TASK OF ENGLISH LANGUAGE
Home Electrical Instalation Project
By :
Name: Arsi Yota Ihsaningrum
NIM / No. : 1131120117 / 02
CLASS : D3 TL 1-A
ELECTRICAL ENGINEERING OF STUDY PROGRAM
ELECTRO ENGINEERING DEPARTEMENT
STATE POLYTECHNIC OF MALANG
2012
8/13/2019 Arsi Yota Ihsaningrum (02)
2/16
STATE POLYTECHNIC OF MALANG
8/13/2019 Arsi Yota Ihsaningrum (02)
3/16
Drawn by : Ars i Yo ta Ihsan ingrum
Scale
1 : 200
Drawing Number
02
Checked by : Mr. Al i Imron
Date : 10 July 2012 STATE POLYTECHNIC OF
MALANG
HOUSE TYPE
2. House Type
House Type is used to know about wide
of building or wide of land.
Example : House type 200, House type
250, House type 450 etc.
TYPE 140/132
[TYPE 140/132]TYPE 105/112 TYPE 140/132
TYPE 185/249 TYPE 250/254
8/13/2019 Arsi Yota Ihsaningrum (02)
4/16
Drawn by : Ars i Yo ta Ihsan ingrum
Scale
1 : 200
Drawing Number
03
Checked by : Mr. Al i Imron
Date : 10 July 2012 STATE POLYTECHNIC OF
MALANG
CONSTUCTION
3. Constuction
Construction is form, condition of manifestly of building, which can be
seen from lenght, wide, and high of building or it can be seen from made
construction material.For example : Construction of home type 250
Specification of home type 250
Wide of home is 250 m2
Wide of grounding is 254 m2
Power Reaktif (PLN) = 2200 VA ( Faction R2 )
Length of house = 16.5 meter
Width of house = 15 meter
High of house = 10 meter ( wall and roof )
High installation of switch = 1.5 meter
High installation of box contact = 1.5 meter
Local foundation = Foundation of reinforced concrete times is ril
Wall = Brick wall is platered by ACI, finishing paint
Roof = construction wood of borneo super, ceramicSpecification of room :
a. Terrace 1
Wide of room : 4.5 m2
Length of room : 3 m
Width of room : 1.5m
High of room : 10 m
Colour of floor : White
Colour of wall : White
b. Terrace 2
Wide of room : 6 m2
Length of room : 3 m
Width of room : 2 m
High of room : 10 mColour of floor : White
Colour of wall : White
c. Living room
Wide of room : 15 m2
Length of room : 5 m
Width of room : 3 m
High of room : 10 m
Colour of floor: : White
Colour of wall : White
Example of home construction
at the drawing number 4
8/13/2019 Arsi Yota Ihsaningrum (02)
5/16
House Ichno graph
Drawn by : Ars i Yo ta Ihsan ingrum
Scale
1 : 200
Drawing Number
04
Checked by : Mr. Al i Imron
Date : 10 July 2012
Garden
Bedroom 1
Ministrant
Room
KitchenAdditional
Kitchen Dining
Room
Guest
Room
Living Room
Toilet
doorstep
Balcony 1
Terrace
1
Bathroom
GardenGarage
11.5 10 34.75 25.5
22.5
11
5.25
25
13.75
21.25
26.2
5
13.2
5
16.7
5
27.5 16.26 24 13.5
Up
STATE POLYTECHNIC OF
MALANG
8/13/2019 Arsi Yota Ihsaningrum (02)
6/16
Drawn by : Arsi Yota Ihsaningrum
Scale
1 : 200
Drawing Number
05
Checked by : Mr. Ali Imron
Date : 10 July 2012 STATE POLYTECHNIC OF
MALANG
RECAPITULATION OF LAMP
4. Recapitulation of Lamp
Recapitulation of Lampis calculation of lamp to be attach
room. It can belooked by using roominess and high of r
be obtained by room flux. Where room flux is divided
Explaining :
I used CFL ( Compact Flourescent Lamp ) Rk = Room factor t = total flux of room (lumen) l = total flux of lamp (lumen, from
catalog) E = Strong of lighting (lux) A = roomines (m) = efficiency of room n = total lamp
Example of recapitulation lamp
at drawing number 06
8/13/2019 Arsi Yota Ihsaningrum (02)
7/16
CALCULATIONOFLAMP
Skala
-
1
Terrace
Direct
3.2
5
2.0
0
4.00
0.3
0
0.7
0
100
931.3
4
930
1.
00
1
PL-ElectronicWarmwhiteBC
16W
2
GuestRoo
m
Direct
4.2
5
2.0
0
3.50
0.3
9
0.6
1
100
1400.0
0
148
5
0.
94
1
MASTERPL-ElectronicPolar23W
3
LivingRoo
m
Direct
5.0
0
4.8
0
3.50
0.7
0
0.3
0
100
7875.0
0
430
0
1.
83
2
MASTERPL-T/4P57W
4
DiningRoom
Direct
4.5
0
4.0
0
3.50
0.6
0
0.4
0
100
4447.0
6
430
0
1.
03
1
MASTERPL-T/4P57W
5
Bedroom1
Direct
5.0
0
4.5
0
3.50
0.6
7
0.3
3
100
6750.0
0
350
0
1.
93
2
MASTERPL-L/4P2G1140W
6
Ministrantroom
Direct
2.5
0
2.0
0
3.50
0.3
1
0.6
9
250
1810.3
4
180
0
1.
01
1
MASTERPL-C/2P26W
7
Toilet
Direct
1.0
5
2.3
0
3.50
0.2
7
0.7
3
250
825.9
8
810
1.
02
1
GenieESaverWarmwhite14
W
8
Bedroom2
Direct
2.7
0
2.2
0
3.50
0.3
4
0.6
6
250
2243.5
3
240
0
0.
93
1
MASTERPL-T/4P32W
9
Kitchen
Direct
2.6
5
2.3
0
3.50
0.3
5
0.6
5
250
2327.1
8
240
0
0.
97
1
MASTERPL-T/4P32W
10
itia
litc
Direct
4.0
0
2.0
0
3.50
0.3
8
0.6
2
250
3230.7
7
320
0
1.
01
1
MASTERPL-T/4P42W
12
Balcony
Direct
3.3
5
2.3
0
3.50
0.3
8
0.6
2
125
1549.8
6
180
0
0.
86
1
MASTERPL-C/2P26W
13
Garage
Direct
5.2
5
5.5
0
3.50
0.7
7
0.2
3
125
15957
430
0
3.71
4
MASTERPL-T/4P57W
CalculationofLamp
No
Room
LightingType
Length
width
high
Rk
(%)
E(lux
t(lmn
l
(lm
)
n
TypeofLamp
Drawnby
:ArsiYotaIhsaningrum
Draw
ingNumber
06
Checkedby
:Mr.
Ali
Imron
Date
:10July2012
STATE
POLYTECHNICOFMALAN
G
8/13/2019 Arsi Yota Ihsaningrum (02)
8/16
Drawn by : A rs i Yo ta Ihsan ing rum
Scale
1 : 200
Draw ing Number
7
Checked by : Mr. Al i Imron
Date : 10 Ju ly 2012 STATE POLYTECHNIC OF
MALANG
WIRING DIAGRAM
Information :
= lamp CFL
= Single Swicth
= series swicth
= Stop kontak
= panel box
= on plaster
= in plaster
KWH
Up
B1
B2
B2B1
C
C
D
D
E E
FF
G
G
A
H
H
H
I
I
J1
J1
J2
J2
K
K
LL
5. Wiring Diagram
Wiring Diagram is diagram which used to explain the connecting cable from
source voltage ( PLN ) until load. Example : At above
8/13/2019 Arsi Yota Ihsaningrum (02)
9/16
STATE POLYTECHNIC OFMALANG
SINGLE LINE DIAGRAM
kWh
Group 1
Group 2
Group 3
7 lamp 1 Electric Socket
5 lamp 2 Electric Socket
11 lamp 2 Electric Socket
Drawn by : Ars i Yota Ihsaningrum
Cheked b y : Mr . A li Im r on
Date
10 July 2012
Drawing Number
08
6. Single Line Diagram
Single Line Diagram is diagram which used to know kinds of burden athouse installation connecting of voltage source. its target is to water
down read of installation diagram.
8/13/2019 Arsi Yota Ihsaningrum (02)
10/16
Drawn by : Ars i Yo ta Ihsan ingrum
Scale
-
Drawing Number
09
Checked by : Mr. Al i Imron
Date : 10 July 2012 STATE POLYTECHNIC OF
MALANG
POWER RECAPITULATION
Quantity Power VA Quantity Power VA Power (VA) Current
1 Terrace 1 18 21.2 - - -
2 Guest Room 1 23 27.1 1 100 100
3 Living room 2 58 136.5 1 100 100
4 Door Step 1 18 21.2 - - -
5 Bedroom 1 2 58 136.5 2 100 200
6 Toilet 1 15 17.6 - - -
7 Bathroom 1 1 36 42.4 - - -
402.4 400
Quantity Watt VA Quantity Watt VA Power (VA) Current
1 Garage 4 58 272.9 - - -
2 Kitchen 1 36 42.4 1 250 250
3 Additional Kitchen 1 58 68.2 1 100 100
4 Dining Room 1 58 68.2 - - -
5 Ministrant 1 30 35.3 - - -
6 Balcony 1 23 27.1 - - -
514.1 350
No. RoomCFL Electric Socket Tota Load
814.1
Total
802.4
Total
CFL Electric Socket Tota Load
No. Room
7. Power Recapitulation
Power recapitulation is calculation of energy
which is used all component in place or building.
That can be used to look for strength pass
of current, using of cable type, protecting ( MCB ).
The formula of strength pass of current :
= %
= %
8/13/2019 Arsi Yota Ihsaningrum (02)
11/16
CALCULATION OF ARRESTERDrawn by : A rs i Yo ta Ihsan ing rum
Scale
-
Drawing n umber
10
Checked by: Mr. Al i Imron
Date : 10 Ju ly 2012
CALCULATION OF ARRESTER
Spanner of Extention
RE1 = 2
RE2 = = = 0.086
A =
=
=
r =
=
=
=
RG =
=
= 14.5
=
= 2,7
RP = = so 4 Electrode is attaced parallel
Explanation :
Level of Protection = 99.9 %
Current of thunder (Ig) = 1.6 kA
T = Time depth thunder pouncing movement (detik)
A = wide of electrode(mm2)
r = electrode radius(m)
= R trouble ( )
= constanta ( 5,3 ( 4 electroda parallel )
= Clay specific mass ( m) 100 m
LR = Length electrode (m) 8 m
STATE POLYTECHNIC OF MALANG
8. Arrester
Arrester is tool which used to protect house of thunder danger. It work from
catching thunder , and then it channelled to land used to neutralizing.
Component of arrester is venial, strand of metal and pillar. To calculate thearrester we require information about high of building, wide of building and
building pounce thunder. It is made because arrester can be used to better.
8/13/2019 Arsi Yota Ihsaningrum (02)
12/16
PICTURE OF ARRESTER
Skala
-
16.5 meter
10
meter
Hb = 9 m
Hb = 9 m
Hb = 9 m
STATE POLYTECHNIC OF
MALANG Drawing Number11
8/13/2019 Arsi Yota Ihsaningrum (02)
13/16
Skala
-
CALCULATION OF GROUNDING SYSTEM
CALCULA TION OF GROUNDING SYSTEM
Drawn by : A rs i Yo ta Ihsan ing rum
Draw ing Number
12
Checked by : Mr . A l i Imron
Date : 10 Ju ly 2012
STATE POLYTECHNIC OF MAL ANG
9. Grounding System
Grounding System is conductor system which relation attributing to system,
equipments body and of instalation with earth so that can protect human of
electrics sting, and protect installation components of tension danger /
current of abnormal.
8/13/2019 Arsi Yota Ihsaningrum (02)
14/16
Drawn by : Ars i Yo ta Ihsan ingrum
Scale Draw ing Number
13
Checked by : Mr. Al i Imron
Date : 10 July 2012 STATE POLYTECHNIC OF
MALANG
MATERIAL OF INSTALA TION
No Name of Material Specification Quantity Explanation
PL-Electronic Warm white BC 16 W 1 component
MASTER PL-Electronic Polar 23 W 1 component
MASTER PL-T /4P 57 W 11 component
MASTER PL-L /4P 2G11 40 W 1 component
MASTER PL-C /2P 26 W 2 component
Genie ESaver Warm white 14 W 1 component
MASTER PL-T /4P 32 W 2 component
Genie ESaver Warm white 18 W 1 component
MASTER PL-S /4P 2G7 9W/ 827 3 component
MASTER PL-T /4P 2G7 36W/827 1 component
MASTER PL-L /4P 2G11 40 W 1 component
MASTER PL-T /4P 42 W 1 component
2 Fitting E27, 250 V / 2 A, BROCO 26 component
3 Single Switch 250 V / 5 A , BROCO 10 component
4 Double Switch 250 V / 5 A , BROCO 6 component
5 Stop Contact 100 VA, BROCO 8 component
6 Stop Contact 250 VA, BROCO 1 component
7 MCB 3 pole 12 A, MERLIN GERIN 1 component
8 Fuse Box 3 pole 25A / 250V, BROCO 1 component
9 MCB 1 pole 4 A, BROCO 3 component
10 KWHmeter 1 phase 1 component
13 NYA cable 2,5 mm Black ( phase ),KABELINDO 165 meter14 NYA cable 2,5 mm Blue (N), KABELINDO 137 meter
15 NYA cable 2,5 mm Yello (PE), KABELINDO 48 meter
16 Elbow 5/8", NAGA 26 component
17 T-Dos 5/8", NAGA 49 component
18 Cross-Dos 5/8", NAGA 6 component
19 PVC pipe 5/8" , MASPION 235 meter
20 PVC clamp 5/8" , MASPION 8 dos
21 Lasdop 2,3,4 109 component
22 Wood Spaner 5/8"x5 7 dos
23 Isolation 5mm, DAIMARU 5 roll
1 CFL (Compact
Flourensence
Lamp)
MATERIAL OF INSTALATION
8/13/2019 Arsi Yota Ihsaningrum (02)
15/16
Description of Material
a. Fluorescant Lamp is lamp capable which yield light by heating red hot fiber ( filamen).Where is
ever greater [of] energy a fluorescant lamp, hence will be bold progressively lamp. Some
fluorescant lamp energy size measure that is : 10 watt, 25 watt, 60 watt of dsb.
b. Lamp fitting / Tender is place to install lamp. Itable to be used for lighting outside room and
does not need roset], and the physically ,it is stonger from local fitting. Tender have 2 terminal,
one terminal for the cable of phasa, and one terminal for neutral cable.
c. Switch is appliance which used to operate 1 lamp or 2 lamp at the same time. Switch is made
from ceramic materials and have 4 terminal , 2 terminal for the phasa of lamp and 2 terminal
for neutral.
d. Push Button is tool which used to start impuls switch or it is used to switch the lamp. It works
without using breach-block and have 2 terminal one to for output and one for input. And it also
has ability of 250 V / 1 A.
e. Electric Socket is apparatus which used to connect burden with source of voltage. It is made
from ceramic materials. Owning 3 terminal ( phasa,netral, PE) and box contact this have ability100 VA, 250 VA or 500 VA.
f. Junction Box is place of tacking on cable of component.Junction box have 8 pole. And it just
can be used to conductor with admitted 1.5 mm2 until 2.5 mm2.
g. PVC pipe is used to protect the electrics installation cable. It is made from polifinilclorida.
Pipe of PVC can not be used to the temperature of normal job 60 C. In needed places, pipe
of PVC have to secure against by mechanical damage, for example in places penetration of
floor.
h. MCB ( Miniatur Circuit Breaker ) is tools which used to protect by overload or short circuit. At
MCB, there are two peacemaker type.That is by thermis and elektromagnetis, peacemaker of
function termis to protect full current while peacemaker of function elektromagnetis is used to
protect if happened short circuit. Peacemaker of thermal at MCB have principle which equal tooverload thermal. That use two joined metal ( bimetal),
i. Cable NYA 2.5 mm2is conductor which used to housing installation because it is relative cheap.
It is have single core , laminated of] insulation materials of PVC, for external installatio. Colour
insulation code is yellow, black and blue. Yellow for Grounding, black for phase ang blue for
neutral.
j. Elbow is pipe which used to watering down and quicken work of installation but pipe factory
also provide the tacking on elbow for the road;street of pipe turning bevel.
k. Clamp is apparatus to detain pipe, so it can be attached at roof or wall. It can be made by iron
or PVC. Its size is adapted by pipe size.
l. APP (Alat Pembagi dan Pembatas) / Grader and Constrictor is tool is used by appliancemeasuring ( KWh-meter ) and at the sam time it can used to protecting ( MCB )
8/13/2019 Arsi Yota Ihsaningrum (02)
16/16
Electric Socket
Electric SocketNYA Cable
MCBLampDouble Switch
Fitting LampJunction BoxElbowKWh-meter