ALSTOM_Interruptores Vacio.pdf

Preview:

Citation preview

  • 8/13/2019 ALSTOM_Interruptores Vacio.pdf

    1/2

    Features

    High number of mechanical andelectrical operating cycles

    No critical current range Long service life High reserve in the switching

    capacity Minimum maintenance require-

    ments

    Vacuum circuit-breakers are used forswitching: rated short-circuit breaking

    currents partial load currents unbalanced breaking currents capacitor banks unloaded cables and overhead

    cables unloaded transformers.

    Vaccum circuit-breakers types VAand VAA are front-mounted switches

    for installation in medium-voltageindoor switchgear. They may befixed mounted in switchgear or ona switchgear truck. In railway ope-ration single-pole or two-pole vacu-um circuit-breakers type VXA, VXBare employed. The vacuum circuit-breakers type VXC, which are de-signed for especially high mechani-cal and electrical switching cycles,are highly suitable for switchingelectrical smelting furnaces. Vacuumcircuit-breakers are suitable for swit-ching in all cases of need in indu-stral plants, distribution networks aswell as in railway operation.

    The vacuum circuit-breakers are fit-ted with an energy-storing drive for

    manual or electrical tensioning andoptionally for fast auto-reclosure.

    Depending on requirements, thevacuum circuit-breakers may be pro-vided with auxiliary switches, auxili-

    ary current releases and under-volta-ge releases.

    Solid pole supports mean that hevacuum chambers are not exposedto external forces. This stacionallyclosed arrier system means that theaxial forces which occur duringmaking and breaking proceduresonly act on the contact system, lea-

    ving the switching chamber housingunaffected.

    Vacuum circuit-breakers VA, VAA, VXA, VXB, VXC

    Vacuum circuit-brekers for all switching applications in industrial plants, in distribution networksand for use primarily on railways.

    Vacuum circuit-breaker VAA Vacuum circuit-breaker VXC

    Vacuum circuit-breaker VXA

  • 8/13/2019 ALSTOM_Interruptores Vacio.pdf

    2/2

    Specificatios

    The vacuum circuit-breakers con-

    tained in this list comply with thespecifications for AC switching de-vices for voltages above 1 kV incompliance with VDE 0670, parts101-108, IEC Publication 60056,BS 5311 and NF-C 64, CSA andVE. The vacuum circuit-breakerscomply to a great extent with theUS standards ANSI C 37.06 aswell as NEMA Standards Publica-tion No. SG4 and are suitable for

    normal service conditions in accor-dance with VDE 0670, part 1000and IEC Publication 60694.

    Tests

    Vacuum circuit-breakers have pro-

    ved their suitability in the type testand in numerous series of testsduring development. The tests wereperformed in our own test shopsand by impartial institutes like FGHand KEMA. The tests covered notonly conformity with the type tests inaccordance with specifications butalso numerous special requirementsas well as determining the life cha-racteristics of the switching cham-

    bers and their suitability for type-tested switchgear and controlgear;in addition they were subjected tonumerous network tests. The reliabi-lity, safety and mechanical functionsof the switching devices were testedin duration tests.

    Ratings Rated Rated Rated Rated Switching cycles without inspectionvoltage current short-circuit short-circuit

    making breakingcurrent current Drive Chamber Chamber

    up to up to up to with In

    1) with Isc

    1)

    Type kV A kA kA up to up to up to

    VAA 12 1250 63 25 10 000 30 000 100

    VA 12 3150 125 50 10 000 30 000 100

    VAA 17,5 1250 63 25 10 000 30 000 100

    VA 17,5 3150 80 31,5 10 000 30 000 100

    VAA 24 1250 63 25 10 000 30 000 100

    VA 24 2500 63 25 10 000 30 000 100

    VA 36 2500 80 31,5 10 000 30 000 100

    VXA single pole 17,52) 2500 100 40 10 000 10 000 100

    VXA single pole 27,5 1600 80 31,5 10 000 10 000 100

    VXB two pole 27,5 2000 80 31,5 10 000 10 000 100

    VXC 24 2500 63 25 25 000 25 000 100VXC 36 2500 80 31,5 25 000 25 000 100

    1) In = Rated current, Isc = Rated short-circuit breaking current

    2) 16 2/3 Hz

    ALSTOM Sachsenwerk GmbH Rathenaustrae 2 D-93055 Regensburg P.O.B. 10 01 55 D-93001 RegensburgTelephone +49 (0)9 41/46 20-0 Telefax +49 (0)9 41/46 20-4 18

    Switchgear panel WBB

    with vacuum circuit-

    breaker mounted on a

    truck

    Switchgear panel WBA

    with vacuum circuit-

    breaker mounted on a

    truck

    T&D/LEAF/VA/uke/PDB/07.01/GER/2419/ALSTOM2001/ConceptundCreation:SCHREMLW

    erbeagentur

    SW.0

    7.19/0701E