1 HVACR214 – Electrical for Oil Oil Solenoid Valves

Preview:

Citation preview

1

HVACR214 – Electrical for Oil

HVACR214 – Electrical for Oil

Oil Solenoid ValvesOil Solenoid Valves

2

The Solenoid ValveThe Solenoid Valve

• A solenoid valve is an electronic valve.• A coil of wire is energizes and creates

magnetism.• The magnetism either opens or closes a

valve.• A valve that is open when de-energized is

considered a normally open valve.• A valve that is closed when de-energized is

considered a normally closed valve.

• A solenoid valve is an electronic valve.• A coil of wire is energizes and creates

magnetism.• The magnetism either opens or closes a

valve.• A valve that is open when de-energized is

considered a normally open valve.• A valve that is closed when de-energized is

considered a normally closed valve.

3

The Solenoid ValveThe Solenoid Valve

• Used in both older and newer high pressure burners.– Older burners this is a field installation– Newer burners this valve is included with the burner

• The valve has two purposes– Delay the flow of oil to the burner at startup– Provide a clean shutoff of the flow of oil at

shutdown.

• Used in both older and newer high pressure burners.– Older burners this is a field installation– Newer burners this valve is included with the burner

• The valve has two purposes– Delay the flow of oil to the burner at startup– Provide a clean shutoff of the flow of oil at

shutdown.

4

Solenoid ValveSolenoid Valve

5

Solenoid ValveSolenoid Valve

6

Delay at startDelay at start

• The oil pump is set at 100psi or 140psi in most cases.

• This pressure is based upon the burner motor operating the pump at full RPMs.

• There is a brief period at the start of the burner cycle that the motor, pump, and air fan are not moving at full speed.

• Thus, the oil delivered to the combustion chamber would not be at the correct pressure or velocity.

• The oil pump is set at 100psi or 140psi in most cases.

• This pressure is based upon the burner motor operating the pump at full RPMs.

• There is a brief period at the start of the burner cycle that the motor, pump, and air fan are not moving at full speed.

• Thus, the oil delivered to the combustion chamber would not be at the correct pressure or velocity.

7

Delay at startDelay at start

• The oil solenoid valve remains closed until the burner motor, the burner fan, and the pump all reach the correct operating speeds.

• The solenoid then opens and allows the correct pressure and air mixtures to occur in the combustion chamber.

• This can also be used as a pre-purge in high efficiency boilers.

• If used as a pre-purge the primary control must be setup for this pre-purge or it will trip.

• The oil solenoid valve remains closed until the burner motor, the burner fan, and the pump all reach the correct operating speeds.

• The solenoid then opens and allows the correct pressure and air mixtures to occur in the combustion chamber.

• This can also be used as a pre-purge in high efficiency boilers.

• If used as a pre-purge the primary control must be setup for this pre-purge or it will trip.

8

Delay at startDelay at start

• If you are at a customers oil furnace or boiler and are not able to solve a rough ignition problem through setting of pressures, cleaning, and air adjustment install an oil solenoid valve and the problem will go away.

• If you are at a customers oil furnace or boiler and are not able to solve a rough ignition problem through setting of pressures, cleaning, and air adjustment install an oil solenoid valve and the problem will go away.

9

Clean shutoffClean shutoff

• When the call for heat is complete the burner shuts down.

• There is a brief period of time where the pump is not delivering the correct oil pressure to the nozzle.

• The oil will “drip” out of the end of the nozzle and cause a buildup of carbon on the end of the nozzle and in the combustion chamber.

• When the call for heat is complete the burner shuts down.

• There is a brief period of time where the pump is not delivering the correct oil pressure to the nozzle.

• The oil will “drip” out of the end of the nozzle and cause a buildup of carbon on the end of the nozzle and in the combustion chamber.

10

Clean shutoffClean shutoff

• The use of the oil solenoid valve causes a clean shutoff. The valve will close at the end of the call for heat and before the pump and burner loose pressure.

• The use of the oil solenoid valve causes a clean shutoff. The valve will close at the end of the call for heat and before the pump and burner loose pressure.

11

Mechanical installationMechanical installation

• The oil solenoid valve is placed on the jet line between the oil pump outlet and the nozzle assembly.

• You will need a second ¼” line to complete this installation.

• The oil solenoid valve is placed on the jet line between the oil pump outlet and the nozzle assembly.

• You will need a second ¼” line to complete this installation.

12

Electrical InstallationElectrical Installation

• For clean shutoff purposes the oil solenoid valve is wired to the burner motor line from the primary control.

• Do not wire to a the ignition transformer line if separate on the control as the ignition transformer may not be operational through the entire cycle.

• For clean shutoff purposes the oil solenoid valve is wired to the burner motor line from the primary control.

• Do not wire to a the ignition transformer line if separate on the control as the ignition transformer may not be operational through the entire cycle.

13

Electrical InstallationElectrical Installation

14

Electrical InstallationElectrical Installation

• For a delayed ignition or pre-purge you must either:– Use a primary control that has a separate line for

the solenoid valve.– Use a solenoid valve with an internal delay

timer.

• Make sure you test any installation prior to leaving the job. Run it through several cycles to be sure the delay will not trip the CAD cell safety.

• For a delayed ignition or pre-purge you must either:– Use a primary control that has a separate line for

the solenoid valve.– Use a solenoid valve with an internal delay

timer.

• Make sure you test any installation prior to leaving the job. Run it through several cycles to be sure the delay will not trip the CAD cell safety.

15

Electrical InstallationElectrical Installation

Recommended