Arc Fault Detection DevicesAF seriesCompatible with Unibis* compact MCBs, RCBOs (2P), ceRCBOs for maximum installation safety, compacity & flexibility
New 2018
AF series
1
2 Introduction
8
9
10
12
16
18
19
Product features
Nomenclature
Arc Fault Detection Device - Order codes
Series AF - UNR B for compact MCBs (1P+N) Unibis 6kA
Series AF - DPC B for RCBO (2P) Unibis up to 10kA
Series AF - DMCE B for ceRCBO neutral switched Unibis 6kA
Accessories
Dimensional drawings
Fire hazards caused by arc faults in electrical installations
Each year in Europe, 2 million fires occur in Europe, mainly in residential and commercial buildings costing billions of property damages and numerous deaths. 33% of these fires are caused by electrical faults in electrical installations.
Circuit Breakers and Earth Leakage detection protects from fire but NOT always…Arc faults in damaged cables or loose connections are some-times intermittent peak currents of low intensity, not detected by traditional Miniature Circuit Breakers or Residual Current Devices, but sufficient enough to create carbon built-up, up to 1000°c local heat and ignite fires.
What causes Arc Faults?Arc faults are small electrical arcs generated by loose connec-tions, isolation defects in high impedance circuits due to aging or damaged load circuits.
Arc Fault Detection Devices
Drilling through Cables Insulation deterioration Pulling Cables
Pets, rodents damaging Cables
Examples of arc faults causes
Loose cable connection Trapped Cables
126 billion €Fire damage costs in
Europe each year
33%of building fires
are caused by electrical
faults
90%of fires in Europe occur in buildings
and mainly at night
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
3
What is an Arc Fault Detection Device (AFDD)?
An Arc Fault device detects series, parallel or ground arc fault on an early stage, before a fire can occur and disconnect the final circuit with the associated circuit breaker, ground leakage device or breaker.
The diagrams below explain the different level of protections you can expect from MCBs, RCBOs (2P) and AFFDs
This type of arc fault occur on a broken conductor of the final circuit, with a low current level above or equal 5A.
MCBNO
RCDNO
RCBONO
AFDDYES
MCB ?MAYBE
RCDYES
RCBOYES
AFDDYES
MCB ?MAYBE
RCCBNO
RCBO ?MAYBE
AFDDYES
This type of arc fault occur on a damaged final circuit (pierced cable by nails or clamp), with an arc between two conductors: phase to phase or phase to neutral or ground. The current level is high and not limited by the load and is above or equal 75A.
Typical tripping characteristics with AFDD combined with a Miniature Circuit Breaker
Example shown of a MCB tripping curves B, C, D, and tripping curves of an AFDD
Tripping/arc currentArc current value vs Maxium operating time acc. IEC/EN 62606
2.5 A / 1 s 5 A / 0.5 s 10 A / 0.25 s 16 A / 0.15 s40 A / 0.12 s
AFDD is designed to distinguish fire hazard arc faults from arcing associated with normal operating standard equipment such as drills, vacuum cleaners, fluorescent lighting, arc soldering, dimmers, sockets switching …
Ground arc fault
Parallel arc fault
Series arc fault
L
N
LOAD
L
N
LOAD
L
N
LOAD
AFDD typical for series arcsAFDD typical for parallel arcs
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
4
Applications of Arc Fault Detection Devices (AFDD)
AFDD (Arc Fault Detection Device) is governed by the European installation standard IEC 60364-4-42 which recommends its installation in Europe in locations indicated on table left.
Germany, under its low voltage electrical installations standard DIN VDE 0100-420, has made the implementation of AFDD mandatory in locations indicated on table left starting January 2018.
Historically, GE was already manufacturing similar protection with Its equivalent in North America, the AFCI (Arc Fault Circuit Interrupter), available on the market since 1995 and mandatory in residential installations such as bedrooms since 2002).
Recommended installation acc. To IEC 60364-4-42
Premises with sleeping accommodations
Fire-propagating structures, i.e. high-rise buildings
Branch circuits with high loads, such as machines, dryers, dishwashers
Already Mandatory in Germany acc. to DIN VDE 0100-420
Woodworking, paper and textile industries
Storage areas with combustible materials
Wood buildings and Barns
Airports(1)
Railway, Subway stations(1)
National monuments, museums(1)
Public buildings(1)
Laboratories(1)
Data centers(1)
Daycare centers(2)
Retirement homes(2)
Barrier-free apartments(2)
(1) With irreplaceable goods/materials(2) To be provided in bedrooms and lounges
HIGH LOADAPPLIANCES
DATA CENTER
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
5
Maximum safety against fires…
RETIREMENT HOMES
HIGH LOADAPPLIANCES
ARCHIVES, MUSEUMS
SLEEPING ACCOMMODATIONS
DATA CENTER
WOOD STRUCTURES
Maximum safety!
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
6
(1) ceRCBOs : Voltage dependent Resiudal Current Circuit Breakers
GE Global Warranty
Complete Solution for all your local installation regulationsAF series are designed to comply with European installation standard IEC 60634-4-42 and Arc Fault Detection Device standard IEC/EN 62602 – More-over, AF devices come in top or bottom power version and Left or Right Neutral position to meet all local regulations and covered under GE‘s global warranty
Arc Fault Detection DevicesGE’s answer to the need for reliable, safe, compact and easy add-on protection devices against fire caused by arc faults in electrical installations.
Reliable. Flexible. Safe.The AF-series features in one add-on module a complete detection against fire caused by arc faults in final circuits. Installed in series with Unibis MCBs and RCBOs (2P), AF-series offer a compact and flexible alternative for new or retrofit electrical installations, meeting local electrical standards with only a few devices.
AF Series combine the following functions:• Parallel or series arc faults detection in damaged cables or
loose connections• Overheating protection of electronic components in loads
due to slow overvoltage.• Circuit opening without the need of external handle• Combined with Unibis MCBs, RCBOs (2P), ceRCBOs(1) and a
maximum rated current of 40A / 230VAC in 1 Pole/Neutral or 2 Poles circuits in full coordination under short-circuit conditions up to a rated breaking capacity (Icn) of 10,000 A.
• Top or Bottom incoming supply, Neutral right or left to meetlocal electrical installation rules.
• Manual test/reset & periodic automatic test• Self-testing function• LED status indicator – test/reset button• DIN-rail mounting and Pozidrive retained screws
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
7
FlexibleAdd-on AF devices give you the freedom to chose the most appropriate protection for your final circuits in the most compact way for your new or existing installation.
• Only 6 models needed to make all your combinations and comply with local electrical installation regulations
• Top, bottom power entry or neutral right or left positions• DIN-rail mount for quick installation• LED hazard indication for quick trouble shooting (Include RCBOs
(2P) offer additional indicator to identify ground fault tripping)• Common busbars to quickly connect AF to MCBs, RCBOs (2P),
ceRCBOs• Common Unibis auxiliary alarm contacts
GE’s compact solution gives you significant space and inventory material cost reduction and flexibility for future add-ons.
Designed for all possible combinationsGE’s AF - Arc Fault Detection Devices are well suited for the following applications:
• Premises with sleeping accommodations.• Fire-propagating structures, i.e. high-rise buildings• Branch circuits with high loads, such as machines,
dryers, dishwashers• Woodworking, paper and textile industries• Storage areas with combustible materials• Wood buildings and Barns• Airports• Railway, Subway stations• National monuments, museums• Public buildings• Laboratories• Data centers• Daycare centers• Retirement homes• Barrier-free apartments
(1) ceRCBOs : Voltage dependent Resiudal Current Circuit Breakers
CompetitiveAF series are offered as add-on devices and not as pre-assem-bled units, reducing substantially inventory to match all pos-sible combinations, wiring positions, tripping curves, ground fault sensitivity.
AF combined with ceRCBO(1) in 2 modules
FULL INSTALLATION
FLEXIBILITY & EASIER TROUBLE
SHOOTING
Up to 85% inventory cost
reduction versus units sold pre-
assembled only
AF combined with MCB in 2 modules
AF combined with RCBO (2P) in 3 modules
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
8
Product features
Examples of AFDD assemblies
Technical Characteristics• Units up to 40 A• Rated voltage 230V • Compatible with MCB, RCBO (2P) and ceRCBO Unibis range• Overvoltage protection 275VAC• Minimum operating voltage: 0.85 x Un• Maximum operating voltage: 1.1 x Un• Maximum terminal tightening torque: 3 Nm• Terminal capacity: 1 to 16 mm2 (rigid) / 1 to 10 mm2 (flexible)• Manual and periodic automatic test• Functionality compliance to IEC/EN 62606 (VDE 0665-10)• Compliance to installation practices IEC 60364-4-42
(VDE 0100-420)• Busbar compatibility• Auxiliaries availability (for MCB, RCBO (2P) and ceRCBO)• Ambient operating temperature: -25°c to 40°c• Storage temperature: -40°c to 75°c
AF - seriesLED indicator - test/reset button
AF-series LED status indication
Device OFF Blinking red Overvoltage detected
MCB + AFDD
Ground fault test button
Ground fault indicator
Ground fault test button
RCBO (2P) + AFDD
Device ON
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
9
AF - seriesLED indicator - test/reset button
Blinking yellow Arc fault detected
Blinking yellow/red Failure mode: defective unit
ceRCBO(1) + AFDD
Ground fault test button
Compactelectronic
RCBO (2P) + AFDD in
2 modules
FULL SELFTESTING DEVICE
(1) ceRCBOs : Voltage dependent Resiudal Current Circuit Breakers
Product Designation
Nomenclature
A F - # # # # - #
UNRUnibis 1P+NNeutral right1 module MCB
UNLUnibis 1P+NNeutral left1 module MCB
BLine Bottom
TLine Top
Arc Fault Detection Device
DPCUnibis RCBO (2P)2 poles2 modules RCBO (2P)
DMCEUnibis ceRCBOUnibis 1P+N electronic RCBONeutral left1 module ceRCBO
33% MORE
AVAILABLESPACE
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
10
Performance
Assembly Unibis EPC 61N
Maximum rated load Current A 40
Rated Frequency Hz 50
Rated voltage (Un) V 230
Operating voltage range 0.85Un to 1.1Un
Overvoltage protection V 275
Minimum operating voltage V 0.85 x Un (195.5)
Maximum operating voltage V 1.1 x Un (253)
Degree of protection IP20 According to EN 60529
Mains connection Bottom
Load connection Top
Max terminal tightening torque Nm 3
Maximum terminal cross-section
mm² Rigid cable (min/max) 1/16 // Flexible cable
(min/max) 1/10
Test method Manual test & periodic automatic test
Rated Short circuit current kA 6
Ambient Operating temperature ºC -25 to 40
Storage temperature ºC -40 to 75
Terminal marking Phase and Neutral terminals clearly marked to prevent wrong connection sequence
AF device power connection AF must be connected on the load side of the associated device
AF device LED status • Continuous Red – Power ON at AF device• Blinking Yellow - serial or parallel Arc fault
detected• Blinking Red - Overvoltage detected• Blinking Red and Yellow – AF device defective
Resistance to climatic conditions
28 cycles with 25-55°C/90-95% relative humidity acc. to IEC 60068-2
Dimensions 2 modules
Weight 80
Applications
Mainly used to ensure reliable, safe, compact and easy add-on protection devices against fire caused by arc faults in electrical installations.
Approvals / Marking
Add-on devicesTele U Tele L
CA CACA UN CA UN
CA UN CA UN2 x CA 2 x CATELE MP TELE MP
Tele UTele L
When coupling an add-on to the MCB, an universal CA UN auxiliary has to be coupled first as interface + rest of auxiliaries
Arc Fault Detection Device
EN/IEC 60898-1 60003
EN/IEC 60947-2 10kA
EN/IEC 62606
AF UNR B for compact MCBs (1P+N) Unibis 6kA
NEUTRAL RIGHT
LINE BOTTOM LOAD TOP
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
11
Series EPC 61N - 6kA - characteristics B-C (Neutral right)
B C
In (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
1P+N 2 EPC 61N B02 692819 EPC 61N C02 692791 121 mod. 4 EPC 61N B04 692820 EPC 61N C04 692792 12
6 EPC 61N B06 692821 EPC 61N C06 692793 1210 EPC 61N B10 692822 EPC 61N C10 692794 1213 EPC 61N B13 692604 EPC 61N C13 692795 1216 EPC 61N B16 692823 EPC 61N C16 692796 1220 EPC 61N B20 692824 EPC 61N C20 692797 1225 EPC 61N B25 692825 EPC 61N C25 692798 1232 EPC 61N B32 692826 EPC 61N C32 692799 1240 EPC 61N B40 692827 EPC 61N C40 692800 12
N
N
Series AF - UNR B
Function Cat. No. Ref. No. Pack.
2P AFDD AF UNR B 660732 1
1P + N (right) – incoming supply from the bottom
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
12
Performance
Assembly Unibis DPC100, DPC60, DPC45
Maximum rated load Current A 40
Rated Frequency Hz 50
Rated voltage (Un) V 230
Operating voltage range 0.85Un to 1.1Un
Overvoltage protection V 275
Minimum operating voltage V 0.85 x Un (195.5)
Maximum operating voltage V 1.1 x Un (253)
Degree of protection IP20 According to EN 60529
Mains connection Bottom
Load connection Top
Max terminal tightening torque Nm 3
Maximum terminal cross-section
mm² Rigid cable (min/max) 1/16 // Flexible cable
(min/max) 1/10
Test method Manual test & periodic automatic test
Rated Short circuit current kA 10
Ambient Operating temperature ºC -25 to 40
Storage temperature ºC -40 to 75Terminal marking L1/N, L2/N (2 Pole device)
AF device power connection AF must be connected on the load side of the
associated device
AF device LED status • Continuous Red – Power ON at AF device• Blinking Yellow - serial or parallel Arc fault
detected• Blinking Red - Overvoltage detected• Blinking Red and Yellow – AF device defective
Resistance to climatic conditions
28 cycles with 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Dimensions 3 modules
Weight 82
Applications
Mainly used to ensure reliable, safe, compact and easy add-on protection devices against fire caused by arc faults in electrical installations.
Approvals / Marking
Add-on devicesTele U Tele L
CA CACA UN CA UN
CA UN CA UN2 x CA 2 x CATELE MP TELE MP
Tele UTele L
0 0-OFF -OFF
When coupling an add-on to the MCB, an universal CA UN auxiliary has to be coupled first as interface + rest of auxiliaries
Arc Fault Detection Device
AF DPC B for RCBO (2P) Unibis up to 10kA
6-10 kAEN/IEC 60898-1
Type ACType A - Ai EN/IEC 62606
2 POLES
LINE BOTTOM LOAD TOP
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
13
Series AF - AF DPC B
Function Cat. No. Ref. No. Pack.
2P AFDD AF DPC B 660733 1
2P device - Incoming supply from the bottom
Series DPC60 - Type AC - characteristic C
10mA 30mA 300mAIn (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Pack.
2P 6 - - DPC60C06/030 606820 DPC60C06/300 606828 1/610 DPC60C10/010 606818 DPC60C10/030 606821 DPC60C10/300 606829 1/613 - - DPC60C13/030 606822 DPC60C13/300 606830 1/616 DPC60C16/010 606819 DPC60C16/030 606823 DPC60C16/300 606831 1/620 - - DPC60C20/030 606824 DPC60C20/300 606832 1/625 - - DPC60C25/030 606825 DPC60C25/300 606833 1/632 - - DPC60C32/030 606826 DPC60C32/300 606834 1/640 - - DPC60C40/030 606827 DPC60C40/300 606835 1/6
Series DPC60 - Type A - characteristic B
2P 6 - - DPCA60B06/030 606872 DPCA60B06/300 606880 1/610 DPCA60B10/010 606870 DPCA60B10/030 606873 DPCA60B10/300 606881 1/613 - - DPCA60B13/030 606874 DPCA60B13/300 606882 1/616 DPCA60B16/010 606871 DPCA60B16/030 606875 DPCA60B16/300 606883 1/620 - - DPCA60B20/030 606876 DPCA60B20/300 606884 1/625 - - DPCA60B25/030 606877 DPCA60B25/300 606885 1/632 - - DPCA60B32/030 606878 DPCA60B32/300 606886 1/640 - - DPCA60B40/030 606879 DPCA60B40/300 606887 1/6
Series DPC60 - Type A - characteristic C
2P 6 - - DPCA60C06/030 606838 DPCA60C06/300 606846 1/610 DPCA60C10/010 606836 DPCA60C10/030 606839 DPCA60C10/300 606847 1/613 - - DPCA60C13/030 606840 DPCA60C13/300 606848 1/616 DPCA60C16/010 606837 DPCA60C16/030 606841 DPCA60C16/300 606849 1/620 - - DPCA60C20/030 606842 DPCA60C20/300 606850 1/625 - - DPCA60C25/030 606843 DPCA60C25/300 606851 1/632 - - DPCA60C32/030 606844 DPCA60C32/300 606852 1/640 - - DPCA60C40/030 606845 DPCA60C40/300 606853 1/6
Series DPC60 - Type Ai - characteristic B
2P 6 - - DPCAi60B06/030 606888 DPCAi60B06/300 606896 1/610 - - DPCAi60B10/030 606889 DPCAi60B10/300 606897 1/613 - - DPCAi60B13/030 606890 DPCAi60B13/300 606898 1/616 - - DPCAi60B16/030 606891 DPCAi60B16/300 606899 1/620 - - DPCAi60B20/030 606892 DPCAi60B20/300 606900 1/625 - - DPCAi60B25/030 606893 DPCAi60B25/300 606901 1/632 - - DPCAi60B32/030 606894 DPCAi60B32/300 606902 1/640 - - DPCAi60B40/030 606895 DPCAi60B40/300 606903 1/6
Series DPC60 - Type Ai - characteristic C
2P 6 - - DPCAi60C06/030 606854 DPCAi60C06/300 606862 1/610 - - DPCAi60C10/030 606855 DPCAi60C10/300 606863 1/613 - - DPCAi60C13/030 606856 DPCAi60C13/300 606864 1/616 - - DPCAi60C16/030 606857 DPCAi60C16/300 606865 1/620 - - DPCAi60C20/030 606858 DPCAi60C20/300 606866 1/625 - - DPCAi60C25/030 606859 DPCAi60C25/300 606867 1/632 - - DPCAi60C32/030 606860 DPCAi60C32/300 606868 1/640 - - DPCAi60C40/030 606861 DPCAi60C40/300 606869 1/6
T
T
ES
1/2 3/4
2/1 4/3
T
T
ES
1/2 3/4
2/1 4/3
T
T
ES
1/2 3/4
2/1 4/3
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
14
Series AF - AF DPC B
Function Cat. No. Ref. No. Pack.
2P AFDD AF DPC B 660733 1
2P device - Incoming supply from the bottom
Series DPC100 - Type AC - characteristic C
10mA 30mA 300mAIn (A) Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Pack.
2P 6 - - DPC100C06/030 606906 DPC100C06/300 606914 1/610 DPC100C10/010 606904 DPC100C10/030 606907 DPC100C10/300 606915 1/613 - - DPC100C13/030 606908 DPC100C13/300 606916 1/616 DPC100C16/010 606905 DPC100C16/030 606909 DPC100C16/300 606917 1/620 - - DPC100C20/030 606910 DPC100C20/300 606918 1/625 - - DPC100C25/030 606911 DPC100C25/300 606919 1/632 - - DPC100C32/030 606912 DPC100C32/300 606920 1/640 - - DPC100C40/030 606913 DPC100C40/300 606921 1/6
Series DPC100 - Type A - characteristic B
2P 6 - - DPCA100B06/030 606964 DPCA100B06/300 606976 1/610 DPCA100B10/010 606961 DPCA100B10/030 606965 DPCA100B10/300 606977 1/6
DPCA100B13/300 606978 1/616 DPCA100B16/010 606963 DPCA100B16/030 606967 DPCA100B16/300 606979 1/620 - DPCA100B20/030 606968 DPCA100B20/300 606980 1/6
25 - - DPCA100B25/030 606973 DPCA100B25/300 606981 1/632 - - DPCA100B32/030 606974 DPCA100B32/300 606982 1/640 - - DPCA100B40/030 606975 DPCA100B40/300 606983 1/6
Series DPC100 - Type A - characteristic C
2P 6 - - DPCA100C06/030 606925 DPCA100C06/300 606937 1/610 DPCA100C10/010 606922 DPCA100C10/030 606926 DPCA100C10/300 606938 1/616 DPCA100C16/010 606924 DPCA100C16/030 606928 DPCA100C16/300 606940 1/620 DPCA100C20/030 606929 DPCA100C20/300 606941 1/6
25 - - DPCA100C25/030 606934 DPCA100C25/300 606942 1/632 - - DPCA100C32/030 606935 DPCA100C32/300 606943 1/640 - - DPCA100C40/030 606936 DPCA100C40/300 606944 1/6
Series DPC100 - Type Ai - characteristic B
2P 6 - - DPCAi100B06/030 606984 DPCAi100B06/300 606992 1/610 - - DPCAi100B10/030 606985 DPCAi100B10/300 606993 1/616 - - DPCAi100B16/030 606987 DPCAi100B16/300 606995 1/620 - - DPCAi100B20/030 606988 DPCAi100B20/300 606996 1/625 - - DPCAi100B25/030 606989 DPCAi100B25/300 606997 1/632 - - DPCAi100B32/030 606990 DPCAi100B32/300 606998 1/640 - - DPCAi100B40/030 606991 DPCAi100B40/300 606999 1/6
Series DPC100 - Type Ai - characteristic C
2P 6 - - DPCAi100C06/030 606945 DPCAi100C06/300 606953 1/610 - - DPCAi100C10/030 606946 DPCAi100C10/300 606954 1/616 - - DPCAi100C16/030 606948 DPCAi100C16/300 606956 1/620 - - DPCAi100C20/030 606949 DPCAi100C20/300 606957 1/625 - - DPCAi100C25/030 606950 DPCAi100C25/300 606958 1/632 - - DPCAi100C32/030 606951 DPCAi100C32/300 606959 1/640 - - DPCAi100C40/030 606952 DPCAi100C40/300 606960 1/6
T
T
ES
1/2 3/4
2/1 4/3
T
T
ES
1/2 3/4
2/1 4/3
T
T
ES
1/2 3/4
2/1 4/3
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
16
Performance
Assembly Unibis DMCE60NS
Maximum rated load Current A 32
Rated Frequency Hz 50
Rated voltage (Un) V 230
Operating voltage range 0.85Un to 1.1Un
Overvoltage protection V 275
Minimum operating voltage V 0.85 x Un (195.5)
Maximum operating voltage V 1.1 x Un (253)
Degree of protection IP20 According to EN 60529
Mains connection Bottom
Load connection Top
Max terminal tightening torque Nm 3
Maximum terminal cross-section
mm² Rigid cable (min/max) 1/16 // Flexible cable (min/max) 1/10
Test method Manual test & periodic automatic test
Rated Short circuit current kA 6
Ambient Operating temperature ºC -25 to 40
Storage temperature ºC -40 to 75
Terminal marking Phase and Neutral terminals clearly marked to prevent wrong connection sequence
AF device power connection AF must be connected on the load side of the associated device
AF device LED status • Continuous Red – Power ON at AF device• Blinking Yellow - serial or parallel Arc fault
detected• Blinking Red - Overvoltage detected• Blinking Red and Yellow – AF device defective
Resistance to climatic conditions
28 cycles with 25-55°C/90-95% relative humidity acc. to IEC 60068-2
Dimensions 2 modules
Weight 80
Applications
Mainly used to ensure reliable, safe, compact and easy add-on protection devices against fire caused by arc faults in electrical installations.
Approvals / Marking
Add-on devicesTele U Tele L
CA CACA UN CA UN
CA UN CA UN2 x CA 2 x CATELE MP TELE MP
Tele UTele L
When coupling an add-on to the MCB, an universal CA UN auxiliary has to be coupled first as interface + rest of auxiliaries
Arc Fault Detection Device
AF DMCE B for ceRCBO(1) neutral switched Unibis 6kA
EN/IEC 61009-1 ed 3.2 (2013-09),
BS EN 61009-1:2012 and6000
3AS/NZS EN 61009-1:2011
Type A
EN/IEC 62606
NEUTRAL LEFT
LINE BOTTOM LOAD TOP
(1) ceRCBOs : Voltage dependent Resiudal Current Circuit Breakers
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
17
Series AF - AF DMCE B
Function Cat. No. Ref. No. Pack.
2P AFDD AF DMCE B 660735 1
1P + N (left) – incoming supply from the bottom
DMCE60NS - Type A - characteristic C - Domestic application
10mA 30mAIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
1P+N 6 DMCEA60C06/010NS 694685 DMCEA60C06/030NS 694699 110 DMCEA60C10/010NS 694686 DMCEA60C10/030NS 694700 113 DMCEA60C13/010NS 694687 DMCEA60C13/030NS 694701 116 DMCEA60C16/010NS 694688 DMCEA60C16/030NS 694702 120 DMCEA60C20/010NS 694689 DMCEA60C20/030NS 694703 125 DMCEA60C25/010NS 694690 DMCEA60C25/030NS 694704 132 DMCEA60C32/010NS 694691 DMCEA60C32/030NS 694705 1
DMCE60NS - Type A - characteristic B - Domestic application
10mA 30mAIn (A) Cat. No. Ref. No. Cat. No. Ref. No. Pack.
1P+N 6 DMCEA60B06/010NS 694678 DMCEA60B06/030NS 694692 110 DMCEA60B10/010NS 694679 DMCEA60B10/030NS 694693 113 DMCEA60B13/010NS 694680 DMCEA60B13/030NS 694694 116 DMCEA60B16/010NS 694681 DMCEA60B16/030NS 694695 120 DMCEA60B20/010NS 694682 DMCEA60B20/030NS 694696 125 DMCEA60B25/010NS 694683 DMCEA60B25/030NS 694697 132 DMCEA60B32/010NS 694684 DMCEA60B32/030NS 694698 1
N L
T
N L
N L
T
N L
(1) ceRCBOs : Voltage dependent Resiudal Current Circuit Breakers
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
18
Accessories
Tele L - Shunt trip
Voltage Cat. No Ref. No. Pack.
1P AC 24-60V / DC 24-48V TELE L-1 672573 11 mod.
AC 110-415V / DC 110-125V TELE L-2 672574 1
Tele U - Undervoltage release
Voltage Cat. No Ref. No. Pack.
1P AC 240V TELE U-230 672575 11 mod. AC/DC 12V TELE U-12 672576 1
AC/DC 24V TELE U-24 672577 1AC/DC 48V TELE U-48 672578 1
Tele MP - Motor operator
Voltage Cat. No Ref. No. Pack.
3 mod. AC 230V TELE MP 672580 1
Series CA UN - Unibis Interface
Function Cat. No Ref. No. Pack.
1/2 mod. H CA UN H 672972 1/40S/H CA UN S/H 672973 1/40
S/H (golden contacts) CA UN S/H G 672974 1/40
H S
Busbars
1 meter busbars entry: Cat. No Ref. No. Pack.
1P+N (9mm)//distribution 1P+N (9mm) 1 mod. Free space for AFDD
BS2AFDUNMCB 625063 1
3P+N (9mm)//distribution 3P+N (9mm) 1 mod. Free space for AFDD
BS3NAFDUNMCB 625064 1
1P+N / 2P (18mm)//distribution 1P+N / 2P (18mm) 1 mod. Free space for AFDD
BS2AFDUNRCBO 625065 1
3P+N (18mm)//distribution 3P+N (18mm) 1 mod. Free space for AFDD
BS3NAFDUNRCBO 625066 1
AF series
Arc
Fau
lt D
etec
tion
Dev
ices
19
Dimensional drawings
AF series - AF UNR B AF series - AF DPC B
AF series - AF DMCE B
17.8
53.4
92.1
861. 29
35.6
17.8
86
1.29
35.6
17.8
86
AF seriesA
rc F
ault
Det
ectio
n D
evic
es
20
Dimensional drawings
Compact MCBs - Series EPC - Unibis*
Auxiliary interface - Series CA UN (Unibis)
Compact RCBOs (2P) - Series DPC - Unibis* ceRCBO - Series DMCE
Undervoltage Release - Tele U
Auxiliary - Series CA
Shunt Trip - Tele L / Tele LT
Motor operator - Tele MP
2/1
1/2
4/3
3/4
36
72
AF series
21
The policy of GE Energy Connections is one of continuous improvement.The right is reserved to alter the design or any structural details of the products at any time without giving notice.
September 2018GE Energy Connections
GE
DEA1024-NLEd. 10/18
* Trademark of General Electric Company © Copyright GE Energy Connections 2018
Since Thomas Edison patented the world’s first circuit breaker, Industrial Solutions has been transforming the future of electrification. We design electrical solutions at the crossroads of digital and industrial – smart, rugged and equipped to control electricity from the grid to its point of use. Every day, we partner with our customers to solve their toughest energy challenges and reimagine industry in a way that only the world’s digital industrial company can.
nl.geindustrial.com
NetherlandsABB Industrial Solutions Parallelweg 10NL-7482 CA Haaksbergen Tel. +31 (0)53 573 03 03
Recommended