TROUBLE SHOOTING•“EXIT” legend does not illuminate • Checkwiringconnections.

•Emergency circuit does not work • Batteriesareshippedunchargedanddisconnected.Connectpowerpackleadsandchargebeforetesting. • Makesurechargerboardisproperlyseated. • Checkwiringconnections.

TESTINGSignsshouldbetestedandmaintainedinaccordancewithNationalElectricalCodeandNFPA101LifeSafetyCoderequirements.Itisrecommendedthatemergencyexitsignsbetestedfor30secondsonceamonthandfor90minutesonceayear.

REPLACING A BATTERY PACKDe-energizetheACpowersupplytotheexitsign;removetheclearcover.Removethewhitetrimplateandtheexitsignface.Disconnectthe2-pinbatterypackconnectorfromthechargerboard.Removethebatterypackfromthecompartment.Installanewbatterypackwiththecorrectpartnumberintothecompartment,andpluginthe2-pinconnectortothechargerboard.Reinstalltheexitsignface,whitetrimplateandsecuretheclearcover.EnergizeACpowertotheexitsign.Allowthenewbatterypacktofullycharge,andpressthe“TEST”buttontoverifyoperation.

RECYCLING INFORMATION Allthermoplasticpartsarerecyclable.Allcartonscontainrecycledmaterials.Pleaserecycleresponsibly.

NOTICE:Emergency model exit signs contain rechargeable nickel-cadmium batteries which must be recycled or disposed of properly.

LN4X SeriesLED Exit Sign Listed For Damp And Wet LocationsAC Non-Emergency Models Are UL Type 4X Rated

Installation, Operation and Maintainance Instructions

Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.comCopyright©HubbellLighting,Inc.,AllRightsReserved•Specificationssubjecttochangewithoutnotice.•PrintedinU.S.A.

93029236A 6/10

IMPORTANT SAFEGUARDSWhenusingelectricalequipment,basicsafetyprecautionsshouldalwaysbefollowedincludingthefollowing.

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1.Donotletpowersupplycordstouchhotsurfaces. 2.Donotmountneargasorelectricheaters. 3.Equipmentshouldbemountedinlocationsandatheightswhereitwillnotreadilybesubjecttotampering byunauthorizedpersonnel. 4.Theuseofaccessoryequipmentnotauthorizedbythemanufacturermaycauseanunsafecondition. 5.Donotusethisequipmentforotherthanitsintendedpurpose. 6.Servicingofthisequipmentshouldbeperformedbyqualifiedservicepersonnel. 7.Testcycling:theLifeSafetyCode(NFPA101)requirestestingofemergencyexitsignsonceamonthfora minimumof30secondsandonceayearforaminimumof90minutes.

INSTALLER: •SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS

•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT

WARNING–ThisproductcontainschemicalsknowntotheStateofCaliforniatocausecancer,birthdefectsand/orotherreproductiveharm.Thoroughlywashhandsafterinstalling,handling,cleaning,orotherwisetouchingthisproduct.

93033371

OPERATION“ACON”LEDisiluminatedwhenACpowerispresent.NOTE:AllmodelsaresuppliedwithanACLockoutcircuit,whichpreventsthe“EXIT”legendfromilluminatingwhenthebatteryisconnectedandnoACpowerispresent.NOTE:AllmodelsaresuppliedwithaLowVoltageDisconnectcircuit,whichpreventsdamagetothebatteryfromdeepdischargeduringprolongedemergencyoperation.NOTE:Batteriesareoftenshippedinadischargedstate–thisisnormal.Thebatterywillrequirecharging.Allowseveralhoursofchargebeforetestingtheunit.

ModelsWithSPECTRON®Self-Testing/Self-DiagnosticCircuitryModelsequippedwiththeSpectronself-testing/self-diagnosticelectronicssystemprovide: ■VisualindicationofACpowerstatus ■Visualindicationofself-diagnostictestcycle —Visualindicationofanyunitmalfunctionsincluding— ■ Battery fault ■ Transfer fault ■ Charger fault ■ Emergency Lamp fault

Spectron equipped units also include:Brownout protection: unit will automatically transfer to emergency operation upon detection of low AC power (approximately 80% of nominal line).Time Delay Retransfer: upon return of normal AC power, unit will remain in the emergency mode for an additional 15 minutes to allow AC power to stabilize.LEDStatusIndicatorAbicolorLED(green/red)isprovidedonthecontrolpanelofallmodelsequippedwiththeSpectronoption.

RedStatusIndicatorCode Description

OneblinkON/pause Batterynotconnected

TwoblinksON/pause Batteryfault

ThreeblinksON/pause Chargerfault

FourblinksON/pause Transfercircuitfault

FiveblinksON/pause EmergencyLampfault

AutomaticTestsTheunitwillautomaticallyinitiateaself-test/self-diag-nosticcyclebasedonthefollowingtable:

TestingPeriod DurationofTest

Onceamonth 1minute

Onceevery6months Alternating:30minutesor60minutes

ManualTestsUsingtheunittestswitch,userscaninitiatedifferentdurationtestcyclesbasedonthefollowingtable:

InitiatingAction TestCycle

Presstestswitchonce 1minute

Presstestswitchtwice 90minutes

Pressingthetestswitchatanytimeafteratestcyclehasbeguncancelstheremainderofthetestandreturnstheunittonormaloperation.

RedServiceAlertIndicatorUndernormaloperatingconditions,theredServiceAlertIndicatorwillremain“off”.IntheeventtheSpectroncontrollerdetectsamalfunction,theredServiceAlertIndicatorwillblinkata1Hz.rate,basedonthefollowingtable:

GreenOperatingStatusIndicatorThegreenOperatingStatusIndicatorservesasbothanACpowerandaself-testindicator.Duringnormaloperation,thegreenOperatingStatusIndicatorwillbeilluminated,indicatingthepresenceofACpower.Duringallautomaticormanualself-testcycles,thegreenOperatingStatusIndicatorwillblinkata1Hz.rate.

MAINTENANCE

130068113006821300684130068593029025930290299302923593029327

Fig. 3

INSTALLATION INSTRUCTIONS

IMPORTANT:Thisexitsignmaybeequippedwithoneormoreoptions.Checkmodelnumbersuffixforoptiondesignation.Optionconnectionwiresmustberunbeforeexitsignface,whitetrimplateandclearcoverareinstalled.FIRE ALARM PANEL (-FAP) OPTIONFAPoptionconnectsto24voltACorDC(purplewires).FlashRate:.5secondson,.5secondsoff.DutyCycle:50%.DC REMOTE (-DC) OPTION DCRemoteoptionconnectsto6-24voltDC[yellow(–),blue(+)].FLASHER MODULE (-FM) OPTIONFlashRate:.5secondson,.5secondsoff.DutyCycle:50%

Connectoptionwires(-FAPor-DC)togreyconnectoronoptionboard.

Routewiresthroughtransformercompartmentandoutbackplate.

93029029

2. Thewhitetrimplatesurroundingtheexitsignfaceisheldinplaceby“hookandloop”velcro,locatedontheundersideofthetrimplate.Removethetrimplatebycarefullyliftingstraightuptodisengagethevelcro.

4.Drilltheappropriatesizeholeintheenclosureforconduitentrance.Fig. 2 showstherecommendedlocations.

1300681

3. RemovetheexitsignandmountingbracketfromtheenclosurebeforeproceedingtoStep4.

5. ConnectappropriateULListedhub(s)totheconduit,andconnecttotheenclosure.Routebuildingutilityconductorsthroughconduitandintoenclosure.

1300681

6. Reinstallexitsignmountingbracketandexitsign.RemoveexitsignfrontfacefromhousingbeforeproceedingtoStep7.

WIRING DIAGRAM120/277VAC

AC ONLY, EMERGENCY MODELS

1. Loosenthefourslottedcoverscrewsandremovetheclearcover.

(Typical,fourlocations)

Fig.1

Fig.2

7. MakeallconnectionstobuildingutilityACconductorsusingcolorcodedleadsprovided.

SeeFig.3andFig4.forappropriatewiringdiagrams.

Fig. 4WIRING DIAGRAM

120/277VACDUAL CIRCUIT (-2C Option) MODELS

8. Foremergencymodels,connectthebatteryasshowninFig.5.

93029025

Dual-circuittransformersecondarywiresconnecttoinputconnectoronoptionboard. Connectdual-circuitprimarytransformer

wirestoutilitysource.120VAC-connectblackandwhiteleads.277VAC-connectredandwhiteleads.

Fig. 5EMERGENCY MODEL

BATTERY CONNECTION

Chargerboardandbatterypack.(Emergencymodelsonly).

Foremergencymodels,plug2-pinbatteryconnectorintoPCboard.

9. Snap-inappropriatechevronarrowblank-outsinexitsignfrontface, ifrequired.Reassembleexitsignfacetohousing.Rinstallthewhite

trimplate(pressdowntoengagethefasteningstrips).Securetheclearcovertotheenclosure.

10.EnergizetheACpowertotheexitsign. NOTE:Foremergencymodels,allowthebatterytofullycharge beforetesting.