Automatic Transfer Switch (ATS)
Generator Transfer Switch (GTS)
Installation Manual020-161-B0 Rev. 01 / 07
Alpha Technologies
ATS GTS
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
2/16
Power
Alpha Technologies
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
3/16
From Alpha Technologies (www.alpha.com)
020-161-B0 Rev. 01 / 07
Installation Manual
Automatic Transfer Switch (ATS)
Generator Transfer Switch (GTS)
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
4/16
Save This Manual: It contains important installation and operating instructions. Keep it in a safe place.
Table of Contents
The emergency shutdown procedure is on the inside rear cover1 Safety Checklists ........................................1
2 Overview......................................................2
3 Mounting the ATS/GTS ............................... 3
4 Wiring the ATS/GTS to the UPS ................. 5
Specifcations ................................................ 8
DANGER
Risk of Electrical ShockTo reduce the risk of electrical shock and to ensure the safe operation of the ATS/GTS, the symbols
below are used throughout this manual. Where they appear, only qualied personnel should carry out
these instructions.
A dangerous voltage exists in this area. Use extreme caution at all times.
Attention: Important operating instructions. Follow them exactly.
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
5/16
1
The ATS and/or GTS are to be installed by people trained in the safe use of high-energy
power supplies and their batteries. Also assumed is knowledge of the local electrical
code(s) and their safe application.
DANGER: NEVERlet water from rain, a hose, tap or a sprinklers output, road splash or
other water sources enter the enclosure of the ATS/GTS to prevent accidental shorts,
shocks or electrocutions.
DANGER: This unit does NOT have an on/off switch. Whenever it is connected to line or
battery power, power is present at the output. Use extreme caution at all times.
Do not work alone under hazardous conditions.
Read this manual. If you have any questions about safe installation, operation or
maintenance, contact Alpha Technologiess customer service department.
Use this manual together with the Operators Manual of the UPS.
Carefully unpack the components. Report any shipping or other damage at once.
Always assume electrical connections or conductors are live. Turn off all circuit breakers
and double-check with a voltmeter before performing installation or maintenance.
Before installation, verify the input voltage and current requirements of the load are met by
the UPSs output (See specications). Verify the line voltage and current meet the UPSs
input requirements.
The ATS/GTS have more than one live circuit. AC power may be present at their outputseven if the UPS is disconnected from line or battery power.
The ATS/GTS can be operated to a maximum operating temperature of 55C.Also see the
specications section for temperature ratings.
At high ambient temperature conditions, the enclosures surface can be very hot to the
touch.
1 Safety Checklists
11
PRELIMINARY:ForInformationOnly
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
6/16
2
2 Overview
The Automatic Transfer Switch (ATS) (Figure 2.1) and the Generator Transfer Switch (GTS)
(Figure 2.2) are optional add-on switching units specically designed for (but not limited to) the
FXM family (FXM 650, 1100, 1500 and 2000) and the Novus Micro family (Micro 300/600/1000,
Standard, XL and XL3) of UPS. These switching units provide power and/or bypass capacity
(automatic or manual) so that the operator may safely disconnect the UPS from line or genera-tor power for easy removal and servicing. In bypass mode, the loads are directly connected to
the line or generator power without any conditioning. The ATS and/or GTS allow the use of 3
different back-up sources (line, batteries and/or generator).
PRELIMINARY:ForInformationOnly
Figure 2.1
Automatic Transfer Switch (ATS)
Figure 2.2
Generator Transfer Switch (GTS)
CB2
SW1
CB1
120 VAC Outputoption (NEMA 5-15R)
SW1
ATS/GTS Installation Manual
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
7/16
3
3 Mounting the ATS/GTS
The ATS and GTS can be mounted as stand alone, chassis (e.g. on the external bottom enclo-
sure of the Novus Micro family UPS) or rack (e.g. inside the end system enclosure of the FXM
family UPS). The following diagrams illustrate some of the possible congurations.
Top
SideFront
Figure 3.1 ATS mounting views (stand alone)
MOUNTINGEAR- TOPMOUNTED
MOUNTINGEAR- REARMOUNTED
Figure 3.2 ATS mounting view (chassis mounted)
Figure 3.3 ATS mounting view (rack mounted)
33
PRELIMINARY:ForInformationOnly
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
8/16
Figure 3. GTS mounting view (rack mounted)
Figure 3.5 ATS & GTS mounting view (rack mounted)
PRELIMINARY:ForInformationOnly
ATS/GTS Installation Manual
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
9/16
5
Wiring the ATS/GTS to the UPS
The ATS/GTS should be wired to the UPS as shown in Figure .1 below.
The ATS/GTS/UPS end system must be correctly grounded for proper operation.
Older facilities may have inadequate electrical grounding. Inspection must be performedby a qualied electrician before installation to ensure that grounding meets the local
electrical code.
To provide branch circuit protection, the utility line attached to the ATS/GTS/UPSs
input MUST be protected by a circuit breaker certied for this use as per the local
or national electrical code.
The breakers minimum size is calculated by the following formula:
Minimum Breaker Size= UPSs maximum input current / 0.8
The units maximum input current is read off of the UPSs nameplate. For example, if thenameplate gives the maximum input current as 25A, the circuit breaker should be rated
at least 30A.
The input and output lines to and from the ATS/GTS/UPS system MUST have
disconnect devices attached.
If stranded wires are used, ferrules or equivalent crimping terminals must be used.
Figure .1 ATS/GTS to UPS Wiring Diagram
55
PRELIMINARY:ForInformationOnly
LOAD
F X M F A MI L Y
ATS
INPUT O UTPU T
L N G
TO UPS FROM U PS
L
NLINE IN LIN E OU T
G
SC R EWLU G
GTS
LIN E IN
G EN
SC R EWLU G
TO UPS
SC R EWLU G
LOAD/ UPS I NPUT
SC R EWLU G
GTS
LIN E IN
G EN
SC R EWLU G
ATSLIN E IN
SC R EWLU G
SC R EWLU G
LIN E O U T
SC R EWLU G
LIN E O U T
L N G
L N G
L N G
L
N
G
L
N
G
L
N
G
L
N
G
UPSINPUT O UTPU T
LOAD
L
N
G
L
N
G
L
N
G
TO UPS FRO M UPS
L N G L N G
L
N
G
L
N
G
UPS
F i g 1. A T S & U P S
Fig 2. GTS
F X M F A M IL Y
F X M F A MI L Y
F i g 3. A T S & G T S
LINE OUT
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
10/16
6
ATS
With SW1 & CB1 On Unit is in UPS
Mode
With SW1 Off, CB1 On Unit is in
Bypass Mode
With SW1 On, CB1 Off UPS Inverter is
supplying power (Not recommended)
With SW1 & CB1 Off Unit is in Bypass
Service Mode
Figure .2 ATS schematic diagram
GTS
With SW1 On Automatic Generator
Transfer is Enabled
With SW1 Off Generator Transfer is
Disabled
Figure .3 GTS schematic diagram
PRELIMINARY:ForInformationOnly
ATS/GTS Installation Manual
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
11/16
7
Figure . ATS & GTS Schematic diagram
Servicing the UPS
ATS: Turn off CB1, SW1 and battery CB of the UPS.
GTS (UPS connected to Line Out): The main source branch CB protection coming either
from Generator or Line has to be turn-off. Likewise, battery CB of the UPS has to be turn-
off.
ATS and GTS combine: Turn off CB1, SW1 and battery CB of the UPS.
Other Note:
Simplex 5-15R receptacle is for 120V (rated 5A) only.
2 position mate and lock connector is for 230V only.
77
PRELIMINARY:ForInformationOnly
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
12/16
8
ATS/GTS Mechanical Specifcations
Dimensions, in (mm)
H x W x D
3.25 x 5.3 x .5
(82 x 135 x 11)
Weight, lb (kg)
(stand alone)
3 (1.36)
Material sheet metal, 1.2 mm thick
Color Black
Mounting options Stand alone, chassis or rack mounted
Connections
Line In
Line Out
From UPS or Gen
To UPS
2 position TB Weco #327-HDS-02 or equivalent.
2 position TB Weco #327-HDS-02 or equivalent.
3 position TB Weco #32-HDS-03 or equivalent.
3 position TB Weco #32-HDS-03 or equivalent.
Recommended Wire Size
Line In
Line Out
From UPS or Gen
To UPS
AWG #1 #6 AWG
AWG #1 #6 AWG
AWG #22 #10 AWG
AWG #22 #10 AWG
Note: Terminate all stranded wires with ferrules orequivalent crimp terminals.
Humidity
Operating (non-condensing)
Storage
Up to 95% (RH)
Up to 95% (RH)
Temperature Range, C
Operating
Storage (non-operating)
20 to 55*
0 to 75
* capable of operating up to 75C for 8 hours
Altitude, ft (m)
Operating
Storage (non-operating)
Up to 12,000* (3658)
Up to 15,000 (572)
* de-rate 2C per 1000 ft above 500 ft.>15000 ft
ATS/GTS Electrical Specifcations
Input
Voltage (nominal), VAC 120 or 230
Frequency, Hz, 5% 50/60
Current, Amps
(@ nominal Vin)30/16 @120/230VAC
Power, VA 3600
Power Factor 0.8 to 1.0
Output
Voltage (nominal), VAC per UPS, Line or Generator
Frequency, Hz, 5% 50/60
Power, W/VA 3600
Regulatory
Electrical Safety CSA 107.305
Immunity CE (for 230V version)
Due to ongoing product improvements, specifcations are subject to change without notice
PRELIMINARY:ForInformationOnly
ATS/GTS Installation Manual
Doc# 020-161-B0 Rev. 01 / 07
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
13/16
This page is intentionally left blank.
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
14/16
This page is intentionally left blank.
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
15/16
Emergency Shutdown Procedure
The ATS/GTS does not have an on/off switch. Whenever it senses battery or line
power, there is power present at the outputs and the unit is active.
1. Turn off the circuit breaker providing line power to the unit.
2. Disconnect the batteries from the UPS.
3. Turn OFF the attached generator (if connected).
For emergency technical support 7 days a week/2 hours a day, call:
USA: 1 800 863 336 Canada: 1 800 667 873
www.alpha.com
Complete the following for your records
Serial # ________________________________________
Options ________________________________________Purchase Date __________________________________
This Novus Micro Secure 100 was purchased from
Dealer _________________________________________
City ___________________________________________
State/Province ___________________________________
Zip/Postal Code __________________________________
Country ________________________________________
Telephone # ____________________________________
Fax # _________________________________________
E Mail Address __________________________________
7/30/2019 ATS_GTS Installation Manual (020-161-B0 Rev- 0107)
16/16
PowerAlpha Technologies
Due to continuing product improvements, Alpha reserves the right to change specications without notice.
Copyright 2007 Alpha Technologies, Inc. All rights reserved. Alpha is a registered trademark of Alpha Technologies. 020-161-B0 Rev. 01/07.
Alpha Technologies
3767 Alpha Way
Bellingham, WA 98226
USA
Tel: +1 360 67 2360
Fax: +1 360 671 936
Web: www.alpha.com
Alpha Technologies Ltd.
08 McConnell Court
Burnaby, BC, V5A 3N7
CANADA
Tel: +1 60 30 176
Fax: +1 60 30 8908
Alpha Technologies
Europe Ltd.
Twyford House
Thorley
Bishop's Stortford
Hertfordshire
CM22 7PA
UNITED KINGDOM
Tel: + 0 1279 501110
Fax: + 0 1279 659870
Alpha Technologies GmbH
Hansastrasse 8
D 91126 Schwabach
GERMANY
Tel: +9 9122 79889 0
Fax: +9 9122 79889 21
Alphatec, Ltd
P.O. Box 5668
Limassol, Cyprus
CYPRUS
Tel: +357 25 375675
Fax: +357 25 359595
AlphaTEK ooo
Khokhlovskiy Pereulok 16
Stroenie 1, ofce 403
109028 Moscow
RUSSIA
Tel: +7 95 916 185Fax: +7 95 916 139
Alphatec Baltics
S. Konarskio G. 9
Vilnius 2009
LITHUANIA
Tel: +350 5 210 5291
Fax: +350 5 210 5292
Alpha Technologies
5 Avenue Victor Hugo
F 9210 Calmart France
FRANCE
Tel: +33 3 1 90 07 07
Fax: +33 1 1 90 93 12
Recommended