upper and lower installation,please refer to Figure 3-1 . Install insulation deflector.
2) Installation space in accordance with Figure 3-1 to ensure enough space for heatdissipation of the inverter. Considering the other components of the cabinet cooling when thelayout.
3) Mounting bracket must be flame-retardant material.4) For applications of metal dust, recommended heat sink cabinet installation. The sealed
cabinet space should be as large as possible.
3.1.2 Under cover removal and installation
7R5G and DR300 series inverter with a plastic shell, the demolition of the plastic casecover (see Figure 3-2). The tools available will cover the hook to the top to the inside force.
Lowercover plate
Hook
Hook slot
Symmetry theinside with the beat
Figure 3-2 plastic shell cover demolition plans
NOTICES!
Under cover removal to avoid the cover off may cause harm to equipment andperson!
011 G / 015 P and above the sheet metal shell DR300 series inverter, sheet metal shell
DR300User'smanual
23
cover plate removal refer to Figure 3-3.It can be used tools directly to loosen screw under thecover plate.
Fixingscrews
Undercover
Figure 3-3 sheetmetal shell cover demolition plans
3.2 Electrical Installation
3.2.1 Peripheral electrical components selection guidance
Table 3-1 DR300 inverter peripheral electrical components selection guidance
Converter modelOpen space
(MCCB)(A)
Recommended
contactor(A)
Recommendedinput side The maincircuit wires(mm2)
The main circuitwires(mm2)
Recommendedoutput side Themain circuit wires(mm2)The main circuitwireswire(mm2)
Recommendedcontrol Returnconductor (mm2)Return conductor(mm2)
DR300-S2-0R4G 16 10 2.5 2.5 1.5
DR300-S2-0R7G 16 10 2.5 2.5 1.5
DR300-S2-1R5G 20 16 4 2.5 1.5
DR300-S2-2R2G 32 20 6 4 1.5
DR300-T3-0R4G/0R7P 10 10 2.5 2.5 1.5
DR300-T3-0R7G/1R5P 10 10 2.5 2.5 1.5
DR300-T3-1R5G/2R2P 16 10 2.5 2.5 1.5
DR300 User's manual
24
DR300-T3-2R2G/4R0P 16 10 2.5 2.5 1.5
DR300-T3-4R0G/5R5P 32 25 4 4 1.5
Converter modelOpen space
(MCCB)(A)
Recommended
contactorr(A)
Recommendedinput side Themain circuitwires(mm2)
Recommendedoutput side The
main circuitwires (mm2)
Recommendedcontrol Return
conductor (mm2)
DR300-T3-5R5G/7R5P 40 32 4 4 1.5
DR300-T3-7R5G/011P 63 40 4 4 1.5
DR300-T3-011G/015P 63 40 6 6 1.5
DR300-T3-015G/018P 100 63 6 6 1.5
DR300-T3-018G/022P 100 63 10 10 1.5
DR300-T3-022G/030P 125 100 16 10 1.5
DR300-T3-030G/037P 160 100 16 16 1.5
DR300-T3-037G/045P 200 125 25 25 1.5
DR300-T3-045G/055P 200 125 35 25 1.5
DR300-T3-055G/075P 250 160 50 35 1.5
DR300-T3-075G/090P 250 160 70 35 1.5
DR30-0T3-090G/110P 350 350 120 120 1.5
DR300-T3-110G/132P 400 400 150 150 1.5
DR300-T3-132G/160P 500 400 185 185 1.5
DR300-T3-160G/185P 600 600 150*2 150*2 1.5
DR300-T3-185G/200P 600 600 150*2 150*2 1.5
DR300-T3-200G/220P 600 600 150*2 150*2 1.5
DR300-T3-220G/250P 800 600 185*2 185*2 1.5
DR300-T3-250G/280P 800 800 185*2 185*2 1.5
DR300-T3-280G/315P 800 800 150*3 150*3 1.5
DR300-T3-315G/355P 800 800 150*4 150*4 1.5
DR300-T3-355G/400P 1000 1000 150*4 150*4 1.5
DR300-T3-400G/450P 1000 1000 150*4 150*4 1.5
3.2.2 Outside the use of electrical components
DR300User'smanual
25
Table 3-2 DR300 inverter peripheral electrical components instructions
Accessoryname
Installation location Functional Description
Air switch Input circuit front-end Downstream equipment over-current time-divisionoff the power.
Contactor Between the open space andthe inverter input side
The inverter pass off operations should (per minuteless than twice) to avoid frequently power off and onoperation by the contactor or start directly .
Ac inputreactor Inverter input side
1) Improve the power factor of the input side;2) The effective elimination of the higher harmonicof the input side to prevent damage due to voltagewaveform distortion caused by other devices;3) The elimination of power unbalance caused by theinput current imbalance.
EMC inputfilter Inverter input side
1) To reduce the external inverter conduction andradiation interference;2) Reduce conducted interference, improveanti-jamming capability of the inverter from thepower supply terminal to the inverter.
DC reactor Between the inverterrectifier and inverter
1) Improve the power factor of the input side;2) Improve the efficiency of the inverter machine andthermal stability.3) Effectively eliminate the higher harmonics of theinput side of the inverter to reduce the externalconduction and radiation interference.
Ac outputreactor
Between the inverter outputside and the motor. Near the
inverter installation.
The inverter output side is generally more higherharmonics. When the motor and the drive distance,the lines were in the large distributed capacitance. Aharmonic in the loop may have a resonance to bring
the impact of the two aspects:1) Destruction of the motor insulation performance, along time will damage the motor.2) Produce a greater leakage current, and causefrequently inverter protection. Inverter and the motora distance of more than 100m, it is recommended
that the installation of the output AC reactor.
3.2.3 Connection mode
DR300 User's manual
26
Breaking Resistor
IMSingle-phase220V inputpower
X3X4X5X6X7
COM
485 InterfaceA-
A+
Ground
J10:AI1J7:A01
+10V
AI1
AI3
GND
PE
A02GND
Y1COM
Y2
+24V
EB(Fault contact output)
0-10V/0-20mA0-10V
Analog Output 0-10V/0-20mA
high-speed pulse output oropen collector output optional
open collector output
1.1(-) (+) PB
UVW
DR300
1.2
QF
0-10V
A01Analog Output 0-10V
EC
EA
AI2
X1X2
Multifunction digitalinput
2J10
J7
V I
V I
PLC
34567
1
log Input
Figure 3-4 DR300-S2-0R4G/DR300-S2-0R7G/DR300-S2-1R5G/DR300-S2-2R2GSingle phase inverter wiring diagram
Note:1) Terminal is the main circuit terminals, Terminal is control circuit terminal.2) 0.4kW ~ 2.2 kW built-in brake unit optional.3) Braking resistor according to the user need to choose the Selection Guide, see thebraking resistor.4) Signal lines and power lines must be routed separately, if the control cables and powercables cross, as far as possible to make them according to the 90-degree angle cross. Theanalog signal line is best to use shielded twisted pair, power cable selection shieldedthree-core cable (its specifications than the average of the motor cable freshman profile)or to comply with the user manual of the inverter.
DR300User'smanual
27
Breaking Resistor
IMThree-phase380V inputpower
X3X4X5X6X7
COM
485 InterfaceA-
A+
Ground
J10:AI1J7:A01
+10V
AI1
AI3
GND
PE
A02GND
Y1COM
Y2
+24V
EB(Fault contact output)
0-10V/0-20mA0-10V
Analog Output 0-10V/0-20mA
high-speed pulse output oropen collector output optional
open collector output
RS
(-) (+) PBUVW
DR300
T
QF
0-10V
A01Analog Output 0-10V
EC
EA
AI2
X1X2
Multifunction digitalinput
2J10
J7
V I
V I
PLC
34567
1
Analog Input
Figure 3-5 DR300-T3-1R5G/2R2P~DR300-T3-015G/018PNote:1) Terminal the main circuit terminals, control circuit terminal.2) 0.75kW ~ 2.2kW Built-in brake unit optional 4.0kW ~ 15kW built-in brake unit for thestandard configuration, no additional installation.3) 7.5kW ~ 55kW built-in DC reactor.4) Braking resistor according to the user need to choose the Selection Guide, see the brakingresistor.
DR300 User's manual
28
Breaking Resistor
IMThree-phase380V inputpower
X3X4X5X6X7
COM
485 InterfaceA-
A+
Ground
J10:AI1J7:A01
+10V
AI1
AI3
GND
PE
A02GND
Y1COM
Y2
+24V
EB(Fault contact output)
0-10V/0-20mA0-10V
Analog Output 0-10V/0-20mA
high-speed pulse output oropen collector output optional
open collector output
RS
P1 (+) (-)UVW
DR300
T
QF
0-10V
A01Analog Output 0-10V
EC
EA
AI2
X1X2
Multifunction digitalinput
2J10
J7
V I
V I
PLC
34567
1
Analog Input
Breaking Unit
Figure 3-6 DR300-T3-018G/022P~DR300-T3-400G/450P
DR300User'smanual
29
3.2.4 Main Circuit Terminal And The Wiring
Danger Be sure to turn off the switch before wiring to avoid electrical shock injury WIiring must be performed by qualified professional workers to avoid a damage to the inverter and the
workers. The terminal must be grounded .Otherwise it may have the risks of fire and electric shock
1) Main circuit terminal description of single phase inverter:
2) Main circuit terminal description of three phase inverter
Symbol Name Function DescriptionR、S、T A three-phase power input terminal Connector for three phase of AC line power
(+)、(-)Positive, negative DC bus
terminal018G /022P and above the external brake unitconnection point
(+)、PB Braking resister terminal015G / 018P and below braking resistor connectionpoint
P1、(+)External DC reactor connectionterminal External DC reactor connection point
U、V、W Output terminal of the inverter Connector for three phase electromotor
Ground terminal
the third method of grounding for 220V
and special grounding for 380 V of Electrical
Engineering Regulations.
Caution
Confirm the input power coresponding with the converter rating, or it may damage the inverterBe sure the motor corresponds with the inverter, Otherwise it may cause the protection of the inverter and
even damage of the motor Do not connect power to U,V.W to avoid the damage of inverter Never connect braking resistor to DC bus(+)and(-),Or it may cause the risk of fire
Symbol Name Function Description
L1、L2Single phase power supple inputterminal
Single phase AC power supply connection point 220V
(+)、(-)(+)、 (-) terminals of a DC
bus Common DC bus input
(+)、PB Braking resister terminal Connector for braking resistor (optional).U、V、W Output terminal of the inverter Connector for three phase electromotor
Ground terminalthe third method of grounding for 220Vand special grounding for 380 V of Electrical EngineeringRegulations.
DR300 User's manual
30
3)Precautions on Wiring
A、power supply of L1、L2 or R、S、T:Inverter input side wiring, phase sequence is not required.
B、DC bus ( + ), ( -).Note that just after power DC bus ( + ), ( -) terminal and residual voltage,After the
lights go out and confirmed to be CHARGE less than 36V before contact, otherwise theremaybe the danger of electric shock.
018G /022P and above the external brake component selection, ensure that ( + ), ( -)polarity cannot be reversed, otherwise it will cause damage to the inverter or maybe fire.
Braking unit wiring length should not exceed 10m. Twisted pair or closely parallelwiring is needed.
Directly connected with the braking resistor in the DC bus is not allowed,it may causedamage or fire inverter.
C、Braking resistor connection terminal ( + ), PB:015G / 018P and below and confirm have built-in braking unit models, its braking
resistor connection terminal is effective.Braking resistor selection reference recommended values and the wiring distance
should be less than 5m. Otherwise it may lead to broken inverter.D、 DC reactor connecting terminal P1, ( + )::
018G /022P and above power inverter, reactor external, assembly, the P1( + ) terminalis connected between the sheet removed, reactor connected to the two terminal.E、The output side of the converter U, V, W:
The output side of the converter is connected to the capacitor or surge absorbers,otherwise it will cause a inverter protection frequenly, even to damage the inverter.
Ifmotor cable is too long, due to the influence of distributed capacitance, easy to produceelectrical resonance, thereby it may cause the motor insulation damage or produce largerleakage current to inverter over-current protection. If the motor cable length is longer than100m,you must install AC output reactor.F、The ground terminal PE:
Terminal must be reliable grounding, grounding resistance value must be less than0.1ohm. Otherwise it will cause abnormal work or even damage equipment. The groundterminal and N terminal of power supply zero line can not be shared.
3.2.5 Control Terminals and Wiring
1)Control circuit terminal plan as follows:
Figure 3-7control circuit terminal layout
2)Control terminal function
DR300User'smanual
31
Table 3-3 DR300inverter control terminal function
Category Terminalsymbol
Terminal name Function description
Powersupply
+10V-GND External10V power
Offer + 10V power supply, themaximum output current:10mAgenerally serves as externalpotentiometer power supply,potentiometer resistance range:1K ~5Kohm ohm
24V-COMExternal +24V
power
Offer +24V power, generally used as adigital input and output terminal powersupply and an external sensor supplyMaximum output current:200mA
simulationInput
AI1-GNDAnalog input
terminal 1
1、Input range: DC0V ~10V /0mA~20mA, controlled by the board ofJ10jumper selection decision.2、Input impedance: voltage input20Kohm, current input500 ohm.
Category Terminalsymbol
Terminal name Function description
Digitalinput
AI2-GNDAnalog input
terminal 21、Input voltage range:DC 0V~10V2、Input impedance :20kΩ
AI3-GNDAnalog input
terminal 31、 Input voltage range:DC 0V~10V2、Input impedance:20kΩ
X1-COM Digital input11、Optical isolation2、Input impedance:3.3k ohm
X2-COM Digital input2
In addition to X1 ~ X6features, can alsobe used as a high speed pulse inputchannel.Maximum input frequency:50kHz
Analogoutput
X3-COM Digital input3
Multi function input terminal end
X4-COM Digital input4X5-COM Digital input5X6-COM Digital input6
X7-COMHigh speed pulse
input terminal
PLCMulti function input
common terminal
AO1-GND Analog output 1
AO1 by the control board J7jumperchoice determines the voltage / currentoutput. AO2voltage output.Output voltage range:0V~10VOutput current range:0mA~20mA
DR300 User's manual
32
AO2-GND Analog output 2
Optically coupled isolation, opencollector output,Programmable defined as functions ofoutput terminal.Output voltage range:0V~24VOutput current range:0mA~50mA
Digitaloutput
Y1-COMMulti function digital
outputContact actuation capability:AC250V,3A,COSφ=0.4.DC 30V,1AY2-COM
The normally closedterminal
Relayoutput
EB-ECThe normally open
terminalThe 485interface standard
EA-EC
Secondaryinterface
A+/A-The 485
communicationinterface
3)Control terminal description:
A、The analog input terminal:Because of the weak analog voltage signals are particularly susceptible to external interference,
so generally need to use shielded cable and wiring, short distance as far as possible, notexceeding 20m, as shown in figure 3-9. In some analog signal by serious interference of theoccasion, the analog signal source side need to add filter capacitor or a ferrite core, as shown infigure 3-10.
+10V
GND
DR300less than 20 meters
potenti-ometer AI1
Figure 3-8 Analog input terminal wiring diagram
DR300User'smanual
33
AI1
GND
DR300To pass through or around the same direction with the same 2-3 turn
Ferrite core
Externalanalogsource
0.22uF、50V
C
Figure 3-9 Analog input terminal processing wiring diagramB、The digital input terminal:
It’s generally needed for shielded cables and wiring, and distance should be short asfar as possible, not exceeding 20m. When we use the active drive, need to take the necessarypower crosstalk filtering measure. Contact control mode. is suggested
C、Digital output terminals:Digital output terminal is connected with the load directly connected to the Y1and 24V,
inside the machine has continued flow absorption circuit. The load current is less than50mA.If the load is too large, please go through the relay transition.
Dry contact common cathode connection mode
+24V+24V
PLCK1
K7
X1
X7
COM
3.3K
3.3K
Inverter control board
Figure 3-10 Dry contact common cathode wiring diagram
This is one of the most commonly used connection mode. If you use an external powersupply, you must put + 24V and PLC short circuit between the COM and COM sheet and a shortcircuit between the sheet removed, the external power of positive electrode in the PLC, externalpower supply negative in COM. Dry contact common anode connection mode
DR300 User's manual
34
+24V
K1
K7
X1
X7
COM
3.3K
3.3K
Inverter control board
PLC
+24V
Figure 3-11 Stem junction common anode wiring diagram
The connection method must take + 24V and PLC short circuit between the sheet removed,
then put PLC and COM together.
The source wiring mode
+24V+24V
PLC
X1
X7
C0M
3.3K
3.3K
Inverter control board
+VCC
信号
0V
NPN
3.3
The external controller
Figure 3-12 Source wiring modeThis is one of the most commonly used connection mode. If you use an external power
supply, must put + 24V and PLC short circuit between the sheet removed, the external power of
positive electrode in the PLC, external power supply negative in COM.
The drain wiring mode
DR300User'smanual
35
+ 2 4 V
X 1
X 7
C O M
3 .3 K
3 .3 K
In v e rto r c o n tro l b o a rd
P L C
+ 2 4 V
3 .3
P N P
信 号
0 V
+ V C C
T h e e x te rn a l c o n tro lle r
Figure 3-13 Drain wiring modeThe connection method must ta ke + 24V and PLC short circuit between the sheet removed,
+24V and external controller of the termination of public together, at the same time put PLC andCOM together.
D、Digital output terminals:When the digital output terminal to drive the relay, the relay coil arranged on both sides
should absorb diode. Otherwise easily lead to24V DC power supply damage.Note: must be properly installed absorption of the polarity of the diode. As shown in Figure
3-15or when the digital output terminal output, will immediately24V DC power supply to burn.
Relay Diode
+24V
DR300 Y1
COM
Figure 3-14 Digital output terminal wiring diagram
DR300 User's manual
36
Chapter 4 Operating And Display
4.1 Operation and display interface
Operation panel, the transducer function parameter modification, inverter working statemonitoring and inverter control ( start, stop ) and other operations, its appearance and functionarea as shown below:
Operation key Stop/Reset key
Confirm key
Knob
Data displayarea
Unit indicating lamp
Cancel keyIncrement/Decrement key
Shift key
Multi-function key
Figure 4-1With potentiometer with keyboard diagram
4.1.1 Function indicator description
ALM:Malfunction indicator light, when a fault occurs on the inverter, the light is on,normally is out.
RUN:When the light is out,the inverter is shutdown, When the light is on,the inverter isrunning.
Hz:Unit of frequency, light shows the corresponding parameter values of the units.A :Unit of current.%:Percentage.V:Unit of voltage.
4.1.2 Digital display zone
A total of ten digital tube, mark of two lines, can simultaneously display the contents of two.Can display the frequency setting, the output frequency, a variety of monitoring data and thealarm code.
DR300User'smanual
37
4.1.3 Keyboard button description table :
Table 4-1keyboard function table
Button Name Function
MKMulti function
keys
Programmable touch, positive / negative input switchingfunction, function code display switching, start / stopcommand to switch, free parking and emergency stop, thespecific function of a reference set of fifth chapter functioncode F0.26
ENTER Confirm key Step into the menu screen, set parameters confirmation
Λ Ascending keyFunction code, menu group, or set parameters valueincrement. Increase the effective reference digital input data
V Decrement keyFunction code, menu group, or set parameter values decline.Reducing the current effective reference digital input data
<< Shift keyIn shutdown show interface and operation display interface,cyclic selection display parameters; parameter changes intime, can select the parameters of the modified bit
ESC Switch keyReturn to the previous state, removal of the currentparameter modification
RUN Operation key In keyboard mode, used in operation
STOP/RESET Stop / resetThe running state, press this button can be used to stopoperation; fault alarm state, can be used to reset operation
The analogpotentiometer The input analog implementation speed function
4.2 View Function Code; Description of Modify Method
DR300converter operation panel uses three levels of menu structure parameter settingsand other operations
The three level menu respectively: functional parameter group ( menu ) to function code( the two level menu ) to function code set value ( the three level menu ). Operational processesas shown in figure 4-3.
50.00 50.00
ESC
ESC
F0 F0.12 050.00
ENTER
ESC ESC
ENTER
One level system Two level system Three level system
Change parameters Change the function code View the function code value
Figure 4-2 Three menu operation flow chartNote: in the three level menu operation, press the ESC key or ENTER key to return to the
two level menu. The difference is: press the ENTER key will set the parameters are saved afterreturning to the two level menu, and automatically transferred to a function code; and press the
DR300 User's manual
38
ESC key is returned directly to the two level menu, not storage parameters, and returns to thecurrent function code.
For example: the function code F0.13changed from 10.00Hz set to15.00Hz
50.00 H0 F0.13
010.00015.00F0.13F0
ENTER
ESC
ESC ENTER
F0 ENTER
Figure 4-3 Parameter editing operation flow chartIn the third level menu state, if the parameter is not flashing, indicates that the feature codes
cannot be modified, may cause:1〕The function code can not modify the parameters. If the actual detection parameters, log
parameters;2〕The function code in the operating condition may not be modified, to be stopped only
after the modification;
4.3 State parameter check method
To stop or run state, can display a variety of state parameters.Under operation state, press < < key sequence switching display F4.19 ~ F4.22selected
parameters.
4.4 Password setting
Converter provides the user password protection function, when the F4.31 is set to non-zero,i.e. for the user password, exit function code edit password protection is effective, press theENTER key again, will display" ... ", must enter the correct password, can enter the menu,otherwise inaccessible. If you want to cancel the password protection function, and only throughthe entry of the password, and set the F4.31 to0.
4.5 Keyboard lock and unlock
Set F4.25 to a value other than 0, namely the lock effectively; while holding down the" < <"key and " V " button more than 2 seconds to unlock.
DR300User'smanual
39
Chapter5 Function Parameter List
Symbols in the menu are described below:“”:That code parameters in the inverter operation status can change;“〇”:That code parameters in the inverter operation status it cannot be changed;“”:The value of this parameter is the record of the actual detection value, status it cannot be
changed;“X” : This parameter is the "factory parameters", limited to the manufacturer settings to
prohibit users from operating.Parameter table
Functioncode
Name Setting rangeFactory
valueattributes Address
F0 group: basic functions
F0.00Type
selection0:G-type1:P-type
Typedetermination
〇 0x0000
F0.01Function
codeprotection
0:Keyboard, communicationport can be modified1:Keyboard can be modified2:Communication port can bemodified3:Keyboard orcommunication port bothcan not be modified
0 〇 0x0001
F0.02
Thekeyboarddisplaymode
0:Basic menu mode1:Quick Menu mode2 : Non-factory value offunction code menu mode(only LCD keypad)
0 0x0002
F0.03Drivemode
selection
0 : V / F, coordination andcontrol (VF)1:Non-encoder feedbackvector control (SVC)
0 〇 0x0003
F0.04Application
macrosselection
0:Universal Macro1:Special macro2:PID application macros3 : The program runsapplication macros4:Modbus communicationapplication macro
Typedetermination
〇 0x0004
F0.05Run the
commandgiven
0:Local keyboard1:External terminal2:PC communication
0 〇 0x0005
DR300 User's manual
40
options 3 : Local keyboard andexternal terminal4 : Local keyboard and PCcommunication
Functioncode
Name Setting range Factory value attributes Address
5:External terminal and PCcommunication
F0.06Terminalcommandoptions
0:Two-wire mode 11:Two-wire mode 22:Three-wire mode 13:Three-wire mode 2
0 〇 0x0006
F0.07Speed given
ways
0:The main speed1:Auxiliary speed2 : The main speed andauxiliary speed3 : The main speed minusauxiliary speed4:The main speed and( themain speed plus auxiliaryspeed)switch5:The main speed and( themain speed minus auxiliaryspeedswitch6: Auxiliary speedand ( the main speed plusauxiliary speed)switch7: Auxiliary speedand ( the main speed minusauxiliary speed)switch8:MAX The main speed、Auxiliary speed9:MIN The main speed、Auxiliary speed10:The main speed multiplyauxiliary speed
0 〇 0x0007
F0.08Main speedgiven ways
0:The main digital frequency1 : AI0 ( Keyboard
1 〇 0x0008
DR300User'smanual
41
potentiometer)2:AI13:AI24:PF(X7)5:PLC6:PID7:Multi-segment speed
F0.09Auxiliary speed
given ways
0:Auxiliary digital frequency1 : AI0 ( Keyboardpotentiometer)2:AI13:AI24:PF(X7)5:PLC6:PID7:Multi-segment speed
0 〇 0x0009
F0.10Auxiliary speedrange selection
0:Relative to the maximumfrequency1:Relative to the main speed
0 0x000A
F0.11Auxiliary speed
range0.00~100.00 100.00% 0x000B
F0.12The main digital
frequency0.00~Fmax 50.00Hz 0x000C
F0.13Auxiliary digital
frequency0.00~Fmax 50.00Hz 0x000D
F0.14
Positive andnegative
direction ofselection
0:Forward1:Reverse
0 0x000E
F0.15Acceleration anddeceleration time
dimension
0:sec1:min
0 〇 0x000F
F0.16Acceleration
time 10.00~600.00
Typedetermination
0X0010
F0.17Deceleration
time 10.00~600.00
Typedetermination
0x0011
DR300 User's manual
42
Functioncode
Name Setting range Factory value attributes Address
F0.18Jog digitalfrequency
0.00~Fmax 5.00Hz 0x0012
F0.19Jog accelerationtime
0.00~600.00 6.00s 0x0013
F0.20Jog decelerationtime
0.00~600.00 6.00s 0x0014
F0.21 Carrier frequency 1.000~16.000Typedetermination
0x0015
F0.22The maximumfrequency
Fmax:0.01~600.00 50.00 Hz 〇 0x0016
F0.23Upper limitfrequency sourcesetting
0:Digital setting1:AI0 ( Keyboardpotentiometer)2:AI13:AI24:PF(X7)
0 〇 0x0017
F0.24The maximumfrequency
Fup:Fdown~Fmax 50.00 Hz 0x0018
F0.25 Lower frequency Fdown:0.00~Fup 0.00 Hz 0x0019
F0.26The definition ofthe multifunctionkey
0:No function1:Positive / negativeinput switchingfunction2:Jog run function3 : Function codedisplay switch4 : Start and stopcommand sourceswitch5:Free Parking6 : Emergency stop(the fastest Parking)
2 0x001A
F0.27Prohibit reversecontrol
0:Allow reverse1:Prohibit reverse
0 〇 0x001B
F0.28Restore the factorysettings
0:Invalid1 : Parameterrecovery mode 1( Does not includeF2.11~F2.30 、
F3.10~F3.21)2 : Parameterrecovery mode 2
0 〇 0x001C
DR300User'smanual
43
( includeF2.11~F2.30 、
F3.10~F3.21)3:Clear the historyinformation
F0.29Parametermodification mode
0:The modifiedaddress- unchangedmodel1:The modifiedaddress-plus-onemodel
1 0x001D
F1 Group: motor, the torque boost
F1.00 Motor model
0 : AC inductionmotor1:AC synchronousmotor
Typedetermination
〇 0x0020
F1.01 Motor rated power 0.40~450.00Typedetermination
〇 0x0021
F1.02 Motor rated voltage 60~660Typedetermination
〇 0x0022
F1.03 Motor rated current 0.1~1000.0Typedetermination
〇 0x0023
F1.04Motor ratedfrequency
20.00~600.00Typedetermination
〇 0x0024
F1.05 Motor nominal speed 1~60000Typedetermination
〇 0x0025
F1.06Motor connectionmethod
0:Y1:Δ
Typedetermination
〇 0x0026
Functioncode Name Setting range Factory value attributes Address
F1.07motor rated powerfactor
0.50~0.99Typedetermination
〇 0x0027
F1.08No-load excitationcurrent I0
0.1~1500.0Typedetermination
〇 0x0028
F1.09 Rated torque current 0.1~1500.0Typedetermination
〇 0x0029
F1.11 Rotor resistance R2 0.01~300.00Typedetermination
〇 0x002B
F1.12Stator leakageinductor (L1)
0.1~3000.0Typedetermination
〇 0x002C
F1.13Mutual inductanceL2
0.1~3000.0Typedetermination
〇 0x002D
F1.14The parametersself-identification
0:Not identification1:Motor stationaryself- identification
0 〇 0x002E
DR300 User's manual
44
2:Motor rotation self-identification
F1.15 V/F Torque boost
0: Straight line1~4:Fan and waterpump lift curve5: Any V / F curve
5 0x002F
F1.16 V/F voltage1 0.00~100.00Typedetermination
0x0030
F1.17 V/F frequency1 0.00~100.00Typedetermination
0x0031
F1.18 V/F voltage2 0.00~100.00Typedetermination
0x0032
F1.19 V/F frequency 2 0.00~100.00Typedetermination
0x0033
F1.20 V/F voltage 3 0.00~100.00Typedetermination
0x0034
F1.21 V/F frequency 3 0.00~100.00Typedetermination
0x0035
F1.22 V/F voltage 4 0.00~100.00Typedetermination
0x0036
F1.23 V/F frequency 4 0.00~100.00Typedetermination
0x0037
F1.24 Slip compensation 0.00~200.00 0.00% 0x0038
F1.25Oscillationsuppression gain
0~1000 0 0x0039
F1.26Over-modulationgain
0~1000 0 0x003A
F1.27 Carrier ways
0:Fixed carrier ways1:Automaticallyadjusting carrierways2 : Random carrierways13 : Random carrierways 2
1 0x003B
F1.28Automatic voltageregulator control
0:Invalid1 : The wholeeffective2 : only invalid indeceleration
0 〇 0x003C
F1.29Torque current filtertime
0.00~100.00 0.30s 0x003D
F2: Input terminals
F2.00Terminal input
filter time0~100 50ms 〇 0x0040
DR300User'smanual
45
F2.01General
multifunction InputX1
0~99 1 〇 0x0041
F2.02General
multifunction InputX2
0~99 2 〇 0x0042
F2.03General
multifunction InputX3
0~99 3 〇 0x0043
Functioncode Name Setting range Factory value attributes Address
F2.04General
multifunction InputX4
0~99 6 〇 0x0044
F2.05General
multifunction InputX5
0~99 7 〇 0x0045
F2.06General
multifunction InputX6
0~99 8 〇 0x0046
F2.07General
multifunction InputX7
0~99 0 〇 0x0047
F2.08Terminal input
positive andnegative logic
X4 X3 X2 X10 0 0 0
0 : Positive logicClosed effective /disconnect invalid1:Anti-logic Closedinvalid /disconnectedeffective
0000 〇 0x0048
F2.09X1 Input Delay
Time0.00~300.00 0.00s 0x0049
F2.10X2 Input Delay
Time0.00~300.00 0.00s 0x004A
F2.11AI0 Input filter
time0.00~30.00 0.30s 0x004B
F2.12AI1 Input filter
time0.00~30.00 0.30s 0x004C
F2.13AI2 Input filter
time0.00~30.00 0.30s 0x004D
F2.14 PF Input filter time 0.00~30.00 0.30s 0x004E
F2.15AI0 Minimum
input0.00~10.00 0.20V 0x004F
DR300 User's manual
46
F2.16AI0 Maximum
input0.00~10.00 10.00V 0x0050
F2.17AI0 Minimum
input-100.0~100.0 0.0% 0x0051
F2.18AI0 Maximum
input-100.0~100.0 100.0% 0x0052
F2.19AI1 Minimum
input0.00~10.00 0.20V 0x0053
F2.20AI1 Maximum
input0.00~10.00 10.00V 0x0054
F2.21AI1 Minimum
input-100.0~100.0 0.0% 0x0055
F2.22AI1 Maximum
input-100.0~100.0 100.0% 0x0056
F2.23AI2 Minimum
input0.00~10.00 0.20V 0x0057
F2.24AI2 Maximum
input0.00~10.00 10.00V 0x0058
F2.25AI2 Minimum
input-100.0~100.0 0.0% 0x0059
F2.26AI2 Maximum
input-100.0~100.0 100.0% 0x005A
F2.27 PF Minimum input 0.000~50.000 0.000 kHz 0x005BF2.28 PF Maximum input 0.000~50.000 50.000 kHz 0x005CF2.29 PF Minimum input -100.0~100.0 0.0% 0x005DF2.30 PF Maximum input -100.0~100.0 100.0% 0x005E
Functioncode
Name Setting range Factoryvalue
attributes Address
F3 Group: output terminal FDT
F3.00Y1 Video output
options
0:DO Pulse output1:Y1 Open collectorswitch output
1 0x0060
F3.01Multifunction output
Y10~99 5 〇 0x0061
F3.02Multifunction output
Y20~99 6 〇 0x0062
F3.03 Relay Output R1 0~99 7 〇 0x0063F3.04 Y1 Output delay time 0.0~600.0 0.0s 0x0064F3.05 Y2 Output delay time 0.0~600.0 0.0s 0x0065F3.06 R1 Output delay time 0.0~600.0 0.0s 0x0066F3.07 Analog output AO1 0~99 1 〇 0x0067F3.08 Analog output AO2 0~99 1 〇 0x0068F3.09 Pulse output DO 0~99 1 〇 0x0069F3.10 AO1 Minimum input 0.00~100.00 0.00% 0x006A
DR300User'smanual
47
F3.11 AO1Maximum input 0.00~100.00 100.00% 0x006BF3.12 AO1 Minimum input 0.00~100.00 0.00% 0x006CF3.13 AO1Maximum input 0.00~100.00 100.00% 0x006DF3.14 AO2 Minimum input 0.00~100.00 0.00% 0x006EF3.15 AO2Maximum input 0.00~100.00 100.00% 0x006FF3.16 AO2 Minimum input 0.00~100.00 0.00% 0x0070F3.17 AO2Maximum input 0.00~100.00 100.00% 0x0071F3.18 DO Minimum input 0.00~100.00 0.00% 0x0072F3.19 DO Maximum input 0.00~100.00 100.00% 0x0073F3.20 DO Minimum input 0.00~100.00 0.00% 0x0074F3.21 DO Maximum input 0.00~100.00 100.00% 0x0075F3.22 FDT1 Upper bound 0.00~Fmax 50.00 Hz 0x0076F3.23 FDT1 Lower bound 0.00~Fmax 49.00 Hz 0x0077F3.24 FDT2 Upper bound 0.00~Fmax 25.00 Hz 0x0078F3.25 FDT2 Lower bound 0.00~Fmax 24.00 Hz 0x0079
F3.26 FDT Output options0:Jog is not output1:Jog output
0 0x007A
F3.27Effective control of the
virtual terminal
Bits: inputterminals X0:The actual terminaleffective1:Virtual terminaleffective10: Outputterminals Y0:The actual terminaleffective1:Virtual terminaleffective
00 〇 0x007B
Functioncode
Name Setting range Factoryvalue
attributes Address
F4 group: Start and stop button to display
F4.00Startup mode
selection
0 : Started by the startingfrequency1:Started after DC injectionbraking2:Started by rotational speedtrack
0 〇 0x0080
F4.01 Starting frequency 0.00~60.00 0.00 Hz 0x0081
F4.02Starting frequencymaintenance time
0.00~60.00 0.00s 0x0082
F4.03Start the DC brake
voltage0.00~30.00 2.00% 0x0083
F4.04 Start the DC 0.00~30.00 0.00s 0x0084
DR300 User's manual
48
braking time
F4.05 Parking options0:Slow down and stop1:Free Parking
0 〇 0x0085
F4.06Parking DC
braking frequency0.10~60.00 2.00Hz 0x0086
F4.07Parking DC
braking voltage0.00~30.00 2.00% 0x0087
F4.08Parking DCbraking time
0.00~30.00 0.00s 0x0088
F4.09Acceleration and
deceleration curves
0:Linear acceleration anddeceleration1:S-curve acceleration anddeceleration
0 〇 0x0089
F4.10S-curve
accelerationsegment initiation
0.00~50.00 30.00% 0x008A
F4.11S-curve
accelerationsegment end
0.00~50.00 30.00% 0x008B
F4.12S-curve
decelerationsegment initiation
0.00~50.00 30.00% 0x008C
F4.13S-curve
decelerationsegment end
0.00~50.00 30.00% 0x008D
F4.14LCD language
selection0:Chinese1:English
0 0x008E
F4.15Auxiliary Display
Selection0:Rotational speed1:Line speed
0 0x008F
F4.16Coefficient of
auxiliary display0.01~600.00 30.00% 0x0090
F4.17Keyboard interface
jump0:Do not jump1:Jump
1 〇 0x0091
F4.18Standby display
code0x0000~0x039F 0x0380 0x0092
F4.19 1 line display code 0x0000~0x039F 0x0382 0x0093F4.20 2 line display code 0x0000~0x039F 0x0387 0x0094F4.21 3 line display code 0x0000~0x039F 0x0389 0x0095F4.22 4 line display code 0x0000~0x039F 0x038A 0x0096F4.23 Reservation 0 0x0097F4.24 Reservation 0 0x0098
Functioncode
Name Setting range Factoryvalue
attributes Address
F4.25 Key lock function0:Not locked1:Full lock
0 〇 0x0099
DR300User'smanual
49
2:Lock except themultifunction key3:Lock except the RUN andSTOP / RESET key
F4.26Parameter copy
(only LCDkeypad)
0:Non-functional1:Parameter upload2:Parametersdownload(without motorparameters)3 : Parameters download(with motor parameters))
0 〇 0x009A
F4.27Keyboard software
version0.00~99.99 XXXX 0x009B
F4.28Functional
software version0.00~99.99 XXXX 0x009C
F4.29Performance
software version0.00~99.99 XXXX 0x009D
F4.30 Factory passwords 0~65535 XXXX X 0x009EF4.31 User passwords 0~65535 XXXX 〇 0x009F
F5 Group: PID function
F5.00 PID dimensionless
0:V1:Mpa2:M/min3:N4:
5:rpm
0 0x00A0
F5.01 PID range 0.01~600.00 10.00 0x00A1
F5.02PID Decimal
places
0:With no decimal1:A decimal2:Two decimal3:Three decimal
2 0x00A2
F5.03 PID Setting mode
0:PID set1:AI12:AI23:AI34:PF(X7)
0 〇 0x00A3
F5.04 PID set 0.00~600.00 5.00 0x00A4
F5.05PID feedback
selection
0:PID feedback1:AI12:AI23:AI34:PF(X7)
0 〇 0x00A5
F5.06 PID feedback 0.00~600.00 5.00 0x00A6
F5.07PID set the filter
time0.00~100.00 0.00s 0x00A7
DR300 User's manual
50
F5.08 PID preset value 0.00~600.00 5.00 0x00A8F5.09 PID preset time 0.00~100.00 0.00s 0x00A9
F5.10PID control
options0:Invalid1:Effective
1 0x00AA
Functioncode
Name Setting range Factoryvalue
attributes Address
F5.11PID conditioner
function0:Positive function1:Negative function
0 〇 0x00AB
F5.12 PID output gain 0.00~100.00 100.00% 0x00ACF5.13 Proportional gain P 0~1000.0 2.0 0x00AD
F5.14 Integration time i0.000~30.0000.000:no integral time
2.000s 0x00AE
F5.15 Differential time d 0.000~10.000 0.000s 0x00AFF5.16 Deviation limit 0.00~20.00 0.00% 0x00B0
F5.17Positive outputlimit frequency
0.00~600.0050.00
Hz 0x00B1
F5.18Negative limit theoutput frequency
0.00~600.0050.00
Hz 0x00B2
F5.19PID auxiliary
control
Bits: Points input ways0:PID input after startingdead time1:PID output soft-start timebefore input10: Feedback Control0:Settings1:Switching to settings fromthe feedback value
0 〇 0x00B3
F5.20PID output smooth
control
0:Within the PID outputsoft-start time,linear to thePID output gain1:PID output gain
0 〇 0x00B4
F5.21 PID dead time 0.00~60.00 0.00s 0x00B5F5.22 PID soft-start time 0.00~60.00 0.00s 0x00B6
F5.23PID setting upper
limit0.00~100.00 100.00% 0x00B7
F5.24PID setting lower
limit0.00~100.00 0.00% 0x00B8
F5.25PID switchselection
0:Only a set of PID1:AI12:AI23:AI1-AI24:PF(X7)
0 0x00B9
F5.26Proportional gain
P20~1000.0 2.0 0x00BA
F5.27 Integration time i2 0.000~30.000 0.000:no 2.000s 0x00BB
DR300User'smanual
51
Integral
F5.28Differential time
d20.000~10.000 0.000s 0x00BC
F5.29PID positiveoutput gain
0.00~100.00 100.00% 0x00BD
F5.30PID negativeoutput gain
0.00~100.00 100.00% 0x00BE
F6 Group: PLC running
F6.00 Program run mode
0:Round robin1:Single cycling then runaccording to the paragraph 72:Finite continuous cycle
0 〇 0x00C0
Functioncode
Name Setting range Factoryvalue
attributes Address
3:Continuous cycle
F6.01Program interrupt
mode
0 : Starts running from theinterruption period1:Running from the the firstparagraph
0 〇 0x00C1
F6.02Program run time
Dimension0:sec1:min
0 〇 0x00C2
F6.03Program
power-downstorage options
0:Not stored1:Stored
0 〇 0x00C3
F6.04Speed cycle
times1~10000 1 0x00C4
F6.05T1 choice of
direction0:The positive direction1:Negative direction
0 〇 0x00C5
F6.06T2 choice of
direction0:The positive direction1:Negative direction
0 〇 0x00C6
F6.07T3 choice of
direction0:The positive direction1:Negative direction
0 〇 0x00C7
F6.08T4 choice of
direction0:The positive direction1:Negative direction
0 〇0x00C8
F6.09T5 choice of
direction0:The positive direction1:Negative direction
0 〇 0x00C9
F6.10T6 choice of
direction0:The positive direction1:Negative direction
0 〇 0x00CA
F6.11T7 choice of
direction0:The positive direction1:Negative direction
0 〇 0x00CB
F6.12T1 Accelerationand deceleration
time selection
0 : Acceleration anddeceleration time 11 : Acceleration anddeceleration time22 : Acceleration and
0 〇 0x00CC
DR300 User's manual
52
deceleration time33 : Acceleration anddeceleration time4
F6.13T2 Accelerationand deceleration
time selection
0 : Acceleration anddeceleration time11 : Acceleration anddeceleration time22 : Acceleration anddeceleration time33 : Acceleration anddeceleration time4
0 〇 0x00CD
F6.14T3 Accelerationand deceleration
time selection
0 : Acceleration anddeceleration time11 : Acceleration anddeceleration time22 : Acceleration anddeceleration time33 : Acceleration anddeceleration time4
0 〇 0x00CE
F6.15T4 Accelerationand deceleration
time selection
0 : Acceleration anddeceleration time11 : Acceleration anddeceleration time22 : Acceleration anddeceleration time33 : Acceleration anddeceleration time4
0 〇 0x00CF
F6.16T5 Accelerationand deceleration
time selection
0 : Acceleration anddeceleration time11 : Acceleration anddeceleration time22 : Acceleration anddeceleration time33 : Acceleration anddeceleration time4
0 〇 0x00D0
F6.17T6 Accelerationand deceleration
time
0 : Acceleration anddeceleration time1
0 〇 0x00D1
Functioncode
Name Setting range Factoryvalue
attributes Address
selection
1 : Acceleration anddeceleration time22 : Acceleration anddeceleration time33 : Acceleration anddeceleration time4
DR300User'smanual
53
F6.18T7 Accelerationand deceleration
time selection
0 : Acceleration anddeceleration time11 : Acceleration anddeceleration time22 : Acceleration anddeceleration time33 : Acceleration anddeceleration time4
0 〇0x00D2
F6.19 T1 Running hours 0.0~6000.030.0s/min
0x00D3
F6.20 T2 Running hours 0.0~6000.030.0s/min
0x00D4
F6.21 T3 Running hours 0.0~6000.030.0s/min
0x00D5
F6.22 T4 Running hours 0.0~6000.030.0s/min
0x00D6
F6.23 T5 running hours 0.0~6000.030.0s/min
0x00D7
F6.24 T6 running hours 0.0~6000.030.0s/min
0x00D8
F6.25 T7 running hours 0.0~6000.030.0s/min
0x00D9
F7 group:Multi-segment speed、Multi-segment addition and subtraction time、 Digitalfrequency adjustment
F7.00multi-segment
speed 10.00~Fmax 1.00Hz 0x00E0
F7.01multi-segment
speed 20.00~Fmax 2.00Hz 0x00E1
F7.02multi-segment
speed 30.00~Fmax 3.00Hz 0x00E2
F7.03multi-segment
speed 40.00~Fmax 4.00Hz 0x00E3
F7.04multi-segment
speed 50.00~Fmax 5.00Hz 0x00E4
F7.05multi-segment
speed 60.00~Fmax 6.00Hz 0x00E5
F7.06multi-segment
speed 70.00~Fmax 7.00Hz 0x00E6
F7.07multi-segment
speed 80.00~Fmax 8.00Hz 0x00E7
F7.08multi-segment
speed 90.00~Fmax 9.00Hz 0x00E8
F7.09 multi-segment 0.00~Fmax 10.00Hz 0x00E9
DR300 User's manual
54
speed 10
F7.10multi-segment
speed 110.00~Fmax 11.00Hz 0x00EA
F7.11multi-segment
speed 120.00~Fmax 12.00Hz 0x00EB
F7.12multi-segment
speed 130.00~Fmax 13.00Hz 0x00EC
F7.13multi-segment
speed 140.00~Fmax 14.00Hz 0x00ED
F7.14multi-segment
speed 150.00~Fmax 15.00Hz 0x00EE
F7.15 speed -up time 2 0.00~600.0012.00s/min
0x00EF
F7.16 slow-down time2 0.00~600.0012.00s/min
0x00F0
F7.17 speed -up time 3 0.00~600.0013.00s/min
0x00F1
functioncode
namesetting range
factorydefaultvalue
property
address
F7.18 slow-down time 3 0.00~600.0013.00s/min
0x00F2
F7.19 speed -up time 4 0.00~600.0014.00s/min
0x00F3
F7.20 slow-down time 4 0.00~600.0014.00s/min
0x00F4
F7.21keyboard∧/∨digita
l adjust frequencycontrol
Bits : hoding whenpower off0 : not holding whenpower off1 : hoding whenpower offTen:clearring controlwhen stopped0:not clearring whenit is stopped1:clearring when
deceleration stops2: clearing when themachine standbyhundre :
keyboard∧/∨setting0:effective only digitalfrequency given1:adjusting is alwayseffective
12000 〇 0x00F5
DR300User'smanual
55
2 : adjusting is nevereffectivethousands:integralmethods0:setting the integralrate1 : setting thefrequency rate2:automatic integratalratemyriabit : reversingselect0:two-way adjustment,or reversing1:one-way adjustment,non- reversing
F7.22keyboard∧/∨theintegratal rate 0.00~4.99 2.00s 0x00F6
F7.23keyboard∧/∨thefrequency rate 0.00~100.00 0.10Hz/s 0x00F7
F7.24
UP/DN digitaladjustablefrequencycontrol
Bits : holding whenpower off0 : not holding whenpower off1 : holding whenpower offTen:clearing controlwhen it is in downtime0: not clearing whenit is in downtime1 : clearing whendeceleration stop2: clearing when themachine standbyhundreds : UP/DNsetting0: it is effective onlywhen digital frequencyis given1:adjusting is alwayseffective2 : adjusting is nevereffectivethousands:integralmethods
12000 〇 0x00F8
DR300 User's manual
56
0:setting the integralrate1 : setting thefrequency rate2:automatic integratalratemyriabit : reversingselect0:two-way adjustment,or reversing
functioncode
name setting rangefactorydefalutvalue
property
address
1:one-way adjustment,non- reversing
F7.25 UP/DN integral rate 0.00~4.99 2.00s 0x00F9
F7.26UP/DN frequencyrate 0.00~100.00 0.10Hz/s 0x00FA
F8group:vector control torque given
F8.00coefficient of speedloop proportional(ASR_P1)
0.00~100.00 15.00% 0x0100
F8.01time of speed loop
integration(ASR_Ti1)
0.000~30.000 0.150s 0x0101
F8.02coefficient of speedloop proportional
(ASR_P2)0.00~100.00 15.00% 0x0102
F8.03time of speed loop
integration(ASR_Ti2)
0.000~30.000 0.150s 0x0103
F8.04frequency of speed
switch 00.00~switchingfrequency1
5.00Hz 〇 0x0104
F8.05frequency of speed
switch 1switchingfrequency0~Fmax
5.00Hz 〇 0x0105
F8.06ASR input filtertime 0.000~30.000 0.040s 0x0106
F8.07ASR output filtertime 0.000~30.000 0.040s 0x0107
F8.08 driving torque limit 0.00~200.00 180.00% 〇 0x0108F8.09 braking torque limit 0.00~200.00 180.00% 〇 0x0109F8.10 torque control select 0:torque control is not 0 〇 0x010A
DR300User'smanual
57
effective1 : torque control iseffective
F8.11the source of
torque upper limition
0:torque upper limit1 : AI0(keyboardpotentiometers)2:AI13:AI24:PF(X7)5:AI1+AI26:AI1-AI2
0 〇 0x010B
F8.12 torque upper limit 0.00~150.00 5.55% 0x010CF9Group:communication
F9.00native address 1~247 0:broadcast
address1 〇 0x0120
F9.01communicationbaud rate
0:48001:96002:192003:38400
1 〇 0x0121
F9.02communicationformat
0:no parity checking1+8+1 for RTU1:even parity checking1+8+1+1 for
0 〇 0x0122
functioncode
name setting rangefactorydefalutvalue
property
address
RTU2:odd parity checking1+8+1+1 forRTU
F9.03
means ofmaster-slavemachinecommunication
0 : native machine isslave machine1 : native machine ishost machine
0 〇 0x0123
F9.04host machine
sending data(hostmachine setting)
0:output frequency1:input frequency 0 〇 0x0124
F9.05
receiving address ofslave machine
(host machinesetting)
0 : the main digitalfrequency1 : auxiliary digitalfrequency
0 〇 0x0125
F9.06receiving ratio of
slave machine0.00~600.00 100.00% 0x0126
DR300 User's manual
58
(slave machinesetting)
F9.07communicationstimeout 0.0~60.0 0.0s 0x0127
F10Group:fault and protection
F10.00
switch value faultdetecting the
frequency of deadzone
0.00~600.00 5.00Hz 0x0140
F10.01switch value faultdetecting the time
of dead zone0.00~600.00 5.00s 0x0141
F10.02analog faultselection
0 : AI0 ( keyboardpotentiometers)
1:AI12:AI23:PF(X7)4:output current5:input voltage
4 〇 0x0142
F10.03the time of analog
fault detecting0.00~60.00 5.00s 0x0143
F10.04the level of analog
fault detecting0.00~300.00 200.00% 0x0144
F10.05the level of analog
fault detectinghysteresis
0.00~300.00 0.00% 0x0145
F10.06the point of voltage
stall protection100.00~150.00 130.00% 〇 0x0146
F10.07the gain of voltage
stall0.00~100.00 1.00% 〇 0x0147
F10.08the point of current
stall protection100.00~200.00 150.00% 〇 0x0148
F10.09the gain of current
stall0.00~100.00 1.00% 〇 0x0149
F10.10Instantaneous
non-stop function0:prohibit1:permit
0 〇 0x014A
F10.11the decline rate of
Instantaneousnon-stop
0.00Hz/s~ themaximum frequency /s
10.00Hz/s
〇 0x014B
F10.12compensatory gain
of dead zone0.00~100.00 0.00% 0x014C
F10.13utilization rate of
braking5.00~100.00 80.00% 〇 0x014D
DR300User'smanual
59
F10.14the automatic fault
reset times0~3 0 〇 0x014E
functioncode
name setting rangefactoryDefalutvalue
property
address
F10.15the time interval of
automatic fault reset0.01~30.00 0.50s 〇 0x014F
F10.16the shortest
deceleration time0.05~30.00 0.05s 0x0150
F10.17fault properties and
shielding 1
Bits : overcurrentprotectionTen : overvoltageprotectionhundreds:undervoltageprotectionthousand : overloadprotection0:fault unshielded,stopping when faultsappear1: fault unshielded,alarming withoutstopping2 : fault have beenshieldedand do not alarm anddo not stop
0000 〇 0x0151
F10.18fault properties and
shielding 2
Bits : overheatprotectionTen: input phase lossprotectionhundreds:output phaseloss protectionthousands :
communication fault0: fault unshielded,stopping when faultsappear1: fault unshielded,alarming withoutstopping2 : fault have beenshieldedand do not alarm anddo not stop
0010 〇 0x0152
DR300 User's manual
60
F10.19fault properties and
shielding 3
Bits:memory faultTen: switching valuefaulthundreds:analog faultthousands:reserving0: fault unshielded,stopping when faultsappear1: fault unshielded,alarming withoutstopping2 : fault have beenshieldedand do not alarm anddo not stop
0000 〇 0x0153
F11Group:auxiliary function
F11.00point dynamicpriority whenrunning
0:point dynamic is nota priority1:point dynamic is apriority
0 0x0160
F11.01jumping frequency
1 low limit0.00~600.00 0.00 Hz 0x0161
F11.02jumping frequency1 top limit
0.00~600.00 0.00 Hz 0x0162
F11.03jumping frequency
2 low limit0.00~600.00 0.00 Hz 0x0163
F11.04jumping frequency
2 top limit0.00~600.00 0.00 Hz 0x0164
F11.05jumping frequency
3 low limit0.00~600.00 0.00 Hz 0x0165
F11.06jumping frequency
3 top limit0.00~600.00 0.00 Hz 0x0166
F11.07the forward and
reverse time of deadzone
0.00~600.00 0.00s 0x0167
functioncode
name setting rangeFactorydefaultvalue
property address
F11.08the run-time
password0~65535 0 X 0x0168
F11.09setting the running
time0~60000 2400H 〇 0x0169
F11.10running time of the
native machine0~65535 XXXX 0x016A
F11.11 low frequency 0:running at the low 0 0x016B
DR300User'smanual
61
control limit frequency1: running at the
speed 0 when reachingthe time of low limit
F11.12low frequencyrunning time
0.01~600.00 0.01s 0x016C
F11.13output frequency
range0.00~50.00 2.50 Hz 0x016D
F11.14AI sampling dead
zone0~256 4 0x016E
F11.15analog ADT1
selectting
0:AI0(keyboardpotentiometer)
1:AI12:AI2
1 〇 0x016F
F11.16analog ADT1
percentage0.00~100.00 20.00% 0x0170
F11.17analog ADT1
hysteresis loop0.00~100.00 5.00% 0x0171
F11.18the rising time of
speed tracking0.00~10.00 1.00s 0x0172
F11.19
the current limitvalue of speed
tracking0.00~100.00 100.00% 0x0173
F11.20the time interval of
speed tracking0.00~10.00 0.50s 0x0173
F11.21the countingcorresponding tothe pulse
0~65000 1 0x0172
F11.22the setting value ofcounting
0~65000 1000 0x0173
F11.23calculating thecurrent value 0~65000 XXXX 0x0174
F12Group:the shotrcut menu list
F12.00the display quantityof shotrcut menu
0~31 15 0x0180
F12.01the shotrcut menu
10x0000~0x039F 0x0003 0x0181
F12.02the shotrcut menu
20x0000~0x039F 0x0004 0x0182
F12.03the shotrcut menu
30x0000~0x039F 0x0005 0x0183
F12.04the shotrcut menu
40x0000~0x039F 0x0006 0x0184
DR300 User's manual
62
F12.05the shotrcut menu
50x0000~0x039F 0x0007 0x0185
F12.06the shotrcut menu
60x0000~0x039F 0x0008 0x0186
F12.07the shotrcut menu
70x0000~0x039F 0x0009 0x0187
F12.08the shotrcut menu
80x0000~0x039F 0x000A 0x0188
F12.09the shotrcut menu
90x0000~0x039F 0x000B 0x0189
F12.10the shotrcut menu
100x0000~0x039F 0x000C 0x018A
F12.11the shotrcut menu
110x0000~0x039F 0x000D 0x018B
F12.12the shotrcut menu
120x0000~0x039F 0x000E 0x018C
F12.13the shotrcut menu
130x0000~0x039F 0x0010 0x018D
functioncode
name setting rangeFactorydefaultvalue
property address
F12.14the shotrcut menu
140x0000~0x039F 0x0011 0x018E
F12.15the shotrcut menu
150x0000~0x039F 0x0016 0x018F
F12.16the shotrcut menu
160x0000~0x039F 0x0018 0x0190
F12.17the shotrcut menu
170x0000~0x039F 0x001A 0x0191
F12.18the shotrcut menu
180x0000~0x039F 0x001B 0x0192
F12.19the shotrcut menu
190x0000~0x039F 0x001C 0x0193
F12.20the shotrcut menu
200x0000~0x039F 0x0021 0x0194
F12.21the shotrcut menu
210x0000~0x039F 0x0022 0x0195
F12.22the shotrcut menu
220x0000~0x039F 0x0023 0x0196
F12.23the shotrcut menu
230x0000~0x039F 0x0024 0x0197
F12.24the shotrcut menu
240x0000~0x039F 0x0025 0x0198
F12.25 the shotrcut menu 0x0000~0x039F 0x0026 0x0199
DR300User'smanual
63
25
F12.26the shotrcut menu
260x0000~0x039F 0x002F 0x019A
F12.27the shotrcut menu
270x0000~0x039F 0x0030 0x019B
F12.28the shotrcut menu
280x0000~0x039F 0x0031 0x019C
F12.29the shotrcut menu
290x0000~0x039F 0x0032 0x019D
F12.30the shotrcut menu
300x0000~0x039F 0x0033 0x019E
F12.31the shotrcut menu
310x0000~0x039F 0x0038 0x019F
F13Group:Analog enhancements
F13.00 analog bias selection
Bits : AI0 biasselection0:two bias1:four bias A curve2:four bias B curveTen:AI1 biasselection0:two bias1:four bias A curve2:four bias B curveHundreds:AI2 biasselection0:two bias1:four bias A curve2:four bias B curvethousands:AI3 biasselection0:four bias A curve1:four bias B curve
0000 〇 0x01A0
F13.01 output offset AY0 0.00~100.00 0.00% 0x01A1F13.02 output offset AY1 0.00~100.00 25.00% 0x01A2F13.03 output offset AY2 0.00~100.00 75.00% 0x01A3
F13.04 output offset0.00~100.00100.00=FMAX
100.00% 0x01A4
F13.05 output offset AX0 0.00~ input offset AX1 0.00% 0x01A5
F13.06 output offset AX1input offset AX0~input offset AX2
25.00% 0x01A6
F13.07 output offset AX2input offset AX1~input offset AX3
75.00% 0x01A7
F13.08 output offset AX3input offsetAX2~100.00
100.00% 0x01A8
DR300 User's manual
64
functioncode
name setting rangefactoryDefalutvalue
property address
F13.09 output offset BY0 0.00~100.00 0.00% 0x01A9F13.10 output offset BY1 0.00~100.00 25.00% 0x01AAF13.11 output offset BY2 0.00~100.00 75.00% 0x01AB
F13.12 output offset BY30.00~100.00100.00=FMAX
100.00% 0x01AC
F13.13 input offset BX0 0.00~ input offset BX1 0.00% 0x01AD
F13.14 input offset BX1input offset BX0~input offset BX2
25.00% 0x01AE
F13.15 input offset BX2input offset BX1~input offset BX3
75.00% 0x01AF
F13.16 input offset BX3input offsetBX2~100.00
100.00% 0x01B0
ER Group:Fault History
ER.00 the latest fault
ERR00:without fault/wrong actionERR01: inverter unitprotectionERR02 : acceleratingspeed over the currentERR03 : constantspeed over the currentERR04 : deceleratingspeed over the currentERR05:acceleratingspeed over thevoltageERR06 : constantspeed over thevoltageERR07:deceleratingspeed over thevoltageERR08:undervoltageprotectionERR09 : overloadprotectionERR10:overheatprotectionERR11: the lack ofinput phraseERR12: the lack ofoutput phraseERR13 :
XXXX 0x0200
DR300User'smanual
65
communication faultERR14 : memoryfaultERR15 : self-tuningfaultERR16 : switchingvalue faultERR17:analog fault
ER.01the output
frequency duringfault
0.00~600.00 XXXX 0x0201
ER.02the output current
during fault 0.0~3000.0 XXXX 0x0202
ER.03the bus voltage
during fault0~1200 XXXX 0x0203
ER.04the working time
during fault0~65535 XXXX 0x0204
ER.05the input terminals
1 during fault0000~1111 XXXX 0x0205
ER.06the input terminals
2 during fault0000~1111 XXXX 0x0206
ER.07the output
terminals duringfault
0000~1111 XXXX 0x0207
ER.08 Previous fault ERR.00~ERR.17 XXXX 0x0208
functioncode
name setting rangefactoryDefalutvalue
property address
ER.09the output
frequency duringfault
0.00~600.00 XXXX 0x0209
ER.10the output current
during fault0.0~3000.0 XXXX 0x020A
ER.11the bus voltage
during fault0~1200 XXXX 0x020B
ER.12the working time
during fault0~65535 XXXX 0x020C
ER.13the input terminals
1 during fault0000~1111 XXXX 0x020D
ER.14the input terminals
2 during fault0000~1111 XXXX 0x020E
ER.15the output
terminals duringfault
0000~1111 XXXX 0x020F
DR300 User's manual
66
ER.16 the second fault ERR.00~ERR.17 XXXX 0x0210
ER.17the output
frequency duringfault
0.00~600.00 XXXX 0x0211
ER.18the output current
during fault0.0~3000.0 XXXX 0x0212
ER.19the bus voltage
during fault0~1200 XXXX 0x0213
ER.20the working time
during fault0~65535 XXXX 0x0214
ER.21the input terminals
1 during fault0000~1111 XXXX 0x0215
ER.22the input terminals
2 during fault0000~1111 XXXX 0x0216
ER.23the output
terminals duringfault
0000~1111 XXXX 0x0217
ER.24the maximum of thebus voltage 0~1200 XXXX 0x0218
H0Group:Monitoring the coefficientH0.00 the frequency
reference andtorque reference
frequency:0.00~600.00Hztorque:0.00~150.00%
XXXX
0x0380
H0.01 0x0381
H0.02 the outputfrequency
0.00~600.00 XXXX 0x3082
H0.03 0x0383H0.04 the rotation speed /
line speed0.0~18000.0 XXXX
0x0384H0.05 0x0385
H0.06the standard value
of the outputcurrent
0.00~100.00 XXXX 0x0386
H0.07the actual value ofthe output current
0.0~3000.0 XXXX 0x0387
H0.08the standard value
of the outputvoltage
0.00~100.00 XXXX 0x0388
functioncode
name setting rangefactorydefalutvalue
property address
H0.09the actual value ofthe output voltage
0.0~660.0 XXXX 0x0389
H0.10the DC bus voltage
0~1200 XXXX 0x038A
H0.11 the overload times 0.00~100.00 XXXX 0x038B
DR300User'smanual
67
countingH0.12 the output power 0.0~3000.0 XXXX 0x038CH0.13 PID setting 0~60000 XXXX 0x038DH0.14 PID feedback 0~60000 XXXX 0x038EH0.15 PID output -100.0~100.0 XXXX 0x038F
H0.16the status of theinput terminal 1
X4 X3 X2 X1 XXXX 0x0390
H0.17the status of theinput terminal 2
* X7 X6 X50 0 0 0
XXXX 0x0391
H0.18the status of theoutput terminal
* R1 Y2 Y10 0 0 0
XXXX 0x0392
H0.19AI0 input
percentage0.00~100.00 XXXX 0x0393
H0.20AI1 input
percentage0.00~100.00 XXXX 0x0394
H0.21AI2 input
percentage0.00~100.00 XXXX 0x0395
H0.22PF input
percentage0.00~100.00 XXXX 0x0396
H0.23AO1 outputpercentage
0.00~100.00 XXXX 0x0397
H0.24AO2 outputpercentage
0.00~100.00 XXXX 0x0398
H0.25DO outputpercentage
0.00~100.00 XXXX 0x0399
DR300 User's manual
68
Chapter6 Parameter Description
F0 :Basic Function
F0.00
Model display Factory value Model dependentSet range 0 G model(Constant torque load model)
1 P model (fan and pump load model)This parameter is only for the user to know the factory default model and cannot be
changed.1: For the constant torque load of the designated rated parameters.2: For the variable torque loads (fan and pump loads) of the designated rated parameters
F0.01
Function code protection Factory value 0
Set range
0 The keyboard and communicate port can be
modified1 The keyboard can be modified
2 The communicate port can be modified
3 The keyboard and communicate port can’t be
modifiedThe parameter is used to set the change permissions and initialization level of parameters.0:The keyboard and communication port can be modified at the same time.1:The keyboard can be modified.2:The communication port can be modified.3:Both of the keyboard and communication port can’t be modified.
F0.02
Keyboard display mode Factory value 0
Set range
0 Basic menu mode
1 Quick menu mode
2 Non factory value function code menu mode(only for LCD keyboard)
When the function is set, the operation panel can display function code parametersaccording to the user’s actual needs and improve work efficiency.
0:Basic menu mode: All the parameters can be displayed on the operation panel .1:Quick menu mode:The operation panel only display the user-defined quick parameters.
When using the inverter’s basic functions, this menu mode can be selected.2:Non factory value function code menu mode: the operation panel only display these
parameters different from the factory valueUsing this mode, the technical personnel can browse user settings when doing on-site
maintenance and troubleshooting.After debugging the inverter, in order to facilitate recording and query the changed
parameters, this mode can be selected.
DR300User'smanual
69
F0.03
Driver control mode Factory value 0
Set range0 V/F coordinated control(VF)
1 Vector control without feedback fromencoder(SVC)
This function is used to set the control mode for the inverter.0:V/F control mode :It is suitable for the situation that the load requirement is not high, or
when a inverter is used to drive multiple motors. E. g: blower and pump load1:Vector control without feedback from encoder:It refers to the open-loop vector. It is
suitable for the usual situation that requires high quality of control, and a transducer can driveonly a motor, such as machine, centrifuge, drawing machine, injection molding machine load.
F0.04
Selection for macro Factory value Model identification
Set range
0 General macro
1 Special macro
2 PID application macro
3 The application macro for program
4 Modbus Communication application macro
Setting this application macro function, for the corresponding applications0:General macro:basic application.1:Special macro:special application according to the customers’ requriment.2:PID application macro:suitable for simple PID application.3:Program application macro:special use for PLC program.4:Mod bus Communication application macro:special use for communication with upper
machine.
F0.05
Set way of run command Factory value 0
Set range
0 Local keyboard
1 external terminals
2 PC communication
3 Local keyboard + external terminals
4 Local keyboard +PC communication
5 external terminals +PC communication
Channel selection of VFD control commandVFD control command: start, stop, forward, inverse, jog.
DR300 User's manual
70
0:Local keyboard:The RUN and STOP/RESET keys on the local keyboard control thecommand.
1:External terminals:The multi-function input terminals FWD,REV,JOGF and JOGRcontrol the command.
2:PC communication:The command is given through communication from PC3:Local keyboard + external terminals:The command is controlled by the keys RUN and
STOP/RESET on the keyboard or the multi-function input terminals (FWD,REV,JOGF andJOGR).
4:Local keyboard + PC communication:The command is controlled by the keys (RUN andSTOP/RESET) on the keyboard or it is given by the PC through communication.
5:External terminals + PC communication:The command is controlled by themulti-function input terminals (FWD,REV,JOGF and JOGR) or it is given by the PC throughcommunication.
F0.06
Terminal command option Factory value 0
Set range
0 2-wire mode 1
1 2-wire mode 2
2 3-wire mode 1
3 3-wire mode 2
These parameters define four ways to control the drive by the external terminals.0:2-wire mode .1:When this mode is selected,X1 will be the enabled and the direction is
decided by the state of X2.
DR300
X1 Digital input
X2 Digital input
COM Digital common
K1
K2
K1
0
0
1
1
K2
0
1
0
1
Command
Stop
Stop
Forward
Reverse
Figure 6-1
1:2-wire mode 2:The most common 2-wire mode. Forward or reverse is decided bycommands from X1 and X2.
DR300User'smanual
71
DR300
X1 Digital input
X2 Digital input
COM Digital common
K1
K2
K1
0
1
0
1
K2
0
0
1
1
Command
Stop
Forward
Reverse
Stop
Figure 6-2
2:3-wire mode 1:In this mode, Xn will be enabled ,and the direction is decided by the stateof X1 and X2. But the pulse is effective and it will keep running until the signal from Xn isdisconnected.
DR300X1 Digital input
Xn 3-wine control
X2 Digital input
COM Digital common
SB1
SB2
SB3
Figure 6-3
Note:SB1:Forward button SB2:Enable button SB3:Reverse buttonXn is the multi-function input terminals from X1 to X7, the corresponded terminal’s
function should be defined the function 5” three-wire control”. Not until the terminal Xn isclosed, the X1 and X2 terminals and the pulses from them are effective.
3:3-wire mode 2:The Xn terminal is enabled . The command comes from terminal X1 andthe direction decided by terminal X2 .It is stopped by disconnecting the Xn signal.
DR300X1 Digital input
Xn 3-wine control
X2 Digital input
COM Digital common
SB1
SB2
K
K Direction
0
1
Forward
Reverse
Figure 6-4
SB1:Run button SB2:Enable button K:Reverse button.When SB2 is enabled and X1 is given a valid pulse, the drive runs forward (the direction
has no relationship with X2).Afterwards it will change the direction whenever X2 is given avalid pulse and it won’t stop until Xn is invalid.
DR300 User's manual
72
F0.07
Speed set mode Factory default value 0
Set range
0 main speed
1 auxiliary speed
2 main speed +auxiliary speed
3 main speed -auxiliary speed
4 Main speed and(main speed +auxiliary speed)switching
5 Main speed and(main speed –auxiliary speed)switching
6 auxiliary speed and(main speed +auxiliary speed switching
7 auxiliary speed and(main speed -auxiliary speed)switching
8 MAX main speed 、auxiliary speed
9 MINmain speed 、auxiliary speed
10 main speed*auxiliary speed
This parameter is used to select the frequency reference channel. Frequency reference isrealized through combination of main frequency source and auxiliary frequency source
When 2 is selected, the frequency source “main frequency source plus auxiliary frequencysource” can realize frequency overlapping function.
When 3 is selected, the speed is main speed-auxiliary speed, can relize a relatively speedgiven function.
When 4 is selected, the speed is main speed+auxiliary speed,it can switch via themultifunctional input terminal “Frequency Source Switching”.
When 5 is selected, the speed is main speed-auxiliary speed, it can switchvia themultifunctional input terminal “Frequency Source Switching”.
When 6 is selected, the speed is main speed+auxiliary speed,it can switch via themultifunctional input terminal “Frequency Source Switching”.
When 7 is selected, the speed is main speed-auxiliary speed, it can switch via themultifunctional input terminal “Frequency Source Switching”.
When 8 is selected, the speed is the bigger one between the main speed andauxiliary speed.When 9 is selected, the speed is the smaller one between the main speed andauxiliary speed.When 10 is selected, the speedis the main frequency source multiplied auxiliary frequency
DR300User'smanual
73
source.
F0.08
Main frequency source
selectionFactory value 0
Set range
0 Main digital frequency
1 Al0(Keyboard potentiometer)
2 Al1
3 AI2
4 PF(X7)
5 PLC
6 PID
7 MS speed
Selection main speed input channels for the inverter,8 channels for the set frequency:0:main digital frequency .1:AI0 2:AI1 3:AI2The frequency is decided by the analog input terminals.There analog input terminals are
provided by the standard unit. Optional I/O expansion card can provide 3 analog input terminalsand among them AI0 is potentionmeter for keyboard .AI1 is 0 to 10V voltage input or 0-20 mAcurrent input,and AI2 is 0-10V voltage input .
4:PF(X7):The speed is set through the pulse from terminals. The set pulsefeature :9V~24V,0kHz~50kHz.
5:PLC:PLC mode. When the frequency is from PLC, the set frequency is decided bysetting the parameters of F6, F7, MS speed and PLC.
6:PID:when select the process PID, you need to set the group F5 “PID function”. thedrive’s frequency is the frequency after the PID take action. Please refer to the F5 group "PID"Introduction.
7:MS speed :when choose the multi-segment speed mode you need to set parameters ofgroup F2 and F7 to determine the corresponding relation between the set signal and the setfrequency..
DR300 User's manual
74
F0.09
Auxiliary Frequency source selection Factory value 0
Set range
0 Auxiliary digital frequency
1 Al0(Keyboard potentiometer0
2 Al1
3 AI2
4 PF(X7)
5 PLC
6 PID
7 MS speed
When auxiliary speed works as a separate speed set channel (the speed switch to thesecondary speed switching), its usage is the same with the main speed.
When the auxiliary frequency source is used as independent frequency reference channel(speed switch to the secondary speed switching), it is used in the same way as the main speed.
When auxiliary speed is used as a member of the superposition set (frequency sourceselection is the main speed+ auxiliary speed or main speed to the main speed + auxiliary speedswitching),it has the following special features:
1.When the auxiliary frequency source is analog input reference (AI1, AI2 ) or pulse inputreference, 100% of input setup is relative to the auxiliary frequency source range (refer to F0-05and F-06). To adjust the main reference frequency, it needs to set the corresponding Set range ofanalog input to “-n% to n% (refer to F4-13 and F4-26).
2: When the frequency source is pulse input reference, it is similar to the analog value.Prompt: There is difference between the auxiliary frequency source Y selection and the
main frequency source X setup value. That is to say, the main and auxiliary frequency sourcescannot use the same frequency reference channel.
F0.10
Auxiliary speed range select Factory value 0
Set range0 Relative to the maximum frequency
1 Relative to the main speed
DR300User'smanual
75
F0.11
Auxiliary Frequency source
YFactory value 100.00%
Set range 0.00~100.00
When speed is superimposed on a set speed, it’s used to determine the scope of theregulation of the auxiliary frequency source,F0.10 is used to determine the scope of the relativeobject. Relative to the maximum speed, its range will change as the main speed change.Attention: it is only effective to the set analog.
F0.12Main digital frequency Factory value 50.00Hz
Set range 0.00~Fmax
F0.13Auxiliary digital frequency Factory value 50.00Hz
Set range 0.00~Fmax
The main digital frequency, auxiliary digital frequency that is set can be modified bykeyboard or communications port.
F0.14
Positive and negative direction of selection Factory value 0
Set range0 Forward
1 Reverse
This parameter is used to change the direction of rotation under the condition that theoperating panel command is given on the operating panel.
0:Forward.1:Reverse.
F0.15
Acceleration and deceleration time dimension Factory value 0
Set range0 sec
1 min
It’s used to select the acceleration and deceleration time , and effective for acceleration anddeceleration time 1 (F0.16, F0.17)and acceleration and deceleration time 2, 3 ,4 (F7.15 ~ F7.20)
F0.16Acceleration time1 Factory value Model identification
Set range 0.00~600.00
F0.17 Deceleration time 1 Factory value Model identification
DR300 User's manual
76
Set range 0.00~600.00
Acceleration time refers to the time t1 to accelerate from 0Hz to the maximum outputfrequency (F0.22).
Deceleration time refers to the time t2 to decelerate to 0Hz from the maximum outputfrequency (F0.22).
As shown:
Output frequency Hz
Max frequency
Setting frequency
actual acceleration time
setting acceleration time
actual deceleration time
setting acceleration time
t
t1 t2
Figure 6-5 Acceleration and deceleration timePay attention to the difference between the actual acceleration/deceleration time and the setup
acceleration/deceleration time.There are totally four groups of acceleration/deceleration time for selection.
Four sets of time options:Group 1:F0.16、F0.17;Group 2:F7.15、F7.16;Group 3:F7.17、F7.18;Group 4:F7.19、F7.20.It can select acceleration/deceleration time via the multifunctional digital input terminals
(F0.180 to F0.19).
F0.18Jog digital frequency Factory value 5.00Hz
Set range 0.00~Fmax
F0.19Jog acceleration time Factory value 6.00s
Set range 0.00~600.00
F0.20Jog deceleration time Factory value 6.00s
Set range 0.00~600.00
DR300User'smanual
77
This function is used to define inverter’s set frequency and acceleration time and thedeceleration time when it is jogging. The jog running process starts and stops in accordance withthe startup mode 0 (F4.00, direct start) and stop mode 0 (F4.05, slow down and stop).
Jog acceleration time refers to the time to accelerate from 0 Hz up to the maximum outputfrequency (F0.22).
Jog deceleration time refers to the time that decelerate to 0Hz from the maximum outputfrequency (F0.22).
F0.21Carrier frequency Factory value Model identification
Set range 1.000~16.000
This feature is used to adjust the carrier frequency of the inverter. By adjusting the carrierfrequency, you can avoid the resonance point of the mechanical systems and reduce the motornoise, the line to ground leakage current and the interference generated by the drive.
When the carrier frequency is low, the high harmonics of the output current increase, themotor loss increases and the increase in motor temperature rises.
When the carrier frequency is high, the loss of the motor reduces, and the motortemperature decreases while the loss the temperature rise and the interference of the inverter allincrease.
Adjusting the carrier frequency may affect the following performance:
The carrier frequency low → high
Motor noise big → small
Output current waveform poor → good
Motor temperature rise high → low
Inverter temperature rise low → high
Leakage current low → high
External radiation interference low → high
F0.22Maximum frequency Factory value 50.00Hz
Set range F max:0.01~600.00
Maximum output frequency refers to the highest frequency the inverter allows to output.
F0.23
maximum frequency set Factory value 0
Set range
0 Digital setting
1 Al0(Keyboard potentiometer)
2 Al1
DR300 User's manual
78
3 AI2
4 PF(X7)
F0.24The maximum frequency The factory value 50.00Hz
Set range F up:F down ~F max
The F0.23 defines the source of the maximum frequency. The maximum frequency can befrom both the digital setting (F0.24) and the analog input channels. When the maximumfrequency is set by the analog input, the 100% input corresponds to F0.24.
For example, the speed control is not valid during the torque control,. In order to avoidmaterial disconnection "speed", you can set the maximum frequency with analog input. Whenthe inverter operates at the maximum frequency, the torque control is invalid and the invertercontinues on the maximum frequency.
F0.25Upper limit frequency Factory value 0.00Hz
Set range F down:0.00~Fup
The inverter starts running from the start frequency .During the operation if the setfrequency is lower than the minimum frequency, the inverter will run all the time at theminimum frequency until the inverter stops or the set frequency is higher than the minimumfrequency.
F0.26
Multi-function selection Factory value 2
Set range
0 No function
1 Positive/Negative input switching function
2 Inching operation function
3 Function code display switching
4 Start / stop command source switching
5 Free parking
6 Emergency stop(Most quickly stopped)
Function of the MK key on the keyboard0:No function1: Positive/Negative input switching function2: Jog operation function3: Function code switch4:Start / stop command source switching5: Free parking
DR300User'smanual
79
6:Emergency stop(the fastest parking)
F0.27Prohibit reverse control Factory value 0
Setting range0 Allow reversal1 Prohibit reverse
Whether to allow the motor reversing:0:Allow rebersal: Motor rotation can be set by code F0.14, or by the set F / R terminal
control1:Prohibit reverse: The motor can only run in one direction, the F0.27 parameters and the F
/ R terminal invalid
F0.28
Restore the factory default Factory value 0
Setting range
0 Invalid
1 Parameter recovery mode 1
2 Parameter recovery mode 2
3 Clear the history information
Restore the factory value function0: Invalid1: Parameter recovery mode 1: Does not contain the analog input and output bias (F2.11 ~
F2.30, F3.10 ~ F3.21) parameters to restore the factory default2: Parameter recovery mode 2: Contains the offset of the analog input and output (F2.11 ~
F2.30, F3.10 ~ F3.21) parameters to restore the factory value.3: Clear the history information
F0.29
Parameter modification mode Factory value 1
Setting range
0 Address the same mode in the modified
1 Address plus-one the mode in the modified
The address changes mode to modify the parameters on the keyboard0: Address the same mode in the modified1: Address plus-one mode in the modified
DR300 User's manual
80
F1: Motor parameters, V / F, the control parameters
F1.00
Motor model Factory value Determine the mode model
Setting range0 AC induction motor
1 AC synchronous motor
F1.01Motor rated power Factory value Determine the model
Setting range 0.40~450.00
F1.02Motor rated voltage Factory value Determine the model
Setting range 60~660
F1.03Motor rated current Factory value Determine the model
Setting range 0.1~1000.0
F1.04Motor rated frequency Factory value Determine the model
Setting range 20.00~600.00
F1.05Motor nominal speed Factory value Determine the model
Setting range 1~60000
F1.06
Electrical connection method Factory value Determine the model
Setting range
0 丫
1 Δ
Warnning:To set following the motor nameplate parameters.Vector control, good control performance, you need accurate motor parameters, accurate
parameter identification from the rated motor parameters set correctlyIn order to guarantee the control performance, the inverter standard adaptive motor
DR300User'smanual
81
configuration, the gap is too large if the motor power and standard adaptive motor controlperformance of the inverter will fall significantly.
F1.07Motor rated power factor Factory value Determine the model
Setting range 0.50~0.99
When the inverter and electrical wiring for the first time, set the motor nameplateparameters: rated power, rated voltage, rated current, rated frequency, rated speed, the electricalconnection method and the motor rated power factor
F1.08No-load excitation current I0 Factory value Determine the model
Setting range 0.1~1500.0
F1.09Rated torque current Factory value Determine the model
Setting range 0.1~1500.0
F1.10Stator resistance R1 Factory value Determine the model
Setting range 0.01~300.00
F1.11Rotor resistance R2 Factory value Determine the model
Setting range 0.01~300.00
F1.12Stator leakage inductance L1 Factory value Determine the model
Setting range 0.01~300.00
F1.13Mutual inductance L2 Factory value Determine the model
Setting range 0.01~300.00
Motor F1.06-F1.10 settings automatically updated after the normal end ofself-identification.
Every time you change the motor rated power F1.01, the drive would F1.08, F1.10 ~ F1.13parameter values will automatically restore the default standard motor parameters.(Quadrupole Y series induction motor) if the live condtion can not self-identification to the thesame kind of motor, the known parameters entered manually.
F1.14Parameters of self-identification Factory value 0
Setting range 0 Not identification
DR300 User's manual
82
1 Motor stationary since the identification
2 Motor rotation since the identification
0: Not identification1: Motor stationary self-identification: When the motor is stationary, its parameters (F1.08,
F1.10 ~ F1.13) self-identification, in order to obtain accurate parameters of the motor.2: Motor rotation self-identification : When the motor rotates, its parameters (F1.08, F1.10
~ F1.13) self-identification, in order to obtain accurate parameters of the motor.Self-identification of the operating instructions:
When F1.14 is set to 1 or 2 and then press ENTER, and then press the RUN key to start theparameters of self-identification, shown “TUNE”. After the end of the self-identification, showback to the shutdown interface. Press the STOP button to abort the process of self-identification.When self-identification is complete, the F1.14 value automatically restores to 0.
Description: self-identification can only be effective in the keyboard control mode, thedeceleration time is recommended to use the factory default values.
F1.15
V/F Torque boost Factory value 5
Setting range
0 Straight line
1~4 Fan and water pump lift curve
5 Any V / F curve
0: Line: linear torque increase1: Fan and water pump lift curve2: Any V / F curve can be based on use requirements set by the user's own
F1.16V/F Voltage 1 Factory value Determine the model
Setting range 0.00~100.00
F1.17V/F Frequency 1 Factory value Determine the model
Setting range 0.00~100.00
F1.18V/F Voltage 2 Factory value Determine the model
Setting range 0.00~100.00
F1.19V/F Frequency 2 Factory value Determine the model
Setting range 0.00~100.00
F1.20V/F Voltage 3 Factory value Determine the model
Setting range 0.00~100.00
DR300User'smanual
83
F1.21V/F Frequenc 3 Factory value Determine the model
Setting range 0.00~100.00
F1.22V/F Voltage 4 Factory value Determine the model
Setting range 0.00~100.00
F1.23V/F Frequenc 4 Factory value Determine the model
Setting range 0.00~100.00
F1.16 ~ F1.23 ,eight parameters defined multi-point V / F curve. The frequency settingrange is from 0.00% to 100.00% of the motor rated frequency, the voltage point setting range isfrom 0.0% to 100%, and corresponding 0V ~ motor rated voltage. Multi-point V / F curvesettings are usually set according to the motor load characteristics. The multi-point V / F curve isset as shown in Figure 6.6.
Note:1.Be sure the following settings :F1.17≤F1.19≤F1.21≤F1.23 .In order to ensure the settings
are correct ,This drive is the relationship between the frequency F1.17, F1.19, F1.21 and F1.23on the lower limit constraints, first set F1.23 settings, and then set the F1.21, and then set theF1.19, the last set F1.17.
2.Low-frequency voltage is set too high may cause the motor to overheat and even burn, thedrive may be the loss of speed or over-current protection.
Voltage%
v3
f1-f3: V/F curve 1-3 frequency pointsv1-v3:V/F curve 1-3 points of frequency percentagefb:Motor rated powerF1-03
f2 fb HZFrequency
v1
100%
v2
f1 f3
Figure 6-6 Multi-point of the V / F curve set schematic
F1.24Slip compensation Factory value 0.00%
Setting range 0.00~200.00
Set the parameters can compensate for V / F control because of the load generated by slip,V / F control the motor speed decreases with the change of the load changes, generally 100%
DR300 User's manual
84
corresponds to rated motor with a rated load slip . Refer to the following principles slipcompensation factor adjustment: When the load for slip compensation coefficient is set to 100%rated load, the speed of the drive motor brought close to a given speed.
Note: When the slip compensation coefficient is too large, easy to cause the motoroscillation, please reduce the slip compensation coefficient.
F1.25
Oscillation suppression gain Factory value 0.00%
Setting range 0~1000
Motor oscillations, the gain is 0. The only obvious oscillation of motor does not operatenormally when appropriate to increase the gain, gain greater the more obvious on the inhibitionof the oscillation. Inhibit the oscillation function, the requirements of the motor rated current andno-load current parameter settings and little deviation. The choice of the gain is to try to take thepremise of effective suppression of oscillation is small, so as not to have much impact on V / F.
F1.26
Overmodulation gain Factory value 0.00%
Setting range 0~1000
In the case of low bus voltage, output current of the motor is too large, by increasing themodulation gain can increase the output voltage, reduce motor current, but the current waveformwill be distortion, the gain selection method is to set the smaller gain value as possible under thecondtion that this value can effective reduce output current, so as not to have much impact on themotor.
F1.27
Carrier way Factory value 1
Setting range
0 Fixed carrier mode
1 Automatically adjust the carrier way
2 A random carrier 1
3 A random carrier 2
0: A fixed carrier: the carrier frequency does not adjust according to the inverter bodytemperature. Various loads must keep good ventilation, low noise on running.
1: Automatically adjust the carrier mode: inverter can load the severity of the carrierfrequency automatically adjusts the temperature detected. Achieve low noise at light loads.
2: A random carrier 1: Adjust the amplitude of the carrier frequency changes randomly toreduce motor noise.
DR300User'smanual
85
3: A random carrier 2: Adjust the amplitude of the carrier frequency changes randomly toreduce motor noise.
Control the inverter temperature in the heavy load, to maintain continuous and reliableoperation.
F1.28
Automatic voltage regulator control Factory value 0
Setting range
0 Invalid
1 The whole invalid
2 Invalid only in the deceleration
In actual practical circumstances, the input voltage instability or load requirements of theinverter output voltage, to set the function according to the need
0: Invalid: inverter automatic voltage regulator function is invalid1:The whole invalid e: the inverter according to the load severity, and the level of input
voltage, automatic calculation of the regulated output voltage in order to achieve the effect.2: Invalid only in the deceleration: voltage regulator is invalid in the deceleration of the
inverter
F1.29Torque current filter time Factory value 0.30s
Setting range 0.00~100.00
F2:Input Terminal
F2.00 Terminal Input Filter Time Default Setting 50msSetting Range 0~100
Set the sensitivity of X-terminals.If the digital input terminals are vulnerable tointerference ,which will cause the wrong actions, we should increase the parameters to enhancethe anti-jamming capability,but the sensitivity of the X-terminal will reduce at the same time.
F2.01Multi-functional Input X1 Default Setting 1
Setting Range 0~99
F2.02Multi-functional Input X2 Default Setting 2
Setting Range 0~99
F2.03Multi-functional Input X3 Default Setting 3
Setting Range 0~99
F2.04 Multi-functional Input X4 Default Setting 6
DR300 User's manual
86
Setting Range 0~99
F2.05Multi-functional Input X5 Default Setting 7
Setting Range 0~99
F2.06Multi-functional Input X6 Default Setting 8
Setting Range 0~99
F2.07Multi-functional Input X7 Default Setting 0
Setting Range 0~99
The following parameters are used to set the corresponding functions of the digitalmulti-functional input terminals.
Setting Function Explanation0 Non-function Non-functional Input1 RUN Run Signal / Foreward Signal(FWD)
2 +/- Input Instruction Commutation signals/Reversal signal(REV)
3 Forward Jog Forward Jog(FJOG)
4 Reversal Jog Reversal Jog(RJOG)
5 The control of three-wire operationalstop
The control of three-wire operational stop needs tobe connected to the normally closed turminals.
6 Free Parking Inverter closed output
7 Emergency Parking ( The most rapidstop )
When the terminal is effective,inverter stops withthe fastestly speed.
8 Reset the broken-down inverter Reset the broken-down inverter
9 Base Block If the terminal is effective, the inverter outputsclosely ,or the track will start.
10 Ban Acceleration or Deceleration When the terminal is effective,the frequencyacceleration and deceleration are baned.
11 Multi-speed Terminals 1 Multi-speed terminal combination 112 Multi-speed Terminals 2 Multi-speed terminal combination 213 Multi-speed Terminals 3 Multi-speed terminal combination 314 Multi-speed Terminals 4 Multi-speed terminal combination 4
15 The accelerational and decelerationaltime terminal 1
Time terminal combination 1 of acceleration anddeceleration .
16 The accelerational and decelerationaltime terminal 2
Time terminal combination 2 of acceleration anddeceleration .
17 UP Terminal If terminal is effective, the digital values executeplus operation.
18 DOWN Terminal If terminal is effective, the digital values executesubstruction operation,.
19 Clear UP/DOWN When the terminal is effective, clear the digitalvalue.
20 The input command of parking with DCbraking
If terminal is effective, the inverter stays in the DCbraking.
21 Switch run command to local keyboard Enforce the switch from the run command to localkeyboard.
22 Switch run command to external terminal Enforce the switch from the run command toexternal terminal.
23 Switch run command to PCcommunication
Enforce the switch from the run command to PCcommunication.
DR300User'smanual
87
24 PF Input(Just for X7) Enable the function of high-speed pulse receivefor X7.
25 Switch the speed input to the main speed Set the given mode of speed to the main speedforcely.
26 Switch the speed input to the auxiliaryspeed
Set the given mode of speed to the auxiliary speedforcely.
27 PID Pause Keep PID outputing and without counting.
28 PID switch between positive andnegative role PID switch between positive and negative role.
29 Clear PID integral action Clear PID integral action forcely.30 PID Stop Enfoece PID not output and clear it.
31 Reset PLC RUN Reset program running ( Reset the time, pulseeffectively).
32 PLC Run Pause Program Running Pause
33 Switch the given modle of main speed toAI0 Switch the given modle of main speed to AI0
34 Switch the given modle of main speed toAI1 Switch the given modle of main speed to AI1
35 Switch the given modle of main speed toAI2 Switch the given modle of main speed to AI2
36 Switch the given modle of main speed toPF(X7) Switch the given modle of main speed to PF(X7)
37 Switch the given modle of auxiliaryspeed to AI0 Switch the given modle of auxiliary speed to AI0
38 Switch the given modle of auxiliaryspeed to AI1 Switch the given modle of auxiliary speed to AI1
39 Switch the given modle of auxiliaryspeed to AI2 Switch the given modle of auxiliary speed to AI2
40 Switch the given modle of auxiliaryspeed to PF(X7)
Switch the given modle of auxiliary speed to PF(X7)
41 Change the given modle of speed Change the given modle of speed according toF0.07.
42 Dedicated macro control invalid Switch dedicated macro to the generic macro.43 Switch fault The terminal of switch fault input
44 Switch the speed mode to the torquemode
Switch the control mode of inverter from speed totorque.
45 Clear Count Cleared Counter Terminal
The instructions of multi-speed terminal combination :
K4 K3 K2 K1 Frequency setting The correspondingparameter
OFF OFF OFF OFF Digital frequency F0.12/F0.13OFF OFF OFF ON Multi-segment speedd 1 F7.00OFF OFF ON OFF Multi-segment speed 2 F7.01OFF OFF ON ON Multi-segment speed 3 F7.02OFF ON OFF OFF Multi-segment speed 4 F7.03OFF ON OFF ON Multi-segment speed 5 F7.04OFF ON ON OFF Multi-segment speed 6 F7.05OFF ON ON ON Multi-segment speed 7 F7.06ON OFF OFF OFF Multi-segment speed 8 F7.07ON OFF OFF ON Multi-segment speed 9 F7.08ON OFF ON OFF Multi-segment speed 10 F7.09ON OFF ON ON Multi-segment speed 11 F7.10
DR300 User's manual
88
ON ON OFF OFF Multi-segment speed 12 F7.11ON ON OFF ON Multi-segment speed 13 F7.12ON ON ON OFF Multi-segment speed 14 F7.13ON ON ON ON Multi-segment speed 15 F7.14
The illustration of multi-segment speed:
Terminal 2 Terminal 1 The time selection ofacceleration or
deceleration
The corresponding parameters
OFF OFF Acceleration time 1 F0.16、F0.17OFF ON Acceleration time 2 F7.15、F7.16ON OFF Acceleration time 3 F7.17、F7.18ON ON Acceleration time 4 F7.19、F7.20
F2.08
The positive and negative logic ofterminal input
Default Setting 0000
Setting Range X4 X3 X2 X10 0 0 0
0:positive logic Closure is effective/ Disconnection is invalid1:negative logic Closure is invalid/ Disconnection is effective
F2.09X1 Input Delay Time Default Setting 0.00s
Setting Range 0.00~300.00
F2.10X2 Input Delay Time Default Setting 0.00s
Setting Range 0.00~300.00
Set the delay time of the X1 and X2 terminals in order to reach results of delay action.
F2.11AI0 Input filter time Default Setting 0.30s
Setting Range 0.00~30.00
F2.15AI0 Min Input Default Setting 0.00V
Setting Range 0.00~10.00
F2.16AI0 Max Input Default Setting 10.00V
Setting Range 0.00~10.00
F2.17AI0 Min Output Default Setting 0.0%
Setting Range -100.0~100.0
F2.18AI0 Max Output Default Setting 100.0%
Setting Range -100.0~100.0
The above functional codes define the relationship between the analog input voltage and therepresentatived setting of analog input.When the analog input voltage exceeds the range of the
DR300User'smanual
89
set maximum input or minimum input,the beyong part will be counted as the maximum input orminimum input.When analog input is current ,the current of 1mA is equivalent to the voltage of0.5V.In different applications,the nominal values corresponding to the 100% of the simulationsettings are different.Please refer to the description of each application part for details.
The following pictures illustrate several settings:
The Correspoding Setting
(Frequency,Torque and so on)100.0%
0.0% 0V(0mA)
Setting Frequency(Hz)
100.0%
-100.0%
AI
0V(0mA)
10V(20mA)
Figure 6-7 The relationship between Analog Given and Setting
F2.12AI1 Input Filter Time Default Setting 0.30s
Setting Range 0.00~30.00
F2.19AI1 Min Input Default Setting 0.00V
Setting Range 0.00~10.00
F2.20AI1 Max Input Default Setting 10.00V
Setting Range 0.00~10.00
F2.21AI1 Min Output Default Setting 0.0%
Setting Range -100.0~100.0
F2.22AI1 Max Output Default Setting 100.0%
Setting Range -100.0~100.0
F2.13AI2 Input Filter Time Default Setting 0.30s
Setting Range 0.00~30.00
F2.23AI2 Min Input Default Setting 0.00V
Setting Range 0.00~10.00
DR300 User's manual
90
F2.24AI2 Max Input Default Setting 10.00V
Setting Range 0.00~10.00
F2.25AI2 Min Output Default Setting 0.0%
Setting Range -100.0~100.0
F2.26AI2 Max Output Default Setting 100.0%
Setting Range -100.0~100.0
The setting of AI1 and AI2 are similar to AI0.
F2.14PF Input Filter Time Default Setting 0.30s
Setting Range 0.00~30.00
F2.27PF Min Input Default Setting 0.000kHz
Setting Range 0.000~50.000
F2.28PF Max Input Default Setting 50.000kHz
Setting Range 0.000~50.000
F2.29PF Min Output Default Setting 0.0%
Setting Range -100.0~100.0
F2.30PF Max Output Default Setting 100.0%
Setting Range -100.0~100.0
This functional codes define the corresponding relationships when the pulse is taken asfrequency setting mode.Pulse frequency input only through X7 channel.The applications of thefunction are similar to AI0.
F3 Groups:Output terminals
F3.00
Y1 Select the output mode Default Setting 1
Setting Range0 DO output impulse
1 Y1 output open integrated switchvalue.
Y1 is a programmable multiplexing terminal and can be used as high-speed pulse outputterminal,which maximum frequency is 50kHz.
F3.01Multi-functional Output Y1 Default Setting 5
Setting Range 0~99
F3.02Multi-functional OutpuY2 Default Setting 6
Setting Range 0~99
DR300User'smanual
91
Settings Function Explanation0 Non-function Non-functional Output
1 Inverter Run Inverter stays in the running status output.2 Jog Status Inverter output in the jog status
3 Reverse StatusInverter output in the negative frequency outputstatus
4 Frequency Output RangeFAR
Frequency output within in the FAR,which is
determined by the parameters of F11.13.
5 The level of frequency outputFDT1
Frequency reaches FDT1 ,which is determined
by F3.22 and F3.23.
6 The level of frequency outputFDT2
Frequency reaches FDT2,which is determined
by F3.24 and F3.25.7 Inverter Fault Inverters stays in a failed state and stop.
8 Inverter AlarmInverters stay in alarm state and runcontinuously.
9 Inverter complete theoperational preparation
Inverter output in the trouble-free state
10 Reach the maximumfrequency
Frequency reaches the upper limit frequencyoutput
11 Reach the minimumfrequency
Frequency reaches the lower limit frequencyoutput
12 Zero speed detection Detection of electric speed output is zero.13 Motor zero-current detection Detection of electric current output is zero.
14 X1 Terminal input iseffective.
Input effective value from X1 terminal.
15 X2 Terminal input iseffective.
Input effective value from X2 terminal.
16 Counter reaches the actionThe counter act when the count value of theinverter input terminals mee to the operatingconditions .
17 Stop command Stop command output effectively.18 Analog level Output analog level ADT1.
19 Inverter speed up and downInverter stays in the acceleration or decelerationstate.
F3.03Relay Output R1 Default Setting 7
Setting Range 0~99
DR300 User's manual
92
The functional codes determine the action time of the output terminals Y1, Y2, R1 and so
on.When it meet the output operating conditions,the terminals will act after the output delay
time.
The standard analog output is 0mA ~ 20mA(or 0V~10V).The output range of DO is50KHz.The ranges of correspondings are showed in the following table:
Setting Function Range0 Reference Inpu Max Frequency1 Output Frequency Max Frequency2 Output Current Inverter rated current3 Output Voltage Inverter rated voltage4 AI0 10.00V5 AI1 10.00V6 AI2 10.00V7 PF(X7) Max Input Pulse Frequency8 +10V +10V9 PID Input 10.00V10 PID Feedback 10.00V
11 Bus Voltage Bus voltage under the rated voltagecondition
12 Output power Inverter rated power
F3.04Y1 Output delay time Default Setting 0.0s
Setting Range 0.0~600.0
F3.05Y2 Output delay time Default Setting 0.0s
Setting Range 0.0~600.0
F3.06R1 Output delay time Default Setting 0.0s
Setting Range 0.0~600.0
F3.07Analog output AO1 Default Setting 1
Setting Range 0~99
F3.08Analog output AO2 Default Setting 1
Setting Range 0~99
F3.09Pulse output DO Default Setting 1
Setting Range 0~99
F3.10AO1 Min Input Default Setting 0.00%
Setting Range 0.00~100.00
F3.11AO1 Max Input Default Setting 100.00%
Setting Range 0.00~100.00
F3.12AO1 Min Output Default Setting 0.00%
Setting Range 0.00~100.00
F3.13 AO1 max Outpu Default Setting 100.00%
DR300User'smanual
93
The function codes define the relationships between the analog output voltage andrepresentative setting of the analog output . When the analog output voltage exceeds the range ofmaximum output or minimum output. The excess portion will be counted as the maximumoutput or the minimum output.
When analog outputs is current, 1mA current is equivalent to 0.5V voltage. In differentapplications, the corresponding nominal value of simulation settings 100% are different. Pleaserefer to the description of each application parts for details.
AO2 only support the voltage output, The remaining reference to AO1 instructions.
When Y1 terminal is set to DO output(F3.00=0),DO high-speed pulse output iseffective.Reference to AO1 output instructions.
Setting Range 0.00~100.00
F3.14AO2 Minimum input Factory value 0.00%
Setting range 0.00~100.00
F3.15AO2 Maximum input Factory value 100.00%
Setting range 0.00~100.00
F3.16AO2 Minimum input Factory value 0.00%
Setting range 0.00~100.00
F3.17AO2 Maximum input Factory value 100.00%
Setting range 0.00~100.00
F3.18 DO Minimum input Factory value 0.00%Setting range 0.00~100.00
F3.19DO Maximum input Factory value 100.00%
Setting range 0.00~100.00
F3.20DO Minimum input Factory value 0.00%
Setting range 0.00~100.00
F3.21DO Maximum input Factory value 100.00%
Setting range 0.00~100.00
F3.22FDT1 Upper bound Factory value 50Hz
Setting range 0.00~Fmax
F3.23FDT1 Lower bound Factory value 49Hz
Setting range 0.00~Fmax
F3.24FDT2 Upper bound Factory value 25Hz
Setting range 0.00~Fmax
F3.25FDT2 Lower bound Factory value 24Hz
Setting range 0.00~Fmax
DR300 User's manual
94
This function is used to detect whether the output frequency is in the setting FDT,Ifthe output frequency of the inverter is in the corresponding FDT setting range ,outputindication signal
Output Frequency
FDT Power LevelUpper Bound
FDT Power LevelLower Bound
Y Terminal100.0%
100.0%Figure 6-8 Frequency level detection signal FDT
F3.26
FDT Output options Factory value 0
Setting range0 Point move not output
1 Point dynamic output
This function determines whether the the FDT output terminal is effective in the jog state.
F3.27
Multi-function terminal OutputSelect Factory value 00
Setting range
Bits(Inputterminals
X)
0 The actual terminal effective
1 Virtual terminal effective
Tens place(Outputterminals
Y)
0 The actual terminal effective
1 Virtual terminal effective
This function determines whether the input and output terminals is the actual terminaleffective or PC communication virtual terminal effectvel,the mailing address is the0x3006.The detail please check in the communication protocol.
DR300User'smanual
95
F4 Group:start and stop buttons display
F4.00
Startup mode selection Factory value 0
Setting range
0 Started by the starting frequency
1 then start the first DC injection braking
2 Speed track start
0:Started by the starting frequency:started from the starting frequency.Applicable to smallinertial load, may produce reversal occasions when starting.
1:then start the first DC injection braking:first implement the DC brake and then start.2:Speed of the track and then restart:Inverter motor first judge the speed and
direction.Then start with the tracking of the motor speed frequency.No impact to start therotational motor smoothly. Applicable to momentary power failure restart of high inertia loads.Inorder to ensure the performance of speed tracking on it again,need to set accurate motorparameters.(F1 group)
In order to ensure the torque on startup,please set the appropriate starting frequency. Inaddition, in order to wait for motor to build the magnetic flux when starting,the start frequencyshould maintain a certain time after starting acceleration.Startting lower frequency value F4.01 isnot limited.if frequency setpoint (frequency source) is less than the starting frequency,theinverter can not start,in standby mode.Reversible switching,starting frequency maintenance timedoes not work.Maintenance time is not included in the acceleration time,but is included in thesimple PLC running time.
Start the DC braking is generally used before the motor stopped completely and then start.Ifthe motor started directly, then inverter brake by the DC braking voltage, after set starting DCbraking time and then started running.If set DC braking time to 0,it will start directly does notpass by the DC braking.The greater the DC braking current,The greater the braking force.
Starting DC braking voltage refers to the percentage relative to rated voltage of inverter.
F4.01Starting frequency Factory value 0.00Hz
Setting range 0.00~60.00
F4.02Starting frequency to maintain time Factory value 0.00s
Setting range 0.00~60.00
F4.03 Start the DC brake voltage Factory value 2.00%Setting range 0.00~30.00
F4.04Start the DC braking time Factory value 0.00s
Setting range 0.00~30.00
DR300 User's manual
96
F4.05
Parking options Factory value 0
Setting range0 Slow down and stop
1 Free Parking
0:Deceleration parking:After stop command is valid,the inverter in accordance with thedeceleration mode and the definition of acceleration and deceleration time reducing the outputfrequency, the frequency is reduced to zero and then shutdown.
1:Free Parking:after stop command is valid,inverter immediately terminate the output.Loadfree parking in accordance with the mechanical inertia.
Stop DC brake start frequency:deceleration in the shutdown process.When you arrive at thefrequency,start shutdown DC braking.
Shutdown DC brake voltage:refers to the increase the amount of DC braking.The larger thisvalue,the stronger DC braking effect is.
Shutdown DC brake time: refers to the increase time of DC braking amount.When thisvalue is 0:00,indicating that there is no DC braking process,The inverter according to thedeceleration during shutdown Parking.
F4.09
Acceleration and decelerationcurves Factory value 0
Setting range0 Linear acceleration and deceleration
1 S-curve acceleration and deceleration
Select the way in starting and stopping process of inverter frequency change.0:Linear acceleration and deceleration:Output frequency in accordance with the line
increment or decrement.Acceleration and deceleration time in accordance with the setdeceleration time.DR300 series inverter provides four kinds of acceleration and decelerationtime.Deceleration time can be selected by multi-function digital input terminal (F2.01 ~ F2.07).
1:S-curve acceleration and deceleration:The output frequency is incremented ordecremented according to the S-curve.S-curve is generally used in a more gentle place to startand stop the process requirements,such as elevators, conveyor belts.Parameter definition seeF4.10 to F4.13.
F4.06Parking DC braking frequency Factory value 2.00Hz
Setting range 0.10~60.00
F4.07Parking DC braking voltage Factory value 2.00%
Setting range 0.00~30.00
F4.08Parking DC braking time Factory value 0.00s
Setting range 0.00~30.00
DR300User'smanual
97
Set the S-curve acceleration segment start、S-curve acceleration segment end、S-curvedeceleration start、S-curve deceleration segment end.In the beginning and end,Deceleration timewill only extend 1/2 of the linear time.Set instances,S-curve characteristic time of the run switch(Forward / Reverse) as shown below:
Forward
Reverse
Frequency F4.10
F4.11 F4.12F4.13
F4.10
F4.11 F4.12
F4.13
Figure 6-9 S-curve characteristics
F4.14
LCD language selection Factory value 0
Setting range0 Chinese
1 English
Effective for LCD keypad.Select word mode of LDC.
F4.15
Auxiliary Display Selection Factory value 0
Setting range0 Speed
1 Line speed
F4.16Coefficient of the secondary display Factory value 30.00%
Setting range 0.01~600.00
H0.04/H0.05 of display options, line speed is optional.You can also display
F4.10S-curve acceleration segment start Factory value 30.00%
Setting range 0.00~50.00
F4.11S-curve acceleration segment end Factory value 30.00%
Setting range 0.00~50.00
F4.12S-curve deceleration start Factory value 30.00%
Setting range 0.00~50.00
F4.13The end of the S-curve deceleration Factory value 30.00%
Setting range 0.00~50.00
DR300 User's manual
98
speed.H0.04=F4.16×H0.02.
F4.17Keyboard interface jump Factory value 1
Factory value0 Do not jump1 Jump
The F4.17 functions decided the keyboard to occur jump or not when changing the inverter state.
Decide the keyboard Jump address.
F4.25
Key lock function Factory value 0
Setting range
0 Not locked
1 Full lock
2 Lock in addition to the multifunction key
3 Lock in addition to RUN and STOP/RESET
0:Not locked:Do not lock button on the operation panel.All keys are in a usable state.1:Full lock:Lock buttons on the operation panel,All keys are in an unusable state.2:In addition to the multifunction key locked:In addition to the multifunction key,all keys are in an
unusable state.3:lock keys except RUN and STOP/RESET,All keys are in an unusable state.
F4.26
Parameter copy(Only effective forLCD keyboard) Factory value 0
Setting range
0 Non-functional
1 Parameter upload
2 Parameters downstream(Without themotor parameters)
3 Parameters downstream ( With themotor parameters)
F4.18Standby display code Factory value 0x0380
Factory value 0x0000~0x039F
F4.191 Line shows the code Factory value 0x0382
Factory value 0x0000~0x039F
F4.202Line shows the code Factory value 0x0387
Factory value 0x0000~0x039F
F4.213Line shows the code Factory value 0x0388
Factory value 0x0000~0x039F
F4.224Line shows the code Factory value 0x038A
Factory value 0x0000~0x039F
DR300User'smanual
99
0:Non-functional1:Parameter upload2:Parameters downstream(Without the motor parameters)3:Parameters downstream(With the motor parameters)
F5 Group: PID function
PID control is a commonly used method for process control, Based on difference between theamount of feedback signal and target signal sent proportion integral differential operation, adjusting theoutput of the inverter frequency, constitute a negative feedback system, The controlled volumestabilized in the target volume. Suitable for flow control, pressure control and temperature control andother process controls. Control the basic principles of block diagram are shown in Figure 6-10.
DeviationRestriction
1 1Ti S
Td*S+1 P
1FeedbackVolume
TargetVolume
+
-
Figure 6-10 Process PID block diagram
F4.27Keyboard software version Factory value XXXX
Setting range 0.00~99.99
F4.28Functional version of the software Factory value XXXX
Setting range 0.00~99.99
F4.29Performance software version Factory value XXXX
Setting range 0.00~99.99
F4.30Factory password Factory value XXXX
Setting range 0~65535
F4.31User password Factory value XXXX
Setting range 0~65535
DR300 User's manual
100
F5.00
PID Dimension Factory value 0
Setting range
0 V
1 Mpa
2 M/min
3 N
4
5 rpm
F5.01PID Dimension Factory value 10.00
Setting range 0.01~600.00
F5.02
PID Decimal places Factory value 2
Setting range
0 Without decimal
1 A decimal
2 Two decimal
3 Three decimal
F5.00, F5.01 and F5.02 to set the properties of PID control.
F5.03
PID Setting mode Factory value 0
Setting range
0 PID setting
1 AI1
2 AI2
3 AI3
4 PF(X7)
Goal for the selection process PID given channel.The target amount which Process PID set is relative value. Set 100% corresponds to 100%
of the feedback signal of the controlled system.
F5.04PID setting Factory value 5.00
Setting range 0.00~600.00
When F5.03 set to 0, this parameter must be set. This parameter baseline values are forPID.When the PID is effective, Keyboard "Λ" and "V" key can quickly manipulate thisparameter.
DR300User'smanual
101
F5.05
PID Feedback to select Factory value 0
Setting range
0 PID feedback
1 AI1
2 AI2
3 AI3
4 PF(X7)
Used to select feedback channel of PID.
F5.06Feedback of PID Factory value 5.00
Setting range 0.00~600.00
F5.07Set the filter time of PID Factory value 0.00s
Setting range 0.00~100.00
When set value change of PID filtering time.
F5.08The default value of PID Factory value 5.00
Setting range 0.00~600.00
F5.09PID preset time Factory value 0.00s
Setting range 0.00 ~ 100.00
Set the PID default value and default time properly, Enable the closed loop adjustmentquickly access to the stable phase.
F5.10
Controlling options of PID Factory value 1
Setting range0 Invalid
1 Effective
PID control is effective or not.
F5.11
Regulator role of PID Factory value 0
Setting range0 Positive role
1 Reaction
DR300 User's manual
102
Positive role: If the feedback signal is less than a given signal of the PID, it requires that theinverter output frequency is increased to make the PID balanced .Such as winding tension PIDcontrol.
Reaction: If the feedback signal is less than a given signal of the PID, requires that theinverter output frequency is decreased to make the PID balanced. Such as unwinding tensionPID control.
F5.13Proportional gain P Factory value 2.0
Setting range 0~1000.0
F5.14Integration time I Factory value 2.000s
Setting range 0.000~30.000 0.000:No points
F5.15Differential time D Factory value 0.000s
Setting range 0.000~10.000
Proportional gain P:Decided the strength of the adjustment of the PID regulator,Pgreater the adjusting intensity is greater. This parameter is 100, said when the PID feedbackamount, and the given quantitation deviation is of 100%,PID regulator adjusting amplitudeis the maximum frequency to the output frequency instructions(Ignore the integral actionand derivative action).
Integration time I : Determine the PID regulator integral adjusting speed to thedeviation of the PID feedback amount and the given quantitation.Integration time is whenthe PID feedback amount and given quantitation deviation is 100% , integral regulator(ignore proportional action and derivative action) after the time for continuous adjustment,the adjustment amount reached the maximum, the shorter the integration time, the greaterthe adjusting intensity.
Differential time D : Determine the PID regulator deviation change rate adjustingintensity of the PID feedback amount and the given quantitation. Differential time is that ifthe feedback amount changes 100% in the time, the adjusting amount of the differentialregulator is the largest , (ignore proportional action and integral action).the longer thedifferential time, the greater the adjusting intensity.
F5.16Deviation limits Manufactured value 0.00%
Setting range 0.00~20.00
Set the maximum allowable deviation of system feedback value and the givenquantitation,When PID feedback and the given deviation within the scope,PID stopsregulating. Deviation limit is calculated according to the percentage of PID setpoint source(or feedback source) .
Appropriate settings for this feature will help balance the precision and stability of thesystem output .Bias time limition is shown in Figure 6-11:
DR300User'smanual
103
Feedback amout
Given quantitation
Output frequency Hz
Time t
Time t
Figure 6-11 Deviation limit schematic
F5.17Positive limitation of the outputfrequency Manufactured value 50.00Hz
Setting range 0.00~600.00
F5.18Negative limitation of the
output frequency Manufactured value 50.00Hz
Setting range 0.00~600.00
Ultimately limited frequency of the PID output.
F5.19
PID auxiliary control Manufactured value 00
Setting range
Bits: Pointsinput way
0 PID input after starting deadtime
1 PID output soft-start time beforeinput
10:FeedbackControl
0 Setting value
1 Switching to a set value fromthe feedback value
Bits:0:PID input after starting dead time;1:PID output soft-start time before input10:
DR300 User's manual
104
0:PID setting is always the set value1:Switching to a set value from the feedback value
F5.20
PID output smooth control Manufactured value 0
Setting range0 Soft-start time of the PID output,
linear to the PID output gain1 PID output gain
F5.20=0:Soft-start time of the PID output,,linear to the PID output gain,to make the PIDoutput smoothly rise to the current PID output value.
F5.20=1:No soft-start,directly output the current PID values when the PID dead timearrived
F5.21PID dead time Manufactured value 0.00s
Setting range 0.00~60.00
F5.22PIDsoft-start time Manufactured value 0.00s
Setting range 0.00~60.00
PID dead time is when the inverter is set to the PID control, issue a start command, waitingfor the time of the PID regulator output, now PID controller output is 0.
PID soft-start time,means after the dead time of the PID output, in order to avoid themutation of the PID output, set the output gain increased linearly from 0 to the time settings.
F5.23PID setting upper limits Manufactured value 100.00
%
Setting range 0.00~100.00
F5.24PID setting lower limits Manufactured value 0.00%
Setting range 0.00~100.00
Used to restrict the output value of PID.When PID output frequency is given, the maximum output frequency is 100%When the PID output has given as torque ,make 300% rated torque as 100%
F5.25
PID switch selection Manufactured value 0
Setting range
0 Only a set of PID
1 AI1
2 AI2
3 AI1-AI2
4 PF(X7)
DR300User'smanual
105
F5.26Proportional gain P2 Manufactured value 2.0
Setting range 0~1000.0
F5.27Integration time i2 Manufactured value 2.000s
Setting range 0.000~30.000 0.000:No integral
F5.28Differential time d2 Manufactured value 0.000s
Setting range 0.000~10.000
F5.29PID positive output gain Manufactured value 100.00%
Setting range 0.00~100.00
F5.30PID negative output gain Manufactured value 100.00%
Setting range 0.00~100.00
Adjust the final output of the gain coefficient, the final output of the PID = to the PID output ×
the PID output gainUsed to adjust the amount of compensation will have notable effect.
F6 Group: the PLC run
Simple PLC function is a simple programmable controller (PLC) built-in inverter tocomplete automatic control of the multi-frequency logic.You can set the running time, runningdirection, the operating frequency to meet process requirements.
The inverter can achieve the 7-speed change control , there are four kinds ofacceleration and deceleration time options. When set PLC completed a cycle, it can usemulti-functional digital output terminal Y1 or multi-function relays (RELAY) output PLCto complete the cycle indication signal,detailed in F3 group output terminal “PLC completethe loop "function description.
When the main speed given mode (F0.08), or auxiliary speed given mode (F0.09) isset to multi-speed operation mode, Just set F6.00 ~ F6.08 to determine its characteristics .
F6.00
PLC operation mode Manufactured value 0
Setting range
0 Round robin
1 Run by period 7 after the round robin
2 Finite continuous cycle
3 Continuous cycle
Speed program operation mode selection0:Round robin. after these seven periods according to their own time and direction run
finish, stop the inverter.
DR300 User's manual
106
1:Run by period 7 after the round robin and these seven periods according to theirown time and direction run finish,Keep running speed of the seventh periods.
2:Finite continuous cycle. after these seven periods according to their own time anddirection run finish,back to the first paragraph of the cycle of operation, when the cycle ofoperation times reaches the set value, stop the inverter.
3:Continuous cycle:When it completes a cycle, the inverter automatically to the nextcycle, until a stop command to shut down.
F6.01 PLC program interruption mode Manufactured value 0
Setting range0 Starts running from the
interruption periods
1 Running from the firstparagraph(start running clear)
Set PLC interrupts mode, to select the starting point of the execution of an interrupt.
F6.02
PLC run-time units Manufactured value 0
Setting range0 sec(second)
1 min(minute)
Set the PLC at every stage of operation of the unit of time, Optional time in seconds
PLC power-down memory ; before the operational phase of PLC of the memorypower-down ,If the power-on and then run,from the memory stage timing run.
F6.04the Speed cycle times Factory value 1
The setting range 1~10000
Set the number of the speed loop .
F6.05
T1 choice of direction Factory value 0
The setting range 0 The positive dieection
1 Reversed direction
F6.03
PLC power - downmemory options Factory value 0
Thesettingrange
0 power - down is not memory
1 power - down memory
DR300User'smanual
107
F6.06
T2 choice of direction Factory value 0
The setting range 0 The positive direction
1 Reversed direction
F6.07
T3 choice of direction Factory value 0
The setting range 0 The positive direction
1 Reversed direction
F6.08
T4 choice of direction Factory value 0
The setting range 0 The positive direction
1 Reversed direction
F6.09
T5 choice of direction Factory value 0
The setting range 0 The positive direction
1 Reversed direction
F6.10
T6 choice of direction Factory value 0
The settingrange
0 The positive direction
1 Reversed direction
F6.11
T7 choice of direction Factory value 0
The settingrange
0 The positive direction
1 Reversed direction
The motor running direction selection during the program working.0:motor forward;1:motor reverse;
( the inversion is invalid if the reverse function is prohibitted)
F6.12
T1 acceleration and deceleration selection Factory value 0
The setting range0 acceleration and deceleration time 1
1 acceleration and deceleration time 2
DR300 User's manual
108
2 acceleration and deceleration time 3
3 acceleration and deceleration time 4
F6.13
T2 acceleration and deceleration selection Factory value 0
The setting range
0 acceleration and deceleration time 1
1 acceleration and deceleration time 2
2 acceleration and deceleration time 3
3 acceleration and deceleration time 4
F6.14
T3 acceleration and deceleration selection Factory value 0
The setting range
0 acceleration and deceleration time 1
1 acceleration and deceleration time 2
2 acceleration and deceleration time 3
3 acceleration and deceleration time 4
F6.15
T4 acceleration and deceleration selection Factory value 0
The setting range
0 acceleration and deceleration time 1
1 acceleration and deceleration time 2
2 acceleration and deceleration time 3
3 acceleration and deceleration time 4
F6.16
T5 acceleration and deceleration selection Factory value 0
The setting range
0 acceleration and deceleration time 1
1 acceleration and deceleration time 2
2 acceleration and deceleration time 3
3 acceleration and deceleration time 4
F6.17
T6 acceleration and deceleration selection Factory value 0
The setting range
0 acceleration and deceleration time 1
1 acceleration and deceleration time 2
2 acceleration and deceleration time 3
3 acceleration and deceleration time 4
F6.18
T7 acceleration and deceleration selection Factory value 0
The setting range0 acceleration and deceleration time 1
1 acceleration and deceleration time 2
DR300User'smanual
109
2 acceleration and deceleration time 3
3 acceleration and deceleration time 4
Set acceleration and deceleration time during the procedure is running , and theacceleration time must set individually .
acceleration and deceleration time 1 effectiveacceleration and deceleration time 2 effectiveacceleration and deceleration time 3 effectiveacceleration and deceleration time 4 effective
F6.19T1 running hours Factory value 30.0s/min
setting range 0.0~6000.0
F6.20T2 running hours Factory value 30.0s/min
setting range 0.0~6000.0
F6.21T3 running hours Factory value 30.0s/min
setting range 0.0~6000.0
F6.22T4 running hours Factory value 30.0s/min
setting range 0.0~6000.0
F6.23T5 running hours Factory value 30.0s/min
setting range 0.0~6000.0
F6.24T6 running hours Factory value 30.0s/min
setting range 0.0~6000.0
F6.25T7 running hours Factory value 30.0s/min
setting range 0.0~6000.0
F6.19~F6.25 define the seven sections of the program running time separately, and it couldbe continuous set within the range of 0.0 to 6000.0 seconds / min.
F7 Group: multi-speed, multi-segment Acceleration anddeceleration time, digital frequency adjustment
According to the Speed control terminal and 16 of the frequency instruction combined withthe keyboard figures and simulation of given, it can provide a 16-segement speed. In addition,superimposed on the analog inputs can also be adjusted.
DR300 User's manual
110
F7.00Multi speed 1 Factory value 1.00Hz
setting range 0.00~Fmax
F7.01Multi speed 2 Factory value 2.00Hz
setting range 0.00~Fmax
F7.02Multi speed 3 Factory value 3.00Hz
setting range 0.00~Fmax
F7.03Multi speed 4 Factory value 4.00Hz
setting range 0.00~Fmax
F7.04Multi speed 5 Factory value 5.00Hz
setting range 0.00~Fmax
F7.05Multi speed 6 Factory value 6.00Hz
setting range 0.00~Fmax
F7.06Multi speed 7 Factory value 7.00Hz
setting range 0.00~Fmax
F7.07Multi speed 8 Factory value 8.00Hz
setting range 0.00~Fmax
F7.08Multi speed 9 Factory value 9.00Hz
setting range 0.00~Fmax
F7.09Multi speed 10 Factory value 10.00Hz
setting range 0.00~Fmax
F7.10Multi speed 11 Factory value 11.00Hz
setting range 0.00~Fmax
F7.11Multi speed 12 Factory value 12.00Hz
setting range 0.00~Fmax
F7.12Multi speed 13 Factory value 13.00Hz
setting range 0.00~Fmax
F7.13Multi speed 14 Factory value 14.00Hz
setting range 0.00~Fmax
F7.14Multi speed 15 Factory value 15.00Hz
setting range 0.00~Fmax
F7.00~F7.14 represent multi speed 1~15 , during the range of 0.00~fmaxHz, It can be
DR300User'smanual
111
continuous setted. Multi speed could be used in procedure , and also be controlled by multispeed terminal.
When the program is controlled by multi speed terminal, firstly, program three inputing postsas the multi speed post ,And then through a combination of state of the three input in terminals,program corresponds multi speed 1 and 15 separately.
F7.15Acceleration time 2 Factory value 12.00s/min
setting range 0.00~600.00
F7.16Acceleration time 2 Factory value 12.00s/min
setting range 0.00~600.00
F7.17Acceleration time3 Factory value 13.00s/min
setting range 0.00~600.00
F7.18Acceleration time3 Factory value 13.00s/min
setting range 0.00~600.00
F7.19Acceleration time4 Factory value 14.00s/min
setting range 0.00~600.00
F7.20Acceleration time4 Factory value 15.00s/min
setting range 0.00~600.00
In addition to the previously defined 1 (F0.16) acceleration time and deceleration time 1(F0.17), you can also define three sets of acceleration, deceleration time, by defining amulti-function X terminal to a different terminal state to select a different acceleration anddeceleration time, ON terminals, OFF terminal invalid.
Set Note:The acceleration and deceleration time are controlled and selected by F7.15 ~ F7.20 as
well as digital multi-function input terminal 11 to 14 when the Multi-segment speed isrunning .
Multi-segment speed run by the F / R and the RUN terminal is ON or not,,If the F / R isON, the multi-speed should be reversed ;
If the multi-stage process needs reversing ,Set the start and stop control program for theterminal and F0.27=0for 0(Allow reversing ).
F7.21 Keyboard ∧/∨Digital frequency control Factory value 12000
DR300 User's manual
112
Thesettingrange
Bits :to save when Powerdown
0 no Save when power - down
1 Save when Power-down
Ten :control of clear whendowntime
0 not cleared when Downtime
1 Cleared when decelerationstop
2 Cleared when standby time
hundred :
Keyboard∧/∨adjustmentsettings
0 Only effective for the timerof digital frequency
1 total effective when Adjust
2 total Invalid when Adjust
thousand :way to Points
0 Set the integral rate
1 Set the frequency rate
2 Automatic integrated rate
Million-bit :Commutation select
0 Bi-directional adjustment
1 Not Bi-directional adjustment
F7.22
Keyboard ∧/∨The integrated rate Factory value 2.00s
The setting range 0.00~4.99
DR300User'smanual
113
F7.23
Keyboard∧/∨Frequency rate Factory value 0.10Hz/s
The setting range 0.00~100.00
F7.24
UP/DNDigital adjust and frequency control Factory value 0000
The settingrange
Bits :to save when Powerdown
0 no Save when power - down
1 Save when Power-down
Ten :control of clear whendowntime
0 not cleared when Downtime
1 Cleared when deceleration stop
2 Cleared when standby time
hundred:UP/DN adjustmentsettings
0 Only effective for the timer ofdigital frequency
1 total effective when Adjust
2 total Invalid when Adjust
thousand:way to Points
0 Set the integral rate
1 Set the frequency rate
2 Automatic integrated rate
Million-bit :Commutationselect
0 Bi-directional adjustment
1 Not Bi-directional adjustment
F7.25UP/DN The integrated rate Factory value 2.00s
The setting range 0.00~4.99
F7.26UP/DN Frequency rate Factory value 0.10Hz/s
The setting range 0.00~100.00
This feature of the F7.21 settings related to ∧ / ∨ to adjust the frequency of the operationpanel ,when Operation panel to display the status of parameters of running or shutdown .Theoperation panel ∧ / ∨ to adjust the frequency setting is the most easy way ; After the operation
DR300 User's manual
114
panel ∧ / ∨ adjustable frequency amount will be saved inside the drive. And superimposed onthe frequency of the other set as a final set frequency .∧ / ∨ digital operation panel of thefrequency control F7.21 to determine the role of the operating panel ∧ / ∨ Adjustment .Theoperation panel ∧ / ∨ points rate F7.22 identified using the ∧ / ∨ to adjust, increase ordecrease the amount of refresh time .The F7.21 functional description:
Bit: action when Power down0:After adjust set frequency of The operation panel ∧ / ∨ , When the drive is powered
down, The operation panel ∧ / ∨ adjustment amount will be automatically recorded.1: After adjust the set frequency of the operation panel ∧ / ∨, When the drive is powered
down, The operation panel ∧ / ∨ adjustment amount will be automatically cleared.bit: Action when shutdown0 : After the shutdown, the operation panel ∧ / ∨ amount of the adjustment remains
unchanged.1:when Deceleration stop ,The operation panel ∧ / ∨ regulation is cleared after the stop
command is issued.2 : Standby mode, The operation panel ∧ / ∨ regulation is cleared at shutdown ,The
shutdown can not use the ∧ / ∨ to adjust the set frequency.hundred: to adjust the setting of The operation panel ∧ / ∨ .0:Only effective when given in the main setting for the open-loop digital frequency.1: all frequencies for a given mode are valid.2: Disable the operation panel ∧ / ∨ to adjust.1000 bits: integral way0: set the integration rate. From 0 to maximum frequency of the time required will be set by
parameter F7.22.1: Set the frequency rate. when using the operation panel ∧ / ∨ to adjust the set
frequency, the step length is fixed at 0.1Hz.2: Automatic integration rate. when using the operation panel ∧ / ∨ to adjust the set
frequency, Continuous adjustment of a direction will have the effect of the integral.The regulating of the step length from from 0.01Hz, and the amount of adjustment step is
10 times larger after 10 times of each adjustment which step up to 1.00Hz.Million-bits: operating panel ∧ / ∨ to adjust the setting.0: two-way adjustment. When the ∧ / ∨ is used to adjust the frequency, it could allows the
inverter to switch direction.1: not two-way adjustment. The inverter can not switch the direction when use∧ / ∨ to adjust the frequency.
Note: In the process of closed-loop PID Running time, the operator panel ∧ / ∨ can alsoused to adjust the closed-loop given when regarded as the analog overlay given in closed loop,and the step length from 1mV.
F7.22 terminal UP / DN interal rate are 0.00 ~ 4.99s.Note: F7.21 ~ F7.23 is for keyboard ∧ / ∨ keys, F7.24 ~ F7.26 is set to 17, 18) for
terminal UP / DN (input terminal function.
DR300User'smanual
115
F8 Group: vector control torque is given
F8.00Speed loop proportional coefficient ASR-P1 Factory value 2.00%
The setting range 0.00~100.00
F8.01Speed loop proportional coefficient(ASR_Ti1) Factory value 0.100s
The setting range 0.000~30.000
F8.02Speed loop proportional coefficient(ASR_P2) Factory value 0.50%
The setting range 0.00~100.00
F8.03Speed loop proportional coefficient(ASR_Ti2) Factory value 0.300s
The setting range 0.000~30.000
Adjust the proportional gain and integration time of the speed regulator.Inverter is adjustting speed dynamic response of vector control though adjusting the speed
of the PID regulator proportional gain ,Speed integration time and the speed differential timewhen there are no PG vector control mode. Increasing the velocity proportional gain, reducingthe speed of integration time or increasing the speed differential time can accelerate the speedloop dynamic response. If the speed proportional gain is too large, the speed integration time istoo small or speed differential time too large, it will lead to larger System overshoot and shock.
The user should adjust the PID parameters according to the actual load characteristicsensure that the system does not shock , try to increase the proportional gain and adjust theintegration time and differential time so as to make the system both fast response characteristicsand litter overshoot.
To make the system to have a fast dynamic response in both low-speed and high-speed, itneed PID regulator in both low-speed and high-speed .When switching frequency is below zero,the speed of the PID parameters is P1, of Ti1. When the switching frequency above 1, the speedof the PID parameters is P2,Ti2. When F8.05 switching frequency 1 greater than the F8.04switching frequency 0, the process of switching frequency 0 to switching frequency is linearover-process as Shown in Figure 6-12.
PID
P1,Ti1
P2,Ti2
Speedf1 f2Figure 6-12 PID parameters schematic
DR300 User's manual
116
F8.04Speed loop switching rate 0 Factory value 5.00Hz
Setting range 0.00~switching frequency 1
F8.05Speed loop switching rate 1 Factory value 10.00Hz
Setting range Switching frequency 0~Fmax
The PI parameters between the frequency band of switching frequency and 2 are two sets ofPI parameters of linear switched.
F8.06ASR Input filter time Factory value 0.040s
Setting range 0.000~30.000
F8.07ASR Output filter time Factory value 0.040s
Setting range 0.000~30.000
F8.06 This function defined the input filter time of automatic speed regulator (ASR).Ingeneral, it doesn’t need to change.
F8.06 This function defined the output filter time of automatic speed regulator (ASR).Ingeneral, it doesn’t need to change.
F8.08torDrive torque limit Factory value 180.00%
Setting range 0.00~200.00
F8.09Drive torque limit Factory value 180.00%
Setting range 0.00~200.00
F8.08 and F8.09 are used to limit the maximum output torque of the inverter whose limitvalues are the relative percentage of rated motor output torque. In addition, large braking torqueis required with the use of dynamic braking.
F8.10
Choice of Torque control Factory value 0
Setting range0 Invalid Torque control
1 Valid Torque control
0:Invalid Torque control. Inverter is used to control ordinary speed.The inverter can outputthe frequency according to the set frequency command. What’s more, the output torque canmatch with the load torque automatically. However, when the load torque is greater than the settorque limit, restricted by the torque limit(refer to F8.11 and F8.12),the output torque of theinverter is limited, as the result of which the output frequency will differ from the set frequency.
1:Valid Torque control. The inverter is used for torque control. The inverter can output the
DR300User'smanual
117
torque according to the set torque command. At the moment, the output frequency can matchwith the load speed automatically. However, when the load speed is greater than the setfrequency limit, restricted by the frequency limit, the output frequency of the inverter is limited,as the result of which the output torque will differ from the set torque. At present, the torquecommand is just the torque limit which can be set by the source of the torque limit(F8.11).Through a multi-function input terminal it can switch between the torque control and the speedcontrol. Now, the output frequency of inverter can track the changes of the load speedautomatically. Nevertheless, as the rate of change of the output frequency is influenced by theacceleration and deceleration time, if the tracking speed needs to be improved, the decelerationtime should be short down. When the set torque of the inverter is greater than the load torque, theoutput frequency of the inverter will rise .And at the time of the output frequency of the inverterreach upper limit, the inverter will operate in the upper limiting frequency. When the set torqueof the inverter is smaller than the load torque, the output frequency of the inverter will drop. Andat the time of the output frequency of the inverter reach lower limit, the inverter will operate inthe lower limiting frequency.
F8.11
Torque limit source Factory value 0
Settingrange
0 Torque limit
1 AI0(Keyboard potentionmeter)
2 AI1
3 AI2
4 PF(X7)
5 AI1+AI2
6 AI1-AI2
F8.12Torque limit Factory value 5.55%
Setting range 0.00~150.00
Under the speed control mode, F8.11 is used to choose the set source of the torque upperlimit. When the setting is analogue,100%of the analog input is corresponding to F8.12,and 100%is corresponding to the motor standard torque which is mating to the inverter. In torque controlmode, the torque upper limiting source is the torque setting source. And the torque limit is thetorque setting command.
DR300 User's manual
118
F9 Group:Communication
F9.00Local address Factory value 1
Setting range 1~247 0:Broadcast address
This function code is used to identify the address of the inverter. The local address isunique(except for the broadcast address) which is the basis of the host computer and the inverterpoint to point communication.
Note: When the local address is set to 0, it is the broadcast address. It only can receive andexecute the broadcast command of the host computer, but not answering the host computer.
F9.01
Communication baud rate Factory value 1
Setting range
0 4800tongxun
1 9600
2 19200
3 38400
The parameter is used to set the data transfer rate between the host computer and converter.Note: The baud rate of host computer and the inverter must be consistent, otherwise, the
communication can not be. The greater the baud rate, the faster the communication.
F9.02
Communication format Factory value 0
Setting range
0 No Parity Bit 1+8+1 for RTU
1 Parity Check 1+8+1+1 for RTU
2 Odd Parity Check 1+8+1+1 for RTU
When elected with even parity or odd parity, each byte length for 11, including 1 start bit, 8data bits, 1 parity,1 stop bit.
When elected with no parity, each byte length for 11, including 1 start bit, 8 data bits, 2 stopbit. The data format of host computer and the inverter must be in the same format, otherwise, thecommunication can not be.
DR300User'smanual
119
F9.03
Master-slave machine communication mode Factory value 0
Setting range0 This is the slave machine
1 This is the master machine
F9.04
Host machine to send data Factory value 0
Setting range0 Output frequency
1 Input frequency
F9.05
Slave receiver address(Host setting) Factory value 0
Setting range0 The main digital frequency
1 Auxiliary digital frequency
F9.06Slave receiver proportion(Slave setting) Factory value 100.00
Setting range 0.00~600.00
The inverter provides two communication ports, SCIA for operation panel interface, SCIBfor terminal A +, A-. General application, inverter are the master-slave mode (F9.03 = 0),accepting external command to respond.
Host mode: Taking the initiative to send out data is mainly used in multi-machinesynchronization condition. As a host, it usually set one of a group machines as the host, and thecurrent operating frequency command of the host is passed to the other machines. Afterreceiving from the host frequency commands, the slave machine stored them in functional codeposition of F0.12 specified.
F9.06 The frequency ratio of the slave machine(from the slave machine):The parameter is only effective to the slave machine, and it is used for setting the given
correction factor of receiving from host machine.Slave machine set = F9.06 × Host given.
F9.07Communications timeout Factory value 0.0s
Setting range 0.0~600.0
When this function code is set to 0.00 s, the communication timeout parameter is invalid.When this function code set to valid value, if a communication and the next communication
time interval exceeded the communications timeout, the system will report communicationfailure error (ERR13).Normally, it will be set to the invalid. If in the continuous communicationsystem, setting up this parameters can monitor the communication situation.
DR300 User's manual
120
F10 Group:Fault and Protection
F10.00
Switch fault detection dead-bandfrequency Factory value 5.00Hz
Setting range 0.00~60.00
F10.01
Switch fault detection dead time Factory value 5.00s
Setting range 0.00~600.00
Set any multi-function input Xn to 43, and if the switch quantity fault, any multi-functionoutput terminals Yn should be set to 7 fault inverter. When the output frequency has reached theswitch quantity test dead zone frequency and the running time has reached the the switchquantity fault detection dead zone, if Xn is effectively, then the output of Yn is effective. Asshown in the figure below.
f Hz t
t
t
F10.01
Xn=43
Yn=7
F10.00
Figure 6-13 Switch failure
DR300User'smanual
121
F10.02
Analog fault selection Factory value 4
Setting range
0 AI0(Keyboard potentionmeter)
1 AI1
2 AI2
3 PF(X7)
4 Output current
5 Input voltage
F10.03Analog fault detection time length Factory value 5.00s
Setting range 0.00~60.00
F10.04Analog fault detection level Factory value 200.00%
Setting range 0.00~300.00
F10.05Analog fault detection level
hysteresis ring Factory value 0.00
Setting range 0.00~300.00
When the selected analog fault source (F10.02) is more than the set value of the analog faultdetection level (F10.04), and maintain a certain period of time (F10.03), the output of theinverter’s fault terminal (Yn is set of 7) will be effective. As shown in the figure below.
Output current
F10.04
F10.03 F10.03
Analog faultDetection signal
Effective
t
t
Figure 6-14 Analog fault
DR300 User's manual
122
F10.06Overvoltage stall protection point Factory value 130.00%
Setting range 100.00~150.00
F10.07Overvoltage stall gain Factory value 1.00%
Setting range 0.00~100.00
Overvoltage stall protection point:Choose the voltage protection point with overvoltagestall function. If exceed the value, the inverter started the voltage stall protection function.
Overvoltage stall gain:Adjust the inverter to inhibit the over-voltage stall.The higher thevalue, the stronger ability to suppress over voltage. For small inertial load, this value should besmall, otherwise it will cause the system dynamic response slowly. For large inertial load, thisvalue should be large, otherwise inhibitory effects may appear over-voltage fault. Applications ofthe gain value less than 10 is designed for the very small inertial load and in the case of notsetting the repressed system function, it will occasionally apply on the situation of over-voltage.
F10.08
The overcurrent stall protectionpoint Factory value 150.00%
Setting range 100.00~200.00
F10.09
The overcurrent stall gain Factory value 1.00%
Setting range 0.00~100.00
Overcurrent stall: When the output current of inverter reaches the overcurrent stallprotection current, if the inverter is in accelerated operation, stop accelerated. If it is in theconstant speed operation, reduce the output frequency. And if it is in the deceleration, slow downthe rate of decline until the current is less than the current stall protection current, and then therunning frequency can return to normal. As shown in the figure 6-18 .
The overcurrent stall protection point: Protection point choose the function of theovercurrent stall. After exceeding the value of this parameter the inverter started to operate thefunction of the over-current stall protection. The value is relative to the percentage of motorrated current.
The overcurrent stall gain: It is used to adjust the inverter to inhibit the loss rate. The greaterof this parameter value, the stronger is the inhibition of the flow capacity. In internal very smalloccasion, it is suggested that the over-current inhibition gain should be set less than 20.
DR300User'smanual
123
Output current
Over-current stallProtect the current point
t
Output frequency Hz
Setting frequency
acceleration process
Constant speed the process of
Deceleration process t
Figure 6-15 The overcurrent stall protection schematic diagram
F10.10
Instantaneous stop non-stopfunction Factory value 0
Setting range0 Ban
1 Allow
F10.11
The decline rate of the instantaneousstop non-stop frequency Factory value 10.00Hz/s
Setting range 0.00Hz/s~maximum frenquency/s
If the function of the instant stop non-stop is permitted and the bus voltage is lower than thenon-stop action judgment voltage, the inverter should reduce the running frequency accroding tothe decline rate of the instantaneous stop non-stop frequency (F10.11). Instantaneous stopnon-stop function is as shown: If the decline rate of instantaneous stop non-stop frequency is settoo small, and the load feedback energy is small, then it can not effectively compensate for thelow voltage. But if the parameter is too large and the load feedback energy is large, then it willcause the over-voltage protection. So please adjust the parameters properly according to the loadinertia and weight situation.
DR300 User's manual
124
V
Busvoltage
Givenfrequency Hz
Settingfrequency
t
Accelerationtime
F10.11
tFigure 6-16 Instantaneous stop non-stop run schematic
F10.12Dead zone compensation gain Factory value 0.00%
Setting range 0.00~100.00
Dead zone compensation parameters: Set the parameters can improve the output waveform.
F10.13Brake duty Factory value 80.00%
Setting range 5.00~100.00
F10.14Number of automatic fault reset Factory value
0
Setting range 0~3
When the inverter choose the automatic fault reset, it is used to set the number of theautomatic fault reset. If it exceeds this values, then will lead to the fault protection.
F10.15Time interval of automatic fault
reset Factory value 0.50s
Setting range 0.01~30.00
This is the waiting time of the inverter from fault alarm to automatic fault reset.
F10.16
The shortest addition andsubtraction time Factory value 0.05s
Setting range 0.05~30.00
This is the shortest time that inverter needs to speed up.
DR300User'smanual
125
F10.17
Fault properties and shielding 1 Factory value 0000
Setting range
bits Overcurrent protection
Ten Overvoltage protection
One hundred Undervoltage protection
One thousand Overload protection
0 Fault is not shielded, stop whenfault.
1 Fault is not shielded, alarm but stop.
2 Fault is shielded, do not alarm orstop.
F10.18
Fault properties and shielding 2 Factory value 0000
Setting range
bits Overheat protection
Ten Input phase loss protection
One hundred Output phase loss protection
One thousand Communication failure
0 Fault is not shielded, stop whenfault.
1 Fault is not shielded, alarm but stop.
2 Fault is shielded, do not alarm orstop.
F10.19
Fault properties and shielding 3 Factory value 0000
Setting range
Bits Memory failure
Ten Switch failure
One hundred Analog fault
One thousand Retention
0 Fault is not shielded, stop whenfault.
1 Fault is not shielded, alarm but stop.
2 Fault is shielded, do not alarm orstop.
When a fault occurs, the inverter decide whether to stop and alarm according to its number
DR300 User's manual
126
that the failure produce. For an example, the first group, for 0102, indicates that if it isover-current, the fault is not shielded, then stop. If it is over-voltage, the fault is not shielded,alarm but stop. If it is undervoltage, the fault is not shielded to stop. And if it is overload, thefault is shielded and neither alarm or shutdown with the inverter running on. The two groupsbehind are the same with the former one.
Note: If you need to change the factory settings, please contact the product distributors ormanufacturers.F11 group:Accessibility
F11.00
The jog priority running Factory value 0
Setting range0 Jog is not a priority
1 Jog is a priority
Inverter jog preferred.0:Jog is not a priority :Running are not allowed in the jog.1:Jog is a priority :Running are allowed in the jog.
F11.01Jumpinging frequency of 1 lower limit Factory
value0.00Hz
Setting range 0.00~600.00
F11.02Jumping frequency of 1 upper limit Factory
value0.00Hz
Setting range 0.00~600.00
F11.03Jumping frequency of 2 lower limit Factory
value0.00Hz
Setting range 0.00~600.00
F11.04Jumping frequency of 2 upper limit Factory
value0.00Hz
Setting range 0.00~600.00
F11.05Jumping frequency of 3 lower limit Factory
value0.00Hz
Setting range 0.00~600.00
F11.06Jumping frequency of 3 upper limit Factory
value0.00Hz
Setting range 0.00~600.00
When the setting frequency in the jumping frequency range ,the actual operation frequencywill be running away from the setting frequency closer to the jumping frequency boundary. Bysetting the jumping frequency, it make the inverter avoid the load of the mechanical resonancepoints .This inverter can be set to three jumping frequency points .If the three jumping frequencyare set to 0.00,the function does not work as shown in figure 6-17:
DR300User'smanual
127
After adjustment of the set
Frequency setting signal
Jump frequency rangeJump frequency range
Jump frequency rangeJump frequency range
Jumpfrequency 3
Jump frequency rangeJump frequency range
Jumpfrequency 2
Jumpfrequency 1
Figure 6-17 Jumping frequency sketch map
F11.07Reversible dead-time Factory value 0.00s
Setting range 0.00~600.00
When the inverter transit from forward to reverse or from reverse to forward, the transitiontime is in the output zero frequency .Dead time is shown in figure 6-18:
Forward
ReverseDead time
Time t
HzOutputfrequency
Figure 6-18 Reversible dead-time diagram
F11.08Run-time password Factory value 0
Setting range 0~65535
F11.09Set the running time Factory value 2400H
Setting range 0~60000
DR300 User's manual
128
F11.10Running time of the machine Factory value XXXX
Setting range 0~65535
The inverter stops output when the running time of the machine reaches the set runtime .
F11.11
Lower frequency control Factory value 0
Setting range0 Run at the lower limit frequency
1 Lower frequency of operation timeto reach 0 speed run
F11.12
Lower limit of the frequency ofrunning time Factory value 0.01s
Setting range 0.01~600.00
Select the operating status of the inverter when the set frequency is lower than the lowlimitation frequency.
In order to avoid the motor in the long-term low-speed run, you can use this function toselect stop the motor.
F11.13Output frequency range frequency
range Factory value 2.50Hz
Setting range 0.00~50.00
When the inverter output frequency reaches the setting frequency value, this function canadjust the detection amplitude.As shown below:
setting frequency
Frequency reach to thedetection signal
ON ON
Detectingamplitude
Time t
Time t
HzOutputfrequency
Figure 6-19 Frequency reaches the detection amplitude schematic
DR300User'smanual
129
F11.14AI sampling digital dead zone Factory value 4
Setting range 0~256
Prevent disruption of the AD sample value, setting the greater the smaller the interference,but the dead zone is sampling .
F11.15
Analog ADT1 selection Factory value 1
Setting range
0 AI0(keyboard potentiometer)
1 AI1
2 AI2
F11.16Analog ADT1 percentage Factory value 20.00%
Setting range 0.00~100.00
F11.17Analog ADT1 hysteresis Factory value 5.00%
Setting range 0.00~100.00
Set the analog ADT can indicate the alarm monitoring and other operations on the size ofthe current analog inputs analog.
Analog ADT1 selection :
F11.15 Analog ADT1 selection :ADT analog input terminal selection.F11.16 Analog ADT1 percentage :ADT of analog input levels .Select and change the ADT
of the analog input levels’ size .Percentage of the analog input terminal of the input signal.
F11.17Analog ADT1 hysteresis:The analog ADT1 input level lag select .Hysteresis is defined assingle-phase down, so the actual action point ADT1 is analog ADT1 (F11.16) value minus thevalue of the analog ADT1 hysteresis (F11.17). Such as:When F11.15=2 、F11.16=25.00、F11.17=5.00,the analog ADT1 is effective when the analog input terminal AI2 input voltagesignal to 2V (10V × 25%-10V x 5% = 2V) , then by the relay output terminals or multi-functionoutput terminal output indicator or alarm signal.
F11.18Speed tracking the rise time Factory value 1.00s
Setting range 0.00~10.00
The smaller the rising time, the faster the tracking speed, on the contrary, the slower.
F11.19Speed tracking current limit value Factory value 100.00%
Setting range 0.00~100.00
The limit value of the speed tracking current .
DR300 User's manual
130
F11.20Speed tracking time interval Factory value 0.50s
Setting range 0.00~10.00
Speed tracking time interval is what the time needs to wait for the speed tracking.
F11.21Count the corresponding pulse Factory value 1
Setting range 0~65000
Count the corresponding pulse is countting one number needed the number of pulses.
F11.22Count setting value Factory value 1000
setting range 0~65000
Counter's setting value.
F11.23Count the current value Factory value XXXX
setting range 0~65000
The current count value of the counter.When current value reaches the setting value, theoutput terminal’s (function is set to 16) output is effective.
DR300User'smanual
131
F12 Group:Quick menu list
F12.00Quick menu to display the number of Factory value 15
Setting range 0~31
F12.01Quick Menu1 Factory value 0x0003
Setting range 0x0000~0x039F
F12.02Quick Menu2 Factory value 0x0004
Setting range 0x0000~0x039F
F12.03Quick Menu3 Factory value 0x0005
Setting range 0x0000~0x039F
F12.04Quick Menu4 Factory value 0x0006
Setting range 0x0000~0x039F
F12.05Quick Menu5 Factory value 0x0007
Setting range 0x0000~0x039F
F12.06Quick Menu6 Factory value 0x0008
Setting range 0x0000~0x039F
F12.07Quick Menu7 Factory value 0x0009
Setting range 0x0000~0x039F
F12.08Quick Menu8 Factory value 0x000A
Setting range 0x0000~0x039F
F12.09Quick Menu9 Factory value 0x000B
Setting range 0x0000~0x039F
F12.10Quick Menu10 Factory value 0x000C
Setting range 0x0000~0x039F
F12.11Quick Menu11 Factory value 0x000D
Setting range 0x0000~0x039F
F12.12Quick Menu12 Factory value 0x000E
Setting range 0x0000~0x039F
F12.13Quick Menu13 Factory value 0x0010
Setting range 0x0000~0x039F
DR300 User's manual
132
F12.14Quick Menu14 Factory value 0x0011
Setting range 0x0000~0x039F
F12.15Quick Menu15 Factory value 0x0016
Setting range 0x0000~0x039F
F12.16Quick Menu16 Factory value 0x0018
Setting range 0x0000~0x039F
F12.17Quick Menu17 Factory value 0x001A
Setting range 0x0000~0x039F
F12.18Quick Menu18 Factory value 0x001B
Setting range 0x0000~0x039F
F12.19Quick Menu19 Factory value 0x001C
Setting range 0x0000~0x039F
F12.20Quick Menu20 Factory value 0x0021
Setting range 0x0000~0x039F
F12.21Quick Menu21 Factory value 0x0022
Setting range 0x0000~0x039F
F12.22Quick Menu22 Factory value 0x0023
Setting range 0x0000~0x039F
F12.23Quick Menu23 Factory value 0x0024
Setting range 0x0000~0x039F
F12.24Quick Menu24 Factory value 0x0025
Setting range 0x0000~0x039F
F12.25Quick Menu25 Factory value 0x0026
Setting range 0x0000~0x039F
F12.26Quick Menu26 Factory value 0x002F
Setting range 0x0000~0x039F
F12.27Quick Menu27 Factory value 0x0030
Setting range 0x0000~0x039F
F12.28Quick Menu28 Factory value 0x0031
Setting range 0x0000~0x039F
F12.29Quick Menu29 Factory value 0x0032
Setting range 0x0000~0x039F
DR300User'smanual
133
F12.30Quick Menu30 Factory value 0x0033
Setting range 0x0000~0x039F
F12.31Quick Menu31 Factory value 0x0038
Setting range 0x0000~0x039F
The operator panel only display user-defined fast parameters; use the basic functions of theinverter, set the menu mode.
F13 Group:Analog enhancements
F13.00
Analog offsetselection Factory value 0000
Setting range
Bits : AI0 Offsetselection0:Two bias1 : Four-point biasCurve A2 : Four-point biasCurve B
One hundred : AI2Offset selection0:Two bias1:Four-point bias CurveA2:Four-point bias CurveB
Ten : AI1 Offsetselection0:Two bias1 : Four-point biasCurve A2 : Four-point biasCurve B
One thousand : AI3Offset selection0:Four-point bias CurveA1:Four-point bias CurveB
In some special circumstances, according to actual needs, arbitrarily set an analog signal fora given bias curve. Voltage, bias current selection
Bits:AI0Voltage source biasing options: F13.00 bit=0/1/2:Corresponding to the input andoutput offset0/1/2;
Ten:AI1Voltage source biasing options: F13.00 ten=0/1/2:Corresponding to the input andoutput offset 0/1/2;
One hundred:AI2Voltage source biasing options: F13.00 hundred=0/1/2:Corresponding tothe input and output offset0/1/2;
One thousand:AI3Voltage source biasing options: F13.00 thousand=0/1:Corresponding tothe input and output offset0/1.
DR300 User's manual
134
F13.01Output offsetAY0 Factory value 0.00%
Setting range 0.00~100.00
F13.02Output offsetAY1 Factory value 25.00%
Setting range 0.00~100.00
F13.03Output offsetAY2 Factory value 75.00%
Setting range 0.00~100.00
F13.04Output offsetAY3 Factory value 100.00%
Setting range 0.00~100.00100.00=FMAX
F13.05Input biasAX0 Factory value 0.00%
Setting range 0.00~Input biasAX1
F13.06Input biasAX1 Factory value 25.00%
Setting range Input biasAX0~Input biasAX2
F13.07Input biasAX2 Factory value 75.00%
Setting range Input biasAX1~Input biasAX3
F13.08Input biasAX3 Factory value 100.00%
Setting range Input biasAX2~100.00
F13.09Output offsetBY0 Factory value 0.00%
Setting range 0.00~100.00
F13.10Output offsetBY1 Factory value 25.00%
Setting range 0.00~100.00
F13.10Output offsetBY1 Factory value 25.00%
Setting range 0.00~100.00
F13.11Output offsetBY2 Factory value 75.00%
Setting range 0.00~100.00
F13.12Output offsetBY3 Factory value 100.00%
Setting range 0.00~100.00100.00=FMAX
F13.13Input biasBX0 Factory value 0.00%
Setting range 0.00~Input biasBX1
F13.14Input biasBX1 Factory value 25.00%
Setting range Input biasBX0~Input biasBX2
DR300User'smanual
135
F13.15Input biasBX2 Factory value 75.00%
Setting range Input biasBX1~Input biasBX3
F13.16Input biasBX3 Factory value 100.00%
Setting range Input biasBX2~100.00
F13.01、F13.02、F13.03、F13.04 define four points of the output offset frequency in any biascurve within the range of 0.0% to 100.0%, continuous seting;
F13.04、F13.05、F13.06、F13.07 define four points anology output in any bias curve withinthe range of 0.0% to 100.0%, continuous seting;
0≤F13.04≤F13.05≤F13.06≤F13.07≤100.0%.Example 1: Code parameter settings as shown in Table 8-1:
Table 8-1
Function code Settings Function code Settings
F13.01 0.00% F13.05 0.00%
F13.02 30.00% F13.06 25.00%
F13.03 65.00% F13.07 75.00%
F13.04 100.00% F13.08 100.00%
Analog input AI0/AI1 (0 ~ 10V) or AI2/AI3 (0 to 20mA) input and output bias as shown inFigure 6-18 (a) below;
Analog input AI0/AI1 (2 to 10V) or AI2/AI3 (4 ~ 20mA), the input and output bias as shownin Figure 6-18 (b) below.
Example 2: the code parameter settings as shown in Table 8-2:Table 8-2
Function code Settings Function code Settings
F13.09 100.00% F13.13 0.00%
F13.10 70.00% F13.14 40.00%
F13.11 40.00% F13.15 75.00%
F13.12 0.00% F13.16 100.00%
Analog input for AI0/AI1 (0 ~ 10V) or AI2/AI3 (0 ~ 20mA), the input and output bias as shown inFigure 6-18 (c);
Analog input AI0/AI1 (2 to 10V) or AI2/AI3 (4 ~ 20mA), the input and output bias as shown inFigure 6-18 (d);
DR300 User's manual
136
Setting frequency Hz
F13.04 100%
FMAX
F13.03 65%
F13.02 30%
F13.01 0.00%
0.00%F13.05
25%F13.06
75%F13.07
100%F13.08
Analog Given2.5V 7.5V 10V
F13.04 100%
FMAX
F13.03 65%
F13.02 30%
F13.01 0.00% 0.00%
F13.05 25% F13.06
75%F13.07
100% F13.08
2V 4V 8V 10V
Setting frequency Hz
(a) (b)
F13.09 100%
F13.10 70%
F13.11 40%
F13.120.00%
0.00%F13.13
40%F13.14
75%F13.15
100%F13.16
4V 7.5V 10V
FMAX
Setting frequency Hz
F13.09 100%
FMAX
F13.10 70%
F13.11 40%
F13.120.00% 0.00%
F13.13 40%F13.14
75%F13.15
100% F13.16
5.2V 8V 10V2V
Setting frequency Hz
(c) (d)
Figure 6-20 Input and output bias
ER Group:Fault HistoryFunction code Function code name Factory value
ER00 The latest fault XXXX
ER.01 Failure when the outputfrequency
XXXX
ER.02 Output current when the faultXXXX
ER.03 Bus voltage failure XXXX
ER.04 Working time of failure XXXX
ER.05 Fault input terminal XXXX
ER.06 Fault input terminal XXXX
ER.07 Failure output terminal XXXX
DR300User'smanual
137
ER.01 Failure frequency ,display the last fault frequency.ER.02 Failure current,display the last fault current.ER.03 Bus voltage failure ,display the last fault bus voltage.ER.04 Failure time,display the working time of the last failure.ER.05 ER.06 Fault input terminal,display the last fault input terminals.ER.07 Fault output terminal display the last fault output terminal.
Function code Name Factory value
ER.08 The previous single fault XXXX
ER.09 Failure when the outputfrequency
XXXX
ER.10 Output current when thefault
XXXX
ER.11 Bus voltage failure XXXX
ER.12 Working time of failure XXXX
ER.13 Fault input terminal XXXX
ER.14 Fault input terminal XXXX
ER.15 Failure output terminal XXXX
ER.16 The first two failures
XXXX
ER.17 Failure when the outputfrequency
XXXX
ER.18 Output current when thefault
XXXX
ER.19 Bus voltage failure XXXX
Function code Name Factory value
ER.20 Working time of failure XXXX
ER.21 Fault input terminal XXXX
ER.22 Fault input terminal XXXX
ER.23 Failure output terminal XXXX
ER.24 The maximum bus voltage XXXX
ER.24 show the maximum bus voltage.
DR300 User's manual
138
H0 Group:Monitoring parametersFunction code Name Display range
H0.00 Speed referenceinputTorque reference input
Frequency: 0.00~600.00Hz/Torque input:H0.01
H0.02Output frequency 0.00~600.00 Hz
H0.03
H0.04Speed / line speed 0~180000Switch to / m per
minuteH0.05
H0.06 Unit value of output current 0.00~100.00%
H0.07 The actual value of the outputcurrent 0.0~3000.0 A
H0.08 Output voltage per unit value 0.00~100.00%
H0.09 The actual value of the outputvoltage 0.0~660.0 V
H0.10 DC bus voltage 0~1200 V
H0.11 Overload count 0.00~100.00%
H0.12 Output power 0.0~3000.0 kW
H0.13 PID settings 0~60000
H0.14 PID Feedback 0~60000
H0.15 PIDOutput -100.0~100.0%
H0.16 Input terminal status1 X4 X3 X2 X10 0 0 0
H0.17 Input terminal status2 * X7 X6 X50 0 0 0
H0.18 Output terminal status * R1 Y2 Y10 0 0 0
H0.19 AI0Enter a percentage 0.00~100.00%
H0.20 AI1Enter a percentage 0.00~100.00%
H0.21 AI2Enter a percentage 0.00~100.00%
H0.22 PF(X7)Enter a percentage 0.00~100.00%
H0.23 AO1 Output percentage 0.00~100.00%
H0.24 AO2 Output percentage 0.00~100.00%
H0.25 DO Output percentage 0.00~100.00%
DR300User'smanual
139
The user can query the function code of the H0 group to understand the operatingparameters when the inverter running. All monitor code are read-only and can not be modified.the default display monitor code are deceided by the function code F4.18 ~ F4.22.
Chapter 7 EMC (Electromagnetic Compatibility)
7.1 Definition
Electromagnetic compatibility is the ability of the electric equipment to run in theelectromagnetic interference environment and implement its function stably withoutinterferences on the electromagnetic environment.
7.2 EMC Standard Description
In accordance with the requirements of the national standard GB/T12668.3, the inverter needsto comply with electromagnetic interference and anti-electromagnetic interference requirements.
The products of our company use the latest international standard-IEC/EN61800-3:2004(Adjustable speed electrical power drive systems part 3:EMC requirements and specific testmethods), which is equivalent to the national standard GB/T12668.3.
IEC/EN61800-3 assesses the inverter in terms of electromagnetic interference and antielectronic interference. Electromagnetic interference mainly tests the radiationinterference,conduction interference and harmonics interference on the inverter (required for theinverter for civil use)Anti-electromagnetic interference mainly tests the conduction interferencerejection,radiation interference rejection, surge interference rejection, fast and mutable pulsegroup interference rejection, ESD interference rejection and power low frequency endinterference rejection (specific test items including: 1.Interference rejection tests of input voltagesag,interrupt and change; 2.Phase conversion interference rejection test; 3.Harmonic inputinterference rejection test; 4. Input frequency change test; 5. Input voltage unbalance test; 6.inputvoltage fluctuation test).
The tests shall be conducted strictly in accordance with the above requirements ofIEC/EN61800-3, and the products of our company are installed and used according to Section7.3and have good electromagnetic compatibility in general industry environment.
DR300 User's manual
140
7.3 EMC Guide
7.3.1 Harmonic Effect
Higher harmonics of power supply may damage the inverter. Thus, at some places wheremains quality is rather poor, it is recommended to install AC input reactor.
7.3.2 Electromagnetic Interference and Installation PrecautionsThere are two kinds of electromagnetic interferences, one is interference of electromagnetic
noise in the surrounding environment on the inverter, and the other is interference of inverter onthe surrounding equipment.Installation precautions:
A、The earth wires of the Inverter and other electric products shall be well grounded;B、 The power input and output power cables of the inverter and weak current signal
cables(e.g. control line) shall not be arranged in parallel and vertical arrangement is preferable.C、It is recommended that the output power cables of the inverter employ shield cables orsteel pipe shielded cables and that the shielding layer be earthed reliably. The lead cables of
the equipment suffering interferences are recommended to employ twisted-pair shieldedcontrol cables, and the shielding layer shall be earthed reliably.D、 When the length of motor cable is longer than 100 meters, it needs to install output
filter or reactor.7.3.3Handling method for the interferences of the surrounding equipment on the
inverter:The electromagnetic interference on the inverter is generated because plenty of
relays,contactors and electromagnetic brakes are installed near the inverter. When the inverterhas error action due to the interferences, the following measures can be taken:
Install surge suppressor on the devices generating interference;B、 Install filter at the input end of the inverter. Refer to Section 7.3.6 for the specific
operations.C、 The lead cables of the control signal cable of the inverter and the detection line employ
shielded cable and the shielding layer shall be earthed reliably.7.3.4 Handling method for the interferences of inverter on the surrounding
equipment:These interferences include two types: one is radiation interference of the inverter, and the
other is conduction interference of the inverter. These two types of interferences cause thesurrounding electric equipment to suffer electromagnetic or electrostatic induction. Thesurrounding equipment hereby produces error action. For different interferences, it can be
handled by referring to the following methods:A、For the measuring meters, receivers and sensors, their signals are generally weak. If they
are placed nearby the inverter or together with the inverter in the same control cabinet, they areeasy to suffer interference and thus generate error actions. It is recommended to handle with thefollowing methods: Put in places far away from the interference source; do not arrange the signalcables with the power cables in parallel and never bind them together; both the signal cables andpower cables employ shielded cables and are well earthed; install ferrite magnetic ring (withsuppressing frequency of 30 to 1,000MHz) at the output side of the inverter and wind it 2 to 3cycles; install EMC output filter in more severe conditions.
B、 When the equipment suffering interferences and the inverter use the same power supply,
DR300User'smanual
141
it may cause conduction interference. If the above methods cannot remove the interference, itshall install EMC filter between the inverter and the power supply (refer to Section 7.3.6 for theprototyping operation);
C 、 The surrounding equipment is separately earthed, which can avoid the interferencecaused by the leakage current of the inverter’s earth wire when common earth mode is adopted.
7.3.5 Leakage current and handlingThere are two forms of leakage current when using the inverter. One is leakage current to
the earth, and the other is leakage current between the cables.A、Factors influencing the leakage current to the earth and the solutions:There are distributed capacitance between the lead cables and the earth. The larger the
distributed capacitance is, the larger the leakage current will be. The distributed capacitance canbe reduced by effectively reducing the distance between the inverter and the motor. The higherthe carrier frequency is, the larger the leakage current will be. The leakage current can bereduced by reducing the carrier frequency. However, reducing the carrier frequency may result inaddition of motor noise. Note that additional installation of reactor is also an effective method toremove the leakage current.The leakage current may increase following the addition of circuitcurrent. Therefore, when the motor power is high, the corresponding leakage current will be hightoo.
B、Factors of producing leakage current between the cables and solutions:There is distributed capacitance between the output cables of the inverter. If the current
passing the lines has higher harmonic, it may cause resonance and thus result in leakage current.If thermal relay is used, it may generate error action. The solution is to reduce the carrierfrequency or install output reactor. It is recommended that thermal relay not be installed beforethe motor when using the inverter, and that electronic over current protection function of theinverter be used instead.
7.3.6 Precautions for Installing EMC input filter at the input end of power supplyA、When installing EMC input filter at the input end of power supply,we recommend use
the EMC filter which was produced by shanghai yingfeng.B、When using the inverter, please follow its rated values strictly. Since the filter belongs to
classification I electric appliances, the metal enclosure of the filter shall be well fixed with themetal ground of the installing cabinet. Otherwise there may be danger of electric shock and theEMC effect may be greatly affected.
C、Through the EMC test, that the filter ground must be connected with the PE end of theinverter at the same public earth. Otherwise the EMC effect may be greatly affected.
D、The filter shall be installed at a place close to the input end of the power supply as muchas possible.
DR300 User's manual
142
Chapter 8 Fault Diagnosis and Solution8.1 Fault Alarm and Countermeasures
There are several warnings and protection features in the DR300 series inverter, Once thefault occurs, Protection is activated,then the inverter stopped, The fault relay in the inverter willbe action, The fault code will be displayed on the inverter display panel.Before seeking for theservice,the users can self-examination according to this section, to analysis the fault reason,andlook for the solution. If the reasons is described as in the dotted frame,please contack our agentor directly contact our company.
ERR01
Seek for technicalsupport
If it works normallyafter replacing themain control board
Inverter Unit Protection
If it works normally afterreplacing the drive board
Check if the inverter outputloop is short circuited
The main controlboard is faulty
If it works normally afterreplacing the inverter module
yPerform troubleshooting
If the cable connectingthe motor with theinverter is too long
n
Install a reactor or output filter
If the module is over heat
Check if the air duct is blocked andif the fan is in nomal status,andresolve the existing problems
Check if the cableconnections inside the
inverter are loosen
Insert all the connectingcables properly
The drive board is faulty
The inveter module is damaged
n
n
n
y
y
y
y
y
y
Figure 8-1 The inverter Unit Protection
DR300User'smanual
143
Check the inverteroutput circuit is groundedor shorted
ERR02
Acceleration time istoo short
Manually increasetorque or V / F curveis appropriate
Voltage on the lowside
Whether to start arotating motor
Whether to accelerate theprocess of sudden load
Drive selection istoo small
Remove peripheralfault
Increase theacceleration time
Adjust manuallyincrease the torqueor V / F curve
Voltage to the normalrange
Select the tracking speedand then start or stop themotor and then start
Cancel sudden load
yes
no
yes
yes
yes
no
no
yes
no
no
no
yes
Motor parameteridentification
Motor parameteridentification
no
V/Fmode
Figure 8-2 Acceleration overcurrent
Check the inverteroutput circuit for shortsor leakage current
ERR03
Run if there are suddenload
Inverter load can bereduced
Drive model istoo small
Cancel sudden loady
can
Constantspeed overcurrent
n
n
can not
yPeripheral failure wereexcluded. If the line is toolong, plus the output chokes
Reduce the load
Motor parameteridentification
Motor parameteridentification
n
y
Figure 8-3 Constant speed over current
DR300 User's manual
144
Check the inverteroutput circuit is groundedor shorted
Remove peripheral fault
ERR04
Deceleration time istoo short
Voltage on the lowside
Whether equippedwith a braking unitand braking resistor
Whether in the process ofdeceleration, sudden load
For technicalsupport
Increase thedeceleration time
Voltage to the normal range
Cancel sudden load
y
y
n
y
Decelerationcurrent
n
n
n
y
n
y
The installation of thebrake unit and resistor
Motor parameteridentification
Motor parameteridentification
n
V/F mode
Figure 8-4 Deceleration current
Speed up the processif there are externaldrag motor running
ERR05
The input voltage isnot too high
Acceleration time istoo short
Voltage to the normal range
y
y
Acceleratedover-voltage
n
n
y
Whether equippedwith a braking unitand braking resistor
For technicalsupport
The installation of thebrake unit and resistor
n
n
Cancel power or installationof the braking resistor
Increase the acceleration time
Figure 8-5 Acceleration over-voltage
DR300User'smanual
145
External drag motorrunning in the running
ERR06
The input voltage isnot too high Voltage to the normal range
Cancel the power orthe installation of thebraking resistor
y
Constantspeedover-voltage
n
y
For technicalsupport
n
Figure 8-6 Constant speed over-voltage
Slow down theprocess of externaldrag motor running
ERR07
The input voltage isnot too high
Deceleration time istoo short
Voltage to the normal range
Cancel the power or theinstallation of the brakingresistor
Increase the deceleration timeor install the brake resistor
y
y
Decelerationvoltage
n
n
y
Whether equippedwith a braking resistor
For technicalsupport
n
Be fitted with braking resistorn
Figure 8-7 Deceleration voltage
DR300 User's manual
146
Reset the fault
ERR08
Measure the DC busvoltage is normal
Check the driveboard is normal
Check the bridge rectifier andbuffering resistor is normal
Adjust the voltage to thenormal range
n
n
n
y
n
n
y
y
Replace the driver board
Detection of inverter inputvoltage in the specificationsvalue
The existence of theinstantaneous power failure
Check the main controlboard is normal
nReplace the control panel
Replace the damaged bridgerectifier or buffer resistance
n
y
Figure 8-8 Undervoltage fault
Load whether or theoccurrence of motor stall
ERR09
The motor protectionparameter settings areappropriate
This parameter is set correctly
Reduce the load and checkthe motor and mechanical
y
Motoroverload
y
n
Small transformermodels
n
ERR10
Inverteroverload
Figure 8-9 Overload fault
DR300User'smanual
147
ERR10
For technicalsupport
Module thermistor isdamaged
Lower ambient temperature
Moduleoverheating
n
y
Inverter module fordamage
n
Replace the inverter module
Ambient temperatureis too high
Duct is blocked
n
Fan is not damaged
n
Clean up the air ducty
Replace the fany
Replace the thermistory
y
Figure 8-10 Overheating fault
ERR11
For technicalsupport
Check the driveboard is normal
Input side ofthe phase
y
Check mine boardis normal
yReplacement of lightningprotection board
n
Check three-phase inputpower supply is normal
Replace the driver board
Check main controlboard is normal
y
Replace the control boardn
Check and the exclusionof peripheral lines, enterthe inverter three-phasepower normally
Figure 8-11 Input phase
DR300 User's manual
148
Inspection is not chargedto run three-phase inverteroutput is balanced
ERR12
For technicalsupport
Check the drive boardis normal
Remove peripheral fault
Check the motorthree-phase winding isnormal and troubleshooting
y
n
Output sideof the phase
y
n
n
Check if the moduleis normal
y
Replace the module
Check the inverter to themotor is normal lead
y
Replace the driver board
Figure 8-12 Output side of the phase
ERR13
Host computerat work
Deceleration time istoo short
Check the hostcomputer wiring
Cancel the power or theinstallation of the brakingresistor
Increase the deceleration timeor install the brake resistor
n
n
Communicationstimeout fault
y
y
n
Whether equipped witha braking resistor
For technicalsupport
y
Be fitted with braking resistor
The input voltage isnot too high
y
n
Figure 8-13 Communication failure
DR300User'smanual
149
ERR14
EEPROM readand write fault
Control board failurenAfter replacing the main
control board is normal
For technical support
Figure 8-14 Memory failure
ERR15
Motor tuningfailure
Parameter identificationprocess is whether thetime-out
y
Check the inverter to themotor leads
The motor parametersare set correctly
nThe motor parametersare set by the data onthe nameplate
y
Figure 8-15 Failure self-tuning
DR300 User's manual
150
8.2 Common faults and their treatment.
May encounter the following fault conditions in the process of the inverter, please refer tothe following method to a simple failure analysis:
No. Fault phenomenon Possible cause Solution
1 Power-on displayor garbled
1.Inverter input poweranomalies.2.Driver board and controlpanel to connect the 8-pin and40-core cable connection isbad.3.Inverter internal devicedamage
1.Check the inputpower.2.Re-plug the 8-pinand 40-core cable.3.Seekingmanufacturers service
2
Power on theinverter displaynormal runningERR10 (moduleoverheating) andimmediately stop
The fan is damaged or stall Replace the fan
3 Frequently reportedERR10 failure
1.The carrier frequency settingis too high.2.Fan damage or ductblockage.3.Inverter internal damage tothe device (thermocouple orother)
1.Reduce the carrierfrequency.2.Replace the fan,clean the air duct.3.Seeking service
4The running of thedrive motor doesnot rotate.
1.Motor damage or stall.2.Parameter setting does not
1.Replace the motoror clear mechanicalfailure.2.Check and re-set
5 X-terminal failure.
1.Parameters are setincorrectly.2.Wiring error.3.Control board failure
1.Check and re-setthe relevantparameters2.Re-connect the PLCand 24V terminals3.Seeking service
6
The inverter isfrequently reportedovercurrent andovervoltage fault.
1.Motor parameter set doesnot.2.Acceleration anddeceleration timeinappropriate.3.Load fluctuations.
1.Re-set the F1 set ofparameters.2.Set the appropriateacceleration anddeceleration time.3.Seekingmanufacturersservice.
DR300User'smanual
151
Appendix I DR300 series inverter ModBuscommunication protocol
I.Scope of application:1. Applicable Series: DR300 series inverter.2. Applicable to network: Support for ModBus Protocol, RTU format, With the RS485 bus,
the "single-master multi-slave communication network.A typical RTU message frame format is as follows:
Start bit Deviceaddress
Functioncode Data CRC
checksum End of the bit
T1-T2-T3-T4 8Bit 8Bit n*8Bit 16Bit T1-T2-T3-T4
II. Physical interface:RS485 asynchronous half-duplex mode of communication.RS485 terminal to the default data format for: 1-8-N-1,Baud rate:9600bps.Data format1-8-N-1、1-8-O-1、1-8-E-1,Baud rate4800bps、9600bps、19200bps、38400bps
optional.
III. Protocol format:Command code 0x03: Read the code parameters or status word of inverter function Send a
message frame structure:Send the order Bytes sent For example
Address code 1 0x01
Function code 1 0x03
Register start address (H)2
0x00
Register start address (L) 0x0C
Register number (H)2
0x00
Register number (L) 0x01
CRC checksum (L)2
0x44
CRC checksum (H) 0x09
Receive information frame structure:In the order received Received byte For example
Address code 1 0x01Function code 1 0x03
Number of bytes read 1 0x02To read the content (H) 2*N 0x13
Read the content (L) 0x88CRC checksum (L) 2 0xB5CRC checksum (H) 0x12
DR300 User's manual
152
Command code 0x06: Write a single inverter function code or control parametersSend a message frame structure:
Send the order Bytes sent For exampleAddress code 1 0x01Function code 1 0x06
Register address (H) 2 0x30Register address (L) 0x00Register content (H) 2 0x00Register content (L) 0x01CRC checksum (L) 2 0x47CRC checksum (H) 0x0A
Receive information frame structure:Send the order Bytes sent For exampleAddress code 1 0x01Function code 1 0x06
Register address (H) 2 0x30Register address (L) 0x00Register content (H) 2 0x00Register content (L) 0x01CRC checksum (L) 2 0x 47CRC checksum (H) 0x0A
Command code 0x10:Rewrite the function code or control of the inverter parameters
Send a message frame structure:Send the order Bytes sent For exampleAddress code 1 0x01Function code 1 0x10
Register start address (H) 2 0x00Register start address (L) 0xE0
Register number (H) 2 0x00Register number (L) 0x02
Content the number of bytes 1 0x04Register content (H)
2*N
0x01Register content (L) 0xF4
… 0x030xE8
CRC checksum (L) 2 0xBDCRC checksum (H) 0x57
Receive information frame structure:In the order received Received byte For example
Address code 1 0x01Function code 1 0x10
Register start address (H) 2 0x00Register start address (L) 0xE0
Register number (H) 2 0x00Register number (L) 0x02CRC checksum (L) 2 0x40CRC checksum (H) 0x3E
DR300User'smanual
153
IV. Protocol format specifier
1:Address codeInverter address from the machine.Setting range is 1 to 247,0 is the broadcast address.
2. Function codeFunction code Function
03H Read the parameter unit or state unit
06H Write a inverter single parameter unit or control unitsingle parameter unit or control unit
10H Write inverter multiple parameters unit or control unit
3. The inverter registers address distribution
Address space Description
Parameter unit0x0000~0x039F Parameters of power-down does not save the address
Parameter unit0x1000~0x139F Parameter of power-down save address
Control unit0x3000~0x300D inverter control command unit
state unit0x3100~0x310D inverter state display unit
4. Communication checkThe use of RTU frame format, message includes an error detection domain based on CRC
method.CRC domain detects the content of the message. The CRC domain is two bytes,including16 bit binary value. It is calculated by the transmitting device and added to message.
The receiving device recalculates the CRC of receiving message, and compare to the CRCdomain’s received value, if two CRC values are not equal, the transmission is error.
CRC is the first deposited in 0xFFFF, and then invoke a process to deal with Continuous 8bytes of message and the current value of the register. Only in each character8Bit data availableto CRC, the start bit and stop bit and parity bits are invalid.
CRC production process, each of the 8characters are individually and the contents of aregister or different (XOR ), the results tend move to the lowest effective bit direction, thehighest effective bit is filled with 0. LSB was extracted from the testing, if LSB is 1, the separateregister is dissimilar with the value of the preset , if LSB is 0, not for. The entire process shouldbe repeated 8 times. After the last place (eighth ) is completed, the next separate8 bit byte isdifferent with register current value . The final value of the register is the CRC value, which isthe after executing all bytes of message
DR300 User's manual
154
CRC is added to the message, the low byte of the first to join, and then thehighbyte.,CRC simple function as follows :
unsigned int CrcValueCalc(const unsigned int *data, unsigned int length)
unsigned int crcValue = 0xffff;int i;
while (length--)
crcValue ^= *data++;for (i = 8 - 1; i >= 0; i--) if (crcValue & 0x0001)
crcValue = (crcValue >> 1) ^ 0xa001;else crcValue = crcValue >> 1;
return (crcValue);
5. Register unit detail (order to Description the address sequence from low to high).arameter unit
Universal machine address The power-down does notsave Power-down save
F0.00~FF.31(Basic parameters) 0x0000~0x01FF 0x1000~0x11FF
ER.00~ER.31(malfunctionparameters)
0x0200~0x021F 0x1200~0x121F
FP.00~FP.255(Plane parameters) 0x0260~0x037F 0x1280~0x135F
H0.00~H0.31(Monitoringparameters) 0x0380~0x039F NO power-down save
address
Inverter control unitRegisteraddress
Meaning Content Meaning
0x3000 Control command word 0x3007 AO1 Output percentage0x3001 Digital frequency is given 0x3008 AO2 Output percentage0x3002 Digital torque is given 0x3009 DO 比 Output percentage0x3003 The run command is given 0x300A ∧/∨digital adjustment lower0x3004 Acceleration time 0x300B ∧/∨digital adjustment higher0x3005 Deceleration time 0x300C nop0x3006 Virtual terminals 0x300D nop
Output terminal from LSB to MSB order: X1、X2、X3、X4、X5、X6、X7、Y1、Y2、R1
DR300User'smanual
155
Inverter control command words (0x3000) are defined as follows:
Bit Meaning Bit Meaning
00:Command effectively stop1:Operation command effective 6
0:Reset command is not available1:Reset command effective
1 0:Are turning direction1:Reverse direction 7 0:Parameters reset invalid
1:Parameters reset effective
2
0:The point start command is notavailable1:The point start commandeffectively
8 Nop
30:Since setting invalid1:Since setting effective 9 Nop
4 0:Free parking invalid1:Free parking effective A Nop
5 0:Emergency stop invalid1:Emergency stop effective B Nop
DR300 User's manual
156
Inverter state unit (0x3100) is defined as follows :
Bit Meaning Bit Meaning
00:Inverter stop1:Inverter running 6 Nop
10:Converter are turning
1:Inverter reversal7 Nop
20:The inverter point start1:Point start inverter 8 Nop
30:Inverter trouble-free1:Inverter is a failure 9 Nop
4 Nop A Nop
5 Nop B Nop
DR300User'smanual
157
Five.Commonly used address
Register name Mailing address
Reference input(Low) 0x0380
Reference input(High) 0x0381
Output prequency(Low) 0x0382
Output prequency(High) 0x0383
The auxiliary display(Low) 0x0384
The auxiliary display(High) 0x0385
Output current Componenf value 0x0386
Output current practical value 0x0387
Output voltage Componenf value 0x0388
Output voltage practical value 0x0389
DC bus voltage 0x038A
Overload count 0x038B
Output power 0x038C
PID set 0x038D
PID feedback 0x038E
PID output 0x038F
Input terminal state 1 0x0390
Input terminal state 2 0x0391
Output terminal state 0x0392
AI0 input percentage 0x0393
AI1 input percentage 0x0394
AI2 input percentage 0x0395
PF(X7)input percentage 0x0396
AO1 output percentage 0x0397
AO2 output percentage 0x0398
DO output percentage 0x0399
DR300 User's manual
158
Appendix II Keyboard installation dimension drawing
DR300User'smanual
159