Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 1 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
PROTH.
FAULTPKP
PTREC
LOCKBF
L5
TRIPCLOSE
L6
L7
ADR 245B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
PROTH.
FAULTPKP
PTREC
LOCKBF
L5
TRIPCLOSE
L6
L7
ADR 145B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
PROTH.
FAULTPKP
PTREC
LOCKBF
L5
TRIPCLOSE
L6
L7
ADR 245B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
PROTH.
PKPFAULT
DTREC
LOCKBF
L5
CLOSETRIP
L6
L7
ADR 245B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
ERRPROTH.
FAULTPKP
PTREC
LOCKBF
L5
TRIPCLOSE
L6
L7
ADR 245B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
PROTH.
FAULTPKP
PTREC
LOCKBF
L5
TRIPCLOSE
L6
L7
ADR 145B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
PROTH.
FAULTPKP
PTREC
LOCKBF
L5
TRIPCLOSE
L6
L7
ADR 245B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
PROTH.
PKPFAULT
DTREC
LOCKBF
L5
CLOSETRIP
L6
L7
ADR 245B
Ashida Numerical Directional 3O/C + 1E/F Protection Relay
ERR
Protection Features:
4 Element (3 Phase + EF +sensitive EF)
Directional / Non Directional Over current
IDMT/DMT.
Negative Phase Sequence element (46)
Selection of Curve: Five selectable curves
(Normal Inverse1 (C1), Normal Inverse2,
(C2) Very inverse (C3), Extremely Inverse
(C4), Long Time Inverse (C5)) and Define
Time (C6).
Instantaneous Over-Current Protection with
adjustable timer.
Breaker Failure detection.
In-built CB Trip Circuit Supervision function
during pre closing and post closing of CB.
In built Auto Reclose Relay (ARR).
On site CT Secondary selection 1A or 5A.
In built VT supervision features and
under/over voltage Alarm.
Internal reconstruction phase-phase
voltage and open delta voltage required
for direction detection.
Internal calculation of zero seq. EF
current (3Io) and Zero sequence voltage
(3Vo) for directional detection for Earth
fault.
NDV Protection.
Relay Design Features:
Large 20x4 LCD display for Parameter and
setting display.
Disturbance Recorder. Up 3sec of actual
waveform of current & voltage along
with logical and physical status are
captured & saved in the built-in memory
with date time stamping, for analyzing
fault condition & fault location. Fully communicable with IEC standard
open protocol. 60870-5-103
Separate Communication Port for SCADA
(RS485) as well as Local testing (RS232C)
Online display of CB status and other digital
and logical status.
Continuous monitoring of module’s internal
hardware and alarm generation in case of
failure of any critical components.
6 Digital Output contacts for local alarm as
well as tele-signalling.
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 2 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
2 Setting Groups.
CB CLOSE/TRIP from Relay keyboard 8 Optically isolated digital status input for
monitoring of status and avoid used of
external relay logic.
2 dedicated status input for Trip Circuit
Monitoring.
100 nos of event memory, event such CB
close, Trip, digital status change, relay pkp
etc. All events are with date and time
stamped up to 1ms.
10 nos of Fault data stored with keypad
interface and time stamping.
Display of Voltage, current, PF, Active,
Reactive Power in terms of primary
value.
Description:
ADR245B is second generation Numerical
Directional Over Current Earth fault Relay. It
consist all the necessary protection and
monitoring functions required for Normal feeder
It consist of
1. High Speed Digital DSP Controller
2. Analog Measuring Module
3. Power supply Module
4. Digital Input output module.
The High speed Digital Signal Controller
continuously monitors phase, E/F current and
PT Secondary voltage along with different
optical isolated status connections. The high-
speed micro-controller samples these current
and voltage signals through a A/D converter.
The Digital Signal performs powerful
Numerical Algorithms to find out RMS of
fundamental & harmonic contents of the current
and voltage, the direction of power flow then
this value is used for protection and metering
function. All measurement is tuned to
fundamental frequency i.e 50 or 60Hz
depending upon setting, thus relay remain
stable during distorted waveform by various
industrial load . All these measure values are
then used for different protection function such
as IDMT/DMT Over current protection,
Instantaneous Over current protection, Earth
Fault protection, IDMT/DMT Directional Over
Current and Earth Fault, Instantaneous
Directional Over Current and Earth Fault
protection etc. These measured values are also
displayed on large 20 x 4 LCD display for
metering purpose. The DSC also monitors
different digital input through optical isolator
and perform some monitoring function such trip
circuit supervision, and control potential free
contact for control CB and generate ALARM
and Tele-signalling
The power supply module is basically DC – DC
converted designed using modern PWM based
Switching mode technique to convert 110Vdc
station battery supply to the 12V and 24Vdc low
voltage supply for relay electronics and control
circuit. It also provides necessary isolation from
station battery. There are two type of power
supply modules are available 1) having range
of 77Vdc – 250Vdc. Covering requirement of
110Vdc and 220Vdc station battery system 2)
having range of 18Vdc to 250Vdc covering
24Vdc, 30Vdc, 110Vdc and 220Vdc station
battery requirement.
The relay is having total 8 nos of high intensity
dual LED for easy identification of type of fault
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 3 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
for easy user interface. LEDs L5, L6 & L7,
digital status input and control output R1 to R6
are fully programmable via keypad interface
Main Functions The ADR245B are having following protection
functions.
1. 4 stage of Directional phase Over current
element. (Ip1>, Ip2>, Ip>> and Ip>>>).
2. 3 stages of Directional 3Io (Internally
derived EF) (3Io>, 3Io>> and 3Io>>>).
3. 3 stages of Directional Ie (Externally EF or
REF) (Ie>, Ie>> and Ie>>>).
4. Negative phase sequence element.
5. Under / over voltage Protection .
6. Neutral Displacement voltage Protection .
7. Trip Circuit Super vision.
8. Breaker Failure Detection.
9. Monitoring Functions.
10. Auto Recloser Relay (ARR).
11. Relay / LED configuration
Each of these functions are independently
programmable and can be enable or disable by
user depending upon requirement.
Over Current Element:
The ADR245B is member of Ashida Numerical
Relay family design for protection general
feeder. The relay has four independent stages
of directional over current (Ip1>, Ip2>, IP>>, &
IP>>>). Stage 1 (>) stage 2 (>>) can be
programmed as IDMT or Definite Time. All
major international IDMT curves are available.
Stage 3 (>>>) can be programmed
Instantaneous or Define Time. Range of for
stage 1 and 2 is 10% to 250% for phase the
output of stage 1 (Ip>) is separate and not
connected to trip contact. The output of Ip1>
and Ip2> can be assigned to any of 6
programmable relay through key board. While
output of Ip>> and Ip>>> is connected to trip
element. Thus Ip> can be used as ALARM
before TRIP or can be used to TRIP another
CB before tripping main CB.
Although the curves tend towards infinite when
the current approaches Is (general threshold),
the minimum guaranteed value of the operating
current for all the curves with the inverse time
characteristic is 1.1Is (with a tolerance of ±
0.05Is).
Earth Fault Element:
The relay has two different type of Earth Fault
one is marked as 3Io and another is marked as
Ie. The 3Io is derived internally by software
through phase current while Ie is measured
from external CT. Thus Ie can be used as Core
Balance CT (CBCT) or Restricted EF (REF).
Each EF is having 3 stages (>, >>, & >>>).
Stage 1 (>) stage 2 (>>) can be programmed
as IDMT or Definite Time. All major
international IDMT curves are available. Stage
3 (>>>) can be programmed instantaneous or
Define Time. Range for stage 1 and stage 2 3Io
is 10% to 100% and for stage 3 3Io is 50% -
1200%. The Range for EF is from 5% to 80%
for stage 1, stage 2 and 50% to 1200% for
stage 3. The output of stage 1 (Ie>) is separate
and not connected to trip contact. The output of
> can be assigned to any of 6 programmable
relay through key board. While output of >> and
>>> is connected to trip element. Thus Ie> can
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 4 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
be used as ALARM before TRIP or can be used
to TRIP another CB before tripping main CB.
As standard practice all direction relay use two
healthy phase voltage for direction detection
and use MTA setting for phase angle
correction. For example R phase element use
R phase current and Y, B phase voltage. In
ADR245B use standard star connection at relay
side and internally reconstruct phase to phase
voltage required for direction detection.
Similarly relay calculates open delta voltage
(3Vo) and EF current (3Io) required for
detection of EF element.
Inverse Time Curves :- The each stage thresholds for phase (earth)
over current can be selected with an Inverse
Definite Minimum Time (IDMT) characteristic.
The time delay is calculated with a
mathematical formula
Curve Type
Description a b
C1 Standard Inverse_1
0.14 0.02
C2 Standard Inverse_2
0.60 0.02
C3 Very Inverse 13.5 1 C4 Extremely
inverse 80 2
C5 Long Time Inverse
120 1
C6 Define Time - -
The separate output contact allows to use each
stage for independent function such as stage 1
can be used for ALARM stage 2 for tripping or
both can be use for tripping independent CB.
Each stage can enable or disable depend upon
application.
Trip Circuit Supervision:-
The ADR245B is having 2 separate digital opto-
coupler status input which can be used to
continuously monitor continuity of trip-circuit.
The general scheme is as shown in fig. 4.
Relay monitor Trip coil continuity through CB
NO during close condition and through CB NC
during Trip condition. If any discontinuity
observed it generate Alarm signal.
The output marked as PROTH (Protection
healthy) is normally is ON and become OFF at
following condition
When DC supply is not sufficient (DC fail)
When T1 and T2 both active or both
inactive.
i.e CB NO as will as CB NC are both close
or open. Relay detects any internal
hardware Error.
K * aI
Iref
b1
t =K * aI
Iref
b1
t =K * aI
Iref
I
Iref
b1
t =K * aI
Iref
b1
t =K * aI
Iref
b1
t =K * aI
Iref
I
Iref
b1
t =
1
62
B+
B-
TC
CB NO
CB NC
Fig.4 Trip Circuit Logic
1
62
To Relay CPU
To Relay CPU
TCCOM
T1
T2
1
62
B+
B-
TC
CB NO
CB NC
Fig.4 Trip Circuit Logic
1
62
To Relay CPU
To Relay CPU1
62
B+
B-
TC
CB NO
CB NC
Fig.4 Trip Circuit Logic
1
62
To Relay CPU
To Relay CPU
TCCOM
T1
T2
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 5 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Auto Recloser Logic:- The ADR245B is provided with 4 shot Auto
recloser function. There are 4 timer for auto
recloser 1) Dead Time for shot 1 (DT1) 2) Dead
Time for shot 2 (DT2) 3) Dead Time for shot 3
(DT3) 4) Dead Time for shot 4 (DT4) and 5)
Reclaim Time (RT). After clearing of fault
ADR245B trigger dead Time 1 i.e DT1. after the
time delay Relay provide reclose command and
start reclaim timer RT. If second fault occur
during RT relay trigger Dead Time 2 i.e DT2. If
third fault occur during RT relay trigger Dead
Time 3 i.e DT3, If Fourth fault occur during RT
relay trigger Dead Time 4 i.e DT4 and after time
delay it again provide reclose command and
retrigger RT. If fifth fault occur during RT Relay
generate Lock-Out alarm and block further
reclose. The Lock-Out condition can be reset
locally as well remotely by SCADA through
communication digital status input.
Breaker Failure Detection :-
Normally after tripping current should become
Zero within 100 – 200ms time depend upon
type of fault and breaker mechanism. After
Fault ADR245B trigger internal timer (settable
from 0.1s to 1.0s) if fault is not cleared during
this time then relay declare as Breaker fail (LBB
function) and change another contacts. These
contacts is marked as Breaker Fail can be used
to TRIP back up breaker or can be used to
generate ALARM signal.
Under / Over Voltage Alarm :-
The ADR245B relay will be included
programmable function to detect under / over
voltage conditions. Relay had separate under
voltage and over voltage element. The under
voltage setting is from 45% to 95% and over
voltage setting from 105% to 155% of rated
(100% = 65.5V). Each function can be
separately enable or disable independently.
Whenever any phase voltage is above over
voltage setting or below under voltage setting
relay start internal timer (settable from 0.1 to 10
sec in steps of 0.1 sec). If voltage remain
abnormal during is time relay generate Alarm
signal. Any of the output element from RL1 to
RL6 can be assign to this function. The output
can be use for alarm or tripping of CB.
Negative sequence over current (46): - The ADR245B relay will be included
programmable function to detect unbalanced
fault conditions. When earth fault elements are
not operated or not sufficiently sensitive. The
ADR245B include negative phase sequence
over current element it can be programmed as
IDMT or definite time the actual setting range
will be finalized during later stage of design.
Neutral Displacement Voltage Protection :- Neutral displacement voltage protection function
is provided with internal & External selection.
With internal setting it uses 3Vo voltage (Open
Delta voltage) for sensing. In external setting it
uses external PT Voltage (Terminals C27 &
C28) for sensing. The setting is from 5.5V to
20V. Any output elements i.e. from RL1 to RL6
can be assign to this function.
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 6 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Setting Group:- The relay is provided with two setting groups G1
and G2, one of the groups is active at time. The
setting group can changed from digital input, this
allow user to change relay setting dynamically
as per outgoing load CB condition.
Programmable DI/DO and LED:- The ADR245B has 6 digital outputs, 8 opto-
isolated input and 6 general purpose LEDs.
These can be programmed by local key board.
Any logical of physical status can be assigned to
any relay contact The logic of digital status input
as well as logical status can be formed and
assigned to any of the relay output. The
disturbance record can be trigger from external
logical input.
Monitoring Functions (Event, Disturbance Record):-
Apart from basic protection functions. Relay is
continuously monitors all substations operation
through status, it internal functions, internal
hardware etc. if any changed is observed it
marked as event. Such type of events is stored
in internal non-volatile memory along with time
stamped. Following some of the events. Relay
PKP, Relay Reset, CB Trip, CB close, Changed
of any digital status input, Relay setting
changed etc.
Up to 100 such event can be stored and can be
download for detailed analysis. Apart from Event
record Relay also record actual waveform of
current and voltage along with all digital and
logical status during fault condition. Up to 10
such waveforms can be recorded, the duration
of disturbance record is 1 sec. The disturbance
record can be trigger from physical status
input as well as from pick, trip operation of
relay. This waveform can be downloaded
through communication port for further analysis
Relay Talk Software: The general communication software is
provided to communicate with relay, known as
Relay Talk. By using this software data such as
event log, disturbance records etc can be down
loaded and can be further analysis. The
disturbance record data can be saved in
standard COMTRADE Format which is
understandable by numbers of relay testing
units for play back.
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 7 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Following as some of software clips All The data can view at time
All The data can view at time
Event list with real time
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 8 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
The waveform and logical and physical status latched by relay can be view and analysed
Data can be viewed as raw sine wave
or RMS value
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 9 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
While Order ing Specify the fol lowing Information for ADR245B Relay
Order ing informat ion:
A D R 2 4 5 B - A M - X X X - X X - X - X - X X - X
Example ADR245B – AM-201-02-3-1-02-0 Type: ADR245B St . Back termina l layout Cabinet Type: CSE -150 H Termina l Removable Aux i l ia ry Supply: 77-250Vdc CT sec: 1 Amp. / 5 Amp selectable PT sec : 63.5V P-N / 110VP-P
AM XXX XX X Over Current Earth Fault Relay
For Adity-V2 series start from 201. For V1 series refer respective document 201 01 Obsolete Version CSE – H – 150 3 201 02 Relay with standard Back Connection CSE – H – 130 3
D e f i n i t i o n o f M o d e l N o o f A d i t y a S e r i e s o f R e l a y s
A M X X X – X X – X – X – X X – X
Auxiliary Supply
01 = 18 – 52 V dc 04 = 30 V dc 02 = 77 – 250 V dc 05 = 48 V dc 03 = 24 V dc 06 = 18 – 250 V dc
Reserved for Future Use
PT Secondary 0 = NO PT 1 = 63.5 PT sec
CT Secondary 1 = 1 Amp. 2 = 5 Amp. 3 = 1 Amp. / 5 Amp. Selectable
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 10 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Technical Specifications: General specifications Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5Amp. Or 1Amp site selectable II. Aux. Supply : 77 - 250VDC. Or 18 – 250VDC to be specified
III. VA burden on CT : Less than 0.2VA IV. VA burden on Aux. : Less than 10 Watts V. VA burden on PT : Less than 0.2 VA
VI. Operating Temp. range : -10 deg. To + 65 deg. VII. Continuous carrying capacity : 2 x of rated for CT and 1.5 x of rated for PT
VIII. Pick up : Within 1.1 times of set value. IX. Reset Value : 95% to 90% of pick up. X. Output Contact : 2 for Trip
: 1 for Reclose : 1 for Protection Healthy : 1 for Reclaim : 6 for General Programmable
XI. Contact Rating : Continuous: 5A : Make & carry for 0.5 sec : 30A : Make carry for 3 sec : 15A
XII. Opto Isolated input : 1 for CB NO & 1 for CB NC : 8 as general programmable
XIII. Thermal Withstand for CT : 20 x of rated for 3.0 sec.
General Setting : Unit ID 1 – 250 in step of 1 : Baud Rate 1200 - 57600 : Com Port RS232 / RS485 : Set Parity None / Even / Odd : Group Selection G1 / G2 : BF Enable YES / NO : BF Delay 100 – 1000 msec in step of 50msec : CT Sec 1A / 5A : CT Primary 10 – 2000 in step of 1 : PT Primary 1KV – 400KV in step of 1KV : Local Control YES / NO : Trip Ckt Test YES / NO : Trip Cont SR / HR : Trip Led SR / HR
XIV. Settings
: Post Trigger 10% - 90% in step of 1%
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 11 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Phase Section (Ip)
: IP1> Enable YES / NO : IP1> Settings 10% – 250% in steps of 1%. : IP1> Time Multiplier (TMS) x0.02 – x1.00 in steps of 0.01 : IP1> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: IP1> C6 Delay 0 – 1899.9 Sec in steps of 0.1Sec.
: IP2> Enable YES / NO : IP2> Settings 10% – 250% insteps of 1% : IP2> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01 : IP2> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: IP2> C6 Delay 0 – 1899.9 Sec in steps of 0.1Sec.
: IP>> Enable YES / NO : IP>> Settings 10% – 250% insteps of 1% : IP>> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01 : IP>> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: IP>> C6 Delay 0 – 99.99 Sec in steps of 0.1Sec.
: IP>>> Enable YES / NO : IP>>> Settings 50% – 3000% insteps of 10% : IP>>> C6 Delay 0 – 90.00 Sec in steps of 0.01Sec.
XV. Phase (OC – G1 )
: MTA Settings 0° – 360 Lead in steps of 5°
External Earth Fault Section (Ie) : IE> Enable YES / NO : IE> Settings 5% – 80% insteps of 1% : IE> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01. : IE> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: IE> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IE>> Enable YES / NO : IE>> Settings 5% – 80% insteps of 1% : IE>> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01. : IE>> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: IE>> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IE>>> Enable YES / NO : IE>>> Settings 50% – 1200% insteps of 10%
XVI. EF – G1
: IE>>> C6 Delay 0 – 3.00 Sec in steps of 0.01Sec.
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 12 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Internally derived Earth Fault Section (3Io)
: 3Io> Enable YES / NO : 3Io> Settings 10% – 100% insteps of 1% : 3Io> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01. : 3Io> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: 3Io> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: 3Io>> Enable YES / NO : 3Io>> Settings 10% – 100% insteps of 1% : 3Io>> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01. : 3Io>> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: 3Io>> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: 3Io>>> Enable YES / NO : 3Io>>> Settings 50% – 1200% insteps of 10% : 3Io>>> C6 Delay 0 – 3.00 Sec in steps of 0.01Sec.
XVII. 3Io – G1
: MTA Settings 0° – 360° Lag in steps of 5°
Negative Phase sequence Element (46)`Section : I2>> Enable YES / NO
: I2>> Settings 10% – 100% insteps of 1%
: I2>> Time Multiplier (TMS) x0.02 – x1.00 in step of 0.01.
: I2>> Curve (Operating Time)
C1 – C6 ( IDMT curve C1 – C5 or Define Time C6 )
: I2>> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: I2>>> Enable YES / NO
: I2>>> Settings 50% – 1500% insteps of 10%
NPS – G1
: I2>>> C6 Delay 0 – 3.00 Sec in steps of 0.01Sec.
: C1 Std. Inverse. 1 (3.0S) : C2 Std. Inverse 2 (1.3S) : C3 Very Inverse : C4 Extremely inverse : C5 Long Time Inverse
XVIII.
Additional Data
: C6
Define Time (00 – 99 Sec In steps of 1.0s.)
Under / Over voltage Section (V< / V>) : V< OFF / ON : Setting 45% - 95% insteps of 1%
Under Voltage (V<)
: Operating Time 0.1 to 10.0 sec : V> OFF / ON : Setting 105% - 155% insteps of 1%
XIX.
Over Voltage (V>)
: Operating Time 0.1 to 10.0 sec
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 13 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Neutral Displacement Voltage Protection (NDV)
: NDV Enable Yes/No : NDV Ext/Int Int/Ext : Setting 5.5 to 20V
XX. Neutral Displacement Voltage
: Timing 0 to 10 sec.
Auto Recloser Section : Numbers of shot 0 – 4 / 0 = bypass : Dead Time 1, 2 , 3, 4 0.1S – 180s
XXI. Auto Recloser
: Relaim Time 200 – 300s
Operational Indicators (Flags) PROT.H /ERR : Green LED indicates Relay OK (Protection Healthy)
: Red LED indicates Fault in following conditions. 1. Problem in relay Hardware. 2. Trip Circuit Faulty
PICK-UP / FAULT : Green LED indicates Start of Timer. Self Reset (SR) Type : Red LED indicates FAULT. Hand Reset (HR) Type.
DT / REC : Green LED indicates Dead Time : Red LED indicate Reclaim Time
LOCK / BF : Green LED indicates ARR lock-out (HR) Type : Red LED indicates Breaker Fail (HR) Type
L5 / L6 / L7 : Spare LEDs Programmable
XXII.
CLOSE / TRIP : Green LED indicates Output CLOSE relay contact closer (SR) Type : Red LED indicates Output TRIP relay contact closer (SR) Type : For Back Connections - ADV02601 : For Cabinet Type - MAC01301 : For Typical External connection - ADV02501
XXIII. Drawing References
: For Typical External connection - ADV02502 The Relay Confirm to following standard Sr. No. Title Standard no. Electromagnetic Compatibility Type Test:
1. High Frequency Test : IEC 60255-22-1, class – III : Frequency : 1MHz Damped Oscillatory : Longitudinal :5 KV (peak) : Duration: sec duration 2 sec. : Between input current Terminal
2. Electrostatic Discharge Direct Application
: IEC 60255-22-2 Class III and IEC 61000-4-2 class III. : Contact discharge: 6kV, : Air discharge: 8KV : Polarity: both +ve and –Ve polarities.
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 14 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
3. Indirect Application : IEC-61000-4-2, Class-III
4. Fast Transient Disturbance
: IEC 60255-22-4 and IEC 61000-4-4, class A : 1.2KV; 5/50ns; 5KHz burst duration = 15ms. : Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.
5. Surge Immunity Test
: IEC 60255-22-5 / IEC 61000-4-6 class 4 : Differential Mode = 2kV : Common Mode = 4kV : 1.2/50uS , 5 surges of each polarity
6. Power Frequency Immunity Test : IEC-60255-22-7, Class-A
7. Power Frequency Magnetic Field Test
: IEC-61000-4-8, Class-V
8. Radiated Electromagnetic Field Disturbance
: IEC- 60255-22-3 : EN-61000-4-3 : Frequency 80MHz – 1GHz
9. Conducted Disturbance Induced By Radio Frequency Field
: IEC 60255-22-6 / IEC 61000-4-6: 1996. : Freq. 150kHz – 80MHz, Amplitude 10 V, Modulation 80% AM @ 1 KHz
10. AC Ripple In DC Supply Test
: IEC 60255-11
11. Radiated Emission : IEC- 60255-25 Insulation Tests:
12. High Voltage Test
: IEC 60255-5. class – III : At 2.5kV 50Hz between all terminal connected together and earth for 1 minutes
13. Impulse Voltage Test
: IEC60255-5. class – III : Test voltage: 5KV (peak) 1.2 / 50us, : Energy :0.5 J, : Polarity : + ve and – Ve : Nos. of impulses : 3 positive and 3 negative impulse : Duration between Impulses : 5 sec.
Environmental tests: 14. Cold test Storage test : IEC-60068-2-1 15. Dry heat test : IEC-60068-2-2
16. Damp heat test, steady state : IEC-60068-2-3
17. Damp heat test, cyclic : IEC-60068-2-30 CE compliance
18. Immunity : IEC-60255-26 19. Emissive Test : IEC- 60255-26 20. Low voltage directive : EN-50178
Ref.:ADR245B_V2 Issue: 01 15.10.09
Page 15 / 15
ASHIDA ELECTRONICS PVT LTD. ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com
Note: Due to our po l icy to upgrade our products constant ly , we reserve the r ight to supply products which may vary s l ight ly f rom that ind icated above.
Type: ADR245B (ADITYA–V2 Ser ies )
(Pre l iminary)
‚þ¹ªþ¸þ
ASHIDA Numerical Directional 3OC + 1EF Protection Relay
Mechanical tests
21. Vibration
: IEC 60255-21-1 class 1 : Frequency Range = 10Hz – 150Hz , acceleration. = 1gn (9.8 m/s2)
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis. 22. Bump Test : IEC 60255-21-2 Class-1
: 1000 bumps of 10gn peak acceleration and 16ms pulse duration in each of the two opposite direction per axis as per IEC60255-21-2 class 1 No. of axes . 3.
23. Shock Withstand : IEC 60255-21-2 Clas-1 : 3 shocks of 15gn peak acceleration and 11ms pulse in each of two opposite direction. No. of axis : 3
24. Seismic Test : IEC 60255-21-3 : In single axis sine sweep in X-axis sweep (@a sweep rate of 1 octave/minute) vibration in the frequency range (5-40 Hz) at amplitude of 3.5mm or 1.0gn (whichever is less)
: In single axis sine sweep in Y-axis - sweep (@a sweep rate of 1 octave/minute) vibration in the frequency range (5-40 Hz) at amplitude of 1.5mm or 0.5gn (whichever is less)
Revision Date Description 01 15.10.2009 Original specifications