2006 User Conference
Safety System Simulation : Using the Virtual Process Link
& Technology Fair
gwith Prosafe RS
Winston Jenks / Cedric OudinotTechnical Dir / Marketing Mgrg g
November 28, 2006
Company Logo
• Privately owned software company
A word about Cape SoftwareYokogawa Technology Innovations Fair & User Conference
• Privately owned software company– HQ in Houston, TX
• Over 15 years of experience in the process simulation y p parena delivering high quality process models
• Three Products:VP Li k ( O t T i i )– VP Link ( Operator Training)
– Test Compiler ( Logic Validation)– XP TrendCorder ( Hi-speed process trending & archiving)
• End users from:– Oil and Gas
Chemicals– Chemicals– Pharmaceuticals– Integrators
Page 2
TitleNov/Dec 2006
• Provide tools to improve FAT execution
What are we trying to do?Yokogawa Technology Innovations Fair & User Conference
• Provide tools to improve FAT execution– 21st Century Software version of HW panel– Multi-user interface allows teams to work simultaneously– Can check logic/communication in multi-vendor systems
• Provide value for the customer during Safety Lifecycle• Provide value for the customer during Safety Lifecycle– Adhere to OSHA and IEC Testing Standards– Use a Structured Test Procedure– Test Procedure generates documentation and Test Scripts– Running the tests produces electronic test logs– Stored tests are run periodically to revalidate logicp y g– Enable integrated training with DCS
Page 3
TitleNov/Dec 2006
What is Process S(t)imulationYokogawa Technology Innovations Fair & User Conference
A dynamic representation of a complex process to an offline control systemp y
Read value of outputs VP Link Server
EngineeringWorkstation
CalculateProcessVariables
Write simulated inputs
Page 4
TitleNov/Dec 2006
VP Link / Prosafe RS InterfaceYokogawa Technology Innovations Fair & User Conference
• Extraction Utility builds VP Link database• Non-invasive
– Positively No change to safety application– Connects at the I/O level to allow for full
f i l ifunctional testing
• Connects to :“ l” t ll– “real” controller
– Emulated PC controller ( Simulation Mode)
• No limits on number of points or controllers• No limits on number of points or controllers
Page 5
Logic Validation with VP Link on Prosafe RSNov/Dec 2006
VP Link / Prosafe RS InterfaceYokogawa Technology Innovations Fair & User Conference
Test Types
Page 6
Logic Validation with VP Link on Prosafe RSNov/Dec 2006
VP Link / Prosafe RS InterfaceYokogawa Technology Innovations Fair & User Conference
VP Link Connection
Page 7
Logic Validation with VP Link on Prosafe RSNov/Dec 2006
VP Link / Prosafe RS InterfaceYokogawa Technology Innovations Fair & User Conference
Virtual Test mode• Security – None requiredy q• Locking
– Input locking not required, I/O is not connected– Internal variable locking is required
• Data Source– Inputs -- Logical values are written– Outputs -- Logical values are read
Page 8
Logic Validation with VP Link on Prosafe RSNov/Dec 2006
VP Link / Prosafe RS InterfaceYokogawa Technology Innovations Fair & User Conference
Target Test Mode• I/O values are forced• Normal security of Prosafe is enforced on SCS
Page 9
Logic Validation with VP Link on Prosafe RSNov/Dec 2006
V-Approach methodology:towards error-free safety logic on a new project
Yokogawa Technology Innovations Fair & User Conference
Safety Requirement
Pre Start-Up Safety
Narrative
Spec
Run manualTests
Review
Cause & Develop
Tests
Effect
Function Bl k
Black Box
Scenarios
BlockDesign
Functional
Testing
Deliverable
Page 10
Logic Validation with VP Link on Prosafe RSNov/Dec 2006
Functional LogicVerification
I have a functional SIS already!Yokogawa Technology Innovations Fair & User Conference
OSHA 29 CFR P t 1910OSHA 29 CFR Part 1910Emergency Shutdown systems :Document each inspection and test, including:
-Date of testN f h f d th t t [ ]
IEC-61511-116.3.1.1: Periodic proof test shall be conducted using a written
-Name of person who performed the test [..]-Description of test results
conducted using a written procedure to reveal undetected faultsOur Answer ?
IEC 61508
Test CompilerIEC-61508Part 1,7.18: Information on the verification activities shall be collected and documented as evidence that the phase being verified has, in all respects, been satisfactorily completed.Part 1,7.14 :Documentation for validation shall include:
A ti iti i h l i l d
Page 11Logic Validation with VP Link on Prosafe RSNov/Dec 2006
-Activities in chronological order-Discrepancies between expected and actual results
VP Link Test CompilerYokogawa Technology Innovations Fair & User Conference
• Generates Test Scripts, using an Excel front-end• Scripts Based on User Test Plan and Functional p
Specifications• A Script is a stand alone entity that AUTOMATICALLY :
F i t t ifi d St t– Forces inputs to a specified State– Compares the outputs to the expected state table ( Cause and
Effect Matrix)– Logs errors to HTML format
• Runs and documents entire test plan unattendedR lt S i tilit• Results Summarizer utility
• Scenario Template Generator
Page 12
TitleNov/Dec 2006
Test Compiler Input FormatYokogawa Technology Innovations Fair & User Conference
• Similar to a Cause and Effect Matrix• Similar to a Cause and Effect Matrix• Verify ALL output changes, not just one prescribed by test• High Level language and keywords for maximum flexibility
– Sequence– Interlocks / SD / Fire & Gas
Page 13
TitleNov/Dec 2006
Test Compiler output (1): DocumentationYokogawa Technology Innovations Fair & User Conference
HTML Test descriptionD:\tb40\Books\Refinery\BMS.xls[templates]
Source
Documentation created: Jun 19, 2003 at 13:08Source File: D:\tb40\Books\refinery[template] last modified Jun 19, 2003 at 13:03Purpose:This scenario will: Start Heater Purge and Verify Purge CompletionVP Database:This scenario is designed to run with the database in refinery 5.cfg. Click on these links for the list of input and
History
Database
This scenario is designed to run with the database in refinery_5.cfg. Click on these links for the list of input and output tags. If this scenario was built from a template, then the tags will be listed, but they will be marked as "not found".Defaults:The standard delay inserted before values are checked is 0 seconds for this scenario. The relative tolerance used in the test for equality is 0.002 %. Values in SET_HI and SET_LO commands are set 1 units above or below the alarm value specified in the Excel sheet.
Global Parameters
v ue spec ed e ce s ee .Scenario Actions:…… Turn i17HS0669B OFF, Field Trip for Heater
Line 4(Row 6): Set i17HS0669B to the OFF state. Set i17XSC1971 to the OFF state. Wait for seconds beyond the standard delay before continuing
Scenario Steps standard delay before continuing.
Line 5(Row 7): Set i17HS0669B to the ON state. Set i17XSC1971 to the ON state.… Get Heater Ready to Purge… Set Level i17LT1641 to 10Line 8(Row 10): Set i17LT1641 to 10.
ETC
p
Page 14TitleNov/Dec 2006
ETC….
Test Compiler output (2): Test Result LogYokogawa Technology Innovations Fair & User Conference
Scenario Log Sample0 Starting test 'D:\TB40\BOOKS\FLINT\PLC5\H1_BRNR.SCE'
at Wed May 28 18:23:48 20031181 # …1181 # … 17H-1 Start Main Burner Sequence1181 # … Satisfy and Reset Fuel Gas Trip1181 # … Turn i17HS1964, i17HS1964A ON to Satisfy FG Trip5397 # … Turn i17HS1964RST ON to Reset FG Trip9614 # T i17HS1923 ON t St t M i B
Time stamps9614 # … Turn i17HS1923 ON to Start Main Burner13830 # Test at line 10 of 'H1_BRNR.SCE' ON i17HS192313830 Verification <i17XY1904> = 1.000000 passed13830 **Verification <i17XY2419> = 1.000000 FAILED Value is 0.00000013830 Verification <i17YL1906> = 0.000000 passed13830 Verification <i17XY1907> = 0 000000 passed13830 Verification <i17XY1907> 0.000000 passed13830 Verification <i17YL1921> = 0.000000 passed13830 # …13830 Closing test log after 0 mins 13.8 secs at Wed May 28 18:24:02 2003
0 Starting test 'D:\TB40\BOOKS\FLINT\PLC5\H1_BRNR.SCE'
Assertion passed
at Wed May 28 18:26:34 2003851 # …851 # … 17H-1 Start Main Burner Sequence851 # … Satisfy and Reset Fuel Gas Trip
Assertion Failed
Page 15
TitleNov/Dec 2006
• BASF Site
Case StudyYokogawa Technology Innovations Fair & User Conference
– 7 SIS systems– Running for 5 years
Upcoming turnaround needs to revalidate all logic SIS up to specs– Upcoming turnaround, needs to revalidate all logic SIS up to specs
• User led Cost Analysis study between:– Option 1: Manual re-certification ( considering C&E/documentations
not up to date), including man-hours only (no resource constraint)– Option 2: Automating entire test plan using Test Compiler®
• Results:– Option 1: not feasible, 10% costlier than option 2 and one-shot
O i 2– Option 2:• Independent third party validation• Reusable change management tool for periodic testing• Fully Automated• Always Up to date Test Plan
Page 16
TitleNov/Dec 2006
• VP Link is a proven in use solution for logic
ConclusionYokogawa Technology Innovations Fair & User Conference
• VP Link is a proven in-use solution for logic validation– It is cross platform (DCS/PLC/SIS)
• Quadlog• Quadlog• CS3000• ProsafeRS
– It is easy to use, learn and maintain (graphic oriented)
• Test Compiler makes compliance with IEC 61508 & 61511 a PLANT REALITY
• Versatile, VP Link is also used for Operator Training– High-fidelity simulation blocks available– Trainee performance assessment module– Actual graphics/control applications used in native control
environmentLow Total Cost of Ownership– Low Total Cost of Ownership
Page 17
TitleNov/Dec 2006
BackupYokogawa Technology Innovations Fair & User Conference
BACK UP SLIDESBACK-UP SLIDES
Page 18
Logic Validation with VP Link on Prosafe RSNov/Dec 2006
Simulation Screen ShotsYokogawa Technology Innovations Fair & User Conference
Automated Tag sheet
Input/Output sheets per ESD
HMI for advanced testing t i ior training
Page 19
TitleNov/Dec 2006
VP Link for Yokogawa CS3000 / Prosafe RSYokogawa Technology Innovations Fair & User Conference
Trainer Station
VP Link/ CS3000 InterfaceExa OPC
Serverwith VP3 driver
Redundant
with VP3 driver
VP Link/RSInterfaceRedundant
Ethernet /V-NetInterface
ProSafe RS HIS
Page 20
TitleNov/Dec 2006
ProSafe RSController or emulated
Trainee Station
FCS Controllers (or emulated in Test Function)
VP Link for Yokogawa CS3000 / Prosafe RSYokogawa Technology Innovations Fair & User Conference
VP Li k D i ll h l ki VP Link Driver allows you to set the locking strategy depending on which target you useuse
Page 21
TitleNov/Dec 2006
VP Link for Yokogawa CS3000 / Prosafe RSYokogawa Technology Innovations Fair & User Conference