6- CABLE-1-Model

Preview:

Citation preview

  • 230V AC

    110V DC

    110V DC

    VOLTAGE

    230 V AC

    14

    13

    AC DISTRIBUTION BOARD

    LT SUPPLY TRANSFORMAR TO

    15A DC FUSE BOX TO

    TERMINAL BOARD

    SUPPLY

    AC POWER

    -DO-

    12

    11

    6

    4,5

    1,2,3

    REFNo

    110 V BATTERYCHARGER

    AC DISTRIBUTION BOARD

    FROM 110 V BATTERY SET TO

    15A DC DISTRIBUTION BOARD

    FUSE BOX AND FUSE BOX TO

    TO 110V BATTERY

    FROM INTREUPTOR TO

    SUPPLYDC POWER

    -DO-

    -DO-

    FROM INTERRUPTOR

    FROM INTERRUPTOR TO INTERRUPTOR

    TO TERMINAL BOARD

    RUN OF CABLE

    CONTROL

    SUPPLYHEATER

    INDICATION&

    PURPOSE

    2CORE 25 sqmm ARMOURED CABLE WITH ALUMINIUM CONDUCTORSPVC INSULATED AND SHEATED.(1100 V GRADE)

    -DO- -DO-

    -do-16m

    -do- 6m

    (1100V GRADE)

    -DO-

    2CORE 2.5 sqmm UNARMOURED

    PVC INSULATED AND SHEATED.CABLE WITH COPPER CONDUCTORS

    (1100V GRADE)

    -DO-

    -DO-

    -DO-

    TWO RUN OF CABLE

    PVC INSULATED AND SHEATED.WITH ALUMINIUM CONDUCTORS2 CORE 4.0 sqmm UNARMOURED CABLE

    DETAILS OF CABLE

    CABLE WITH COPPER CONDUCTORSPVC INSULATED AND SHEATED.

    7 CORE 2.5 sqmm UNARMOURED

    (1100V GRADE)

    -do-

    -do-

    5m

    6m

    -do-

    58.50mIS1554

    -do-

    (PT-1)1976

    24m

    SPEC . LENGTHIN METERS

    APPROX

    FROM PT TYPE-1

    TO TERMINAL BOARD.

    2 CORE, 2.5 sqmm UNARMOUREDCABLE WITH COPPER CONDUCTORSPVC INSULATED AND SHEATHED(1100V GRADE)

    100V ACCATENARYVOLTAGE

    INDICATION7,8,9,1032m-do-

    1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE SPECIFIED.

    2. WHEREVER 50X6 EARTHING FLATS ARE WELDED, THE MS. SURFACES OF JUNCTIONS SHALL BE SCRAPPED OUT

    BEFORE WELDING AND SHALL BE TREATED FOR ANTICORROSION AS PER STANDARD PRACTICE.3. RESISTANCE OF HT EARTH CIRCUITS SHALL BE LESSTHAN 2 OHMS.4. THE MS FLATS FORMING THE HT EARTH BUS SHALL BE BURRIED AT A DEPTH OF 300 mm BELOW GROUND LEVEL

    AND LT EARTH BUS SHALL BE FIXEDTO WALL INSIDE THE CUBICLE AT THE HEIGHT OF 300 mm FROM FLOOR LEVEL

    5. RESISTANCE OF LT EARTH CIRCUIT SHALL BE LESSTHAN 2 OHMS.6. FOR ARRANGEMENT OF SINGLE &MULTIPLE EARTHING STATIONS REFER STY NO 01&02 OF DRG NO ETI OHE/P/7020. 7. IF NECESSERY, EARTHINGSTATIONS SHALL BE ADDED IN PARALLEL TO BRING DOWN THE EARTH RESISTANCE

    9. IF NECESSARY EARTHING STATIONS SHALL BE ADDED IN PARALLEL TO BRINGDOWN THE EARTH RESISTANCE

    8. THE MS FLATS SHALL BE PAINTED WITH TWO COATS OF REDOXIDE ZINC CHROMATE PRIMER AND FINISHED WITH

    MEANS OF 2 Nos.OF 8 SWG GI WIRES.

    NOTES

    WITH SUITABLE SUPPORTING ON TEAK WOOD BLOCKS

    LESS THAN 2 OHMS

    TWO COATS OF BITUMEN.

    TO LESS THAN 2 OHMS10. EARTHING OF BATTERY CHARGER, RC PANEL AND L.T. DISTRIBUTION BOARD SHALL BE DONE BY

    REINDIAN RAILWAYS